NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

ORTHOPEDIC CLINIC 300
04110 BRIARGATE PKWY

Review DateStatusComment(s)
12/23/2013 FYICHEMICAL INVENTORY, AS DECLARED SEE ELECTRONIC DOCUMENTS SMALL QUANTITIES Phone call with Mr. Nelson 12/23/13 Amounts are below permit threshold amounts discussed 25 gal. flamm or comb liquids which are primarily what facility has flammable liquid storage cabinets ALL MATERIALS ARE STORED AND USED IN THE LAB 2-348 VENT HOODS
FYICONTROL AREAS, AS SHOWN ON THIS SUBMITTAL ARE AS FOLLOWS NONE
FYILabeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
FYIA minimum of 2 sets of Material Safety Data Sheets (MSDS), hard copy, must be readily availiable on the premises at all times.


 