RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

CALLAHAN PEDIATRIC DENTAL
13335 VOYAGER PKWY

Review DateStatusComment(s)
12/13/2013 FYIRESUBMITTED: The plans have been re-submitted, and the disapproved issues have been addressed as follows: APPROVED **PLEASE NOTE** ALL COMMENTS FOUND ON PREVIOUS PLAN REVIEWS REMAIN ENFORCEABLE UNLESS OTHERWISE NOTED IN THIS REVIEW. See comments below. OK
E-MailTHIS SUPPLY SOURCE ROOM IS A One-hour Interior room: Automatic sprinkler(s) shall be installed within the room. [Ian Frazier] keynote 36 on sheet 1M-3 of original submittal reads, "Install new sprinkler head, and connect to the potable water pipe with 1" pipe as shown, complete with backflow preventer as Indicated. Sprinkler head shall be a dry pendant type, installed in a manner preventing freezing. Install backflow prevention device in the new sprinkler line as shown. Pipe dumping port to the adjacent mop sink. Backflow prevention device: Watts model 9D-M3 back?ow preventer with Intermediate atmospheric vent, or Febco 805-Y-BV reduced pressure backflow preventer. The room shall be exhausted through a duct to the exterior. Supply and exhaust ducts shall be enclosed in a 1-hour-rated shaft enclosure from the room to the exterior. [Ian Frazier] Wall type #2 on sheet G1.1 of the original submittal graphically depicts (and provides construction materials list for) the UL listed, 1 hour rated wall that the medical gas closet will be constructed of. The gas closet itself provides the 1 hour rated shaft. Sheet 1M-2 shows the supply and exhaust located within the walls of the 1 hour rated gas closet. Keynotes 26, 27 & 28 describe the supply and exhaust system used. Approved mechanical ventilation shall comply with the International Mechanical Code and be provided at a minimum rate of 1 cubic foot per minute per square foot [0.00508 m3/(s o m2)] of the area of the room. [Ian Frazier] See Keynote 26 on sheet 1M-2 *** PPRBD mechanical dept has not reviewed and released plans. Ensure that Mechanical has reviewed 1 hr rated room and compliance with above. RESUBMIT TO CSFD HAZMAT FOLLOWING REVIEW AND RELEASE BY PPPRBD MECHANICAL FOR THE MEDGAS ROOM [Ian Frazier] I assume that the PPRBD mechanical plans examiner has reviewed the plans in accordance his/her expertise and with the mechanical code. **** PLEASE INDICATE SPRINKLER HEAD TYPE AND INSTALLATION WITHIN THIS ROOM. [Ian Frazier] See response above for sprinkler type IT HAS NOT BEEN NOTED ON THE PLAN SET. *** Ensure that door and assembly is rated for a one hr room[Ian Frazier] The gas closet door is door #111. On sheet A0.2 of the original submittal the "Door and Frame Schedule" lists door #111 as being a 60 min. (1hr) rated door. The hardware set for door #111 reads, "Hardware Set: 05 DOOR NUMBER: 111 Each To Have: Qty Description Catalog Number Finish Mfr 1 EA HINGE 3CB1 4.5 X 4.5 NRP - AT TOP HINGE 652 IVE 3 EA SPRING HINGE 3SP1 4.5 X 4.5 652 IVE 1 EA ENTRANCE LOCK AL53PD NEP 626 SCH 1 SET SEALS 5050B HEAD AND JAMBS BRN NGP 1 EA DOOR BOTTOM 220SA CL NGP
11/26/2013 FYICallahan Pediatric Dental, 13335 Voyager Suite 100: interior remodel SYSTEMS: None CN:Code: 09 IBC - 09 IFC - 11 PPRBC /Class: B / Const:V-B /Stories1: /Size: 1656 /OL: TBD MED GAS SOURCE SUPPLY STORAGE ROOM #111 ATTENTION: See our web site for our latest plan review comments for your job at: www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work.
FYIMED GAS SYSTEMS These requirements shall apply to all facilities described in Section 3006.1 of the 2009 International Fire Code. **The requirements of NFPA 99 will apply to all piped Med Gas Systems, including Oxygen, Nitrogen Oxides, Waste Gas, Medical Air and Vacuum based on their LEVEL Designation (1, 2 or 3) as defined by NFPA 99. All Med Gas (piped) systems shall be installed and maintained in accordance with all applicable provisions of 2009 International Fire Code Chapters 27 (Hazardous Materials), 30 (Compressed Gases) and 40 (Oxidizers). **Oxidizing Cryogenic fluids shall comply with IFC 2009 Chapter 32 and NFPA 55. **All Med Gas (piped) systems that utilize a source of commonly located compressed gas cylinders as shall have all cylinders, related manifolding and electronics (if electronic monitoring required by NFPA 99) in a room that complies with 2009 IFC Section 3006 (or) gas cabinets that comply with 3006.3. **No declaration of the Med Gas Level (category) Designation has been provided on plan set. -This facility will fall under the definition of a "Medical/Dental Office" (3.3.108) provided that only sedation or local anesthesia is involved and treatment or procedures DO NOT render the patient incapable of self-preservation under emergency conditions, and that overnight stays for patients (or 24 hour operation) ARE NOT provided** -If the above statement is true in all respects regarding this facility, the CSFD will consider the medical gas systems within to be CATEGORY LEVEL 3, as defined by NFPA 99. All applicable provisions of NFPA 99 are required to be conformed with.
AttentionSPRINKLER HEAD IN A ONE HOUR FIRE RATED ROOM FOR MEDICAL GAS STORAGE/USE ** A single ordinary temperature, quick response sprinkler head from the domestic water supply after the building's back flow preventer in non sprinkle red building where the room does not exceed 24 square feet. ** This line shall have a quarter turn isolation valve to facilitate changing the head. ** This valve must be chained and locked in the open position and be labeled indicating the valve function. ** No Design area calculations or sprinkler reviews are required for this configuration. ** A minimum of 40 degrees F must be maintained in this room and anywhere the water supply piping is run.
FYICHEMICAL INVENTORY, AS DECLARED. NITROUS OXIDE = 977 CF OXYGEN = 502 CF 1,479 cf = total OXIDIZING GASES BELOW THE MAQ FOR UNSPRINKLERED BUILDING (1,500 CF). OK **********ATTENTION********* THIS FACILITY EXCEEDS THE HAZARDOUS MATERIALS PERMIT AMOUNT FOR OXIDIZNG GASES @ 504 CF. ******** THIS FACILITY IS REQUIRED TO ENROLL AND APPLY FOR AN ANNUAL OPERATIONAL HAZARDOUS MATERIALS PERMIT THE CSFD. ***** APPLICATION IS VIA THE CSFD ON LINE WEBSITE @ https://hammers.springsgov.com/submit
FYINFPA 99, CATEGORY LEVEL 3- PIPED GAS & VACUUM SYSTEMS Including, but NOT LIMITED TO: -Door Labeling per 5.3.3.1.5 -Operational considerations per 5.3.3.2 and 5.3.3.3 -Valving, connections, components, manifolding, etc. per 5.3.3.4 and 5.3.4 -An alarm system per 5.1.9 as excepted by 5.3.9.1 -Special piping per 5.3.10 -Installation of piping per 5.3.10.3 thru 5.3.10.10 -Qualified Installers per 5.3.10.10 -Pipe labeling per 5.3.11 -Independent Performance Testing per 5.3.12 -System Management per 5.3.13 -Air system requirements as shown in 5.3.3.5 -Vac System requirements as shown in 5.3.3.6
FYIANNUAL OPERATION HAZMAT PERMIT This facility is REQUIRED TO enroll in the annual Hazardous Materials Operational permit program ***** APPLICATION IS VIA THE CSFD ON LINE WEBSITE @ https://hammers.springsgov.com/submit
FYIMED GAS FLOOR PLAN SHEET 1M-4 EQUIPMENT INSTALLATION SCHEDULE AND MED GAS NOTES SOURCE SUPPLY STORAGE ROOM #111 MECHANICAL PLAN SHEET FOR MED GAS VENTILATION EXTERIOR ROOM SHEET 1M-2
FYI5.1.11.2 PIPE LABELING AND SHUTOFF VALVES LABELING Piping and shutoff valves shall be labeled in accordance with NFPA 99, 5.1.11.1 and 5.1.11.2
FYILOCATION OF PIPING NFPA 99 Section 5.3.10.10.5 Location of piping shall be located in accordance with 5.3.10.10.5.1 (A) through 5.3.10.10.5.1(C) AND Piping shall be permitted to be installed overhead where possible. Piping shall NOT be installed in electrical switchgear rooms, elevator shafts and areas having open flames. Piping shall NOT be located where subject to contact with oil.
DisapprovedTHIS SUPPLY SOURCE ROOM IS A One-hour Interior room: Automatic sprinkler(s) shall be installed within the room. The room shall be exhausted through a duct to the exterior. Supply and exhaust ducts shall be enclosed in a 1-hour-rated shaft enclosure from the room to the exterior. Approved mechanical ventilation shall comply with the International Mechanical Code and be provided at a minimum rate of 1 cubic foot per minute per square foot [0.00508 m3/(s o m2)] of the area of the room. *** PPRBD mechanical dept has not reviewed and released plans. Ensure that Mechanical has reviewed 1 hr rated room and compliance with above. RESUBMIT TO CSFD HAZMAT FOLLOWING REVIEW AND RELEASE BY PPPRBD MECHANICAL FOR THE MEDGAS ROOM **** PLEASE INDICATE SPRINKLER HEAD TYPE AND INSTALLATION WITHIN THIS ROOM. IT HAS NOT BEEN NOTED ON THE PLAN SET. *** Ensure that door and assembly is rated for a one hr room
AttentionINSPECTIONS ATTENTION CONTRACTOR Medical Gas system piping installation requires MULTIPLE INSPECTIONS by the CSFD due to installation requirements and procedures. ALL PORTIONS OF PIPING SYSTEMS SHALL REQUIRE INSPECTION; no piping shall be sealed or concealed prior to inspection. Contact the CSFD Office of the Fire Marshal at 385-5978 for an inspection schedule for this project. All paperwork, documentation, installer/verifier certifications, and needed test equipment shall be available upon Inspector's request. Performance Testing is required per 5.1.12. Independent Testing for specific conformance to the requirements of NFPA 99 will be required. Performance testing documentation and inspection is subject to field verification by the Fire Inspector.
AttentionCREDENTIALS AND CERTIFICATIONS American Society of Sanitary Engineers (ASSE) Medical Gas Installer, Medical Gas Verifier and Brazing certification credentials, or documents shall be required prior to commencement of work, and on site and available AT ALL TIMES for inspection by the CSFD. CREDENTIALS SHALL BE CURRENT. Performance Testing is required per 5.1.12. Independent Testing for specific conformance to the requirements of NFPA 99 will be required. Performance testing documentation and inspection is subject to field verification by the Fire Inspector.
AttentionATTENTION: CONTRACTOR SHALL MAKE AVAILABLE TO THE INSPECTOR: SPECIFICATIONS, DOCUMENTATION, LISTINGS, VERIFICATION BY 3RD PARTY TESTING. ANY FIELD MODICATIONS SHALL BE DOCUMENTED AND SUBMITTED ON ENGINEER STAMPED AS BUILT PLANS, AND RESUBMITTED TO THE CSFD AND/OR FIRE INSPECTOR.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com

printer friendly version Printer friendly version