NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

TELEMATRIX
05025 GALLEY RD

Review DateStatusComment(s)
10/28/2013 FYI*****(STANDARD COMMENT) This project is: Cetis Group, 5025 Galley Rd: clean agent suppression system You can access our web site for the latest fire department plan review comments: 1. From www.springsgov.com, select CITY AGENCIES then FIRE 2. Click on FIRE CODE ENFORCEMENT. 3. Click on REVIEW PLANS STATUS in the gray box 4. Then select VIEW PLAN REVIEW STATUS. 5. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYI*****(STANDARD COMMENT 3) The special hazard suppression system is being installed by: CINTAS This plan review is based on the requirements found within the adopted International Building Code, International Fire Code and the most recent editions of the applicable NFPA standards.
FYI*****(STANDARD COMMENT 3) DESIGN: Type of System: FM-200 Size of System: 84 POUNDS PRE-ENGINEERED Hazard Protected: SERVER ROOM
Attention*****(STANDARD COMMENT 4) REDLINED COMMENTS: The following RED-LINED items are to be corrected prior to final inspection: 1. Horn/strobe on the exterior of the room shall be provided with a red lens. 2. Upon agent discharge, the building shall enter a general alarm/evacuation state.
FYI(CLEAN AGENT) SIGNAGE: Warning and instruction signs shall be provided at the entrance to and inside the protected areas. (NFPA 2001:4.3.5.5)
FYI(CLEAN AGENT) PNEUMATIC TESTING Pneumatic test of 40 psi for a duration of 10 minutes - pressure drop shall not exceed 20% of the test pressure. (NFPA 2001:7.7.2.2.12)
FYI(CLEAN AGENT) AIR FLOW TEST: Air flow test (nitrogen or inert gas) on piping network to verify flow is continuous and piping and nozzles are unobstructed. (NFPA 2001:7.7.2.2.13)
FYI(CLEAN AGENT) NOZZLES: All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease, vapors, moisture or other foreign materials into the piping. (NFPA 2001:4.2.5.4)
FYI(STANDARD COMMENT 5) INDICATION OF SYSTEM ACTIVATION: An audible OR visual indication shall be provided that the system has operated, that personnel response is needed, and that the system is inneed of recharge. (IFC 904.3.4)
FYI(STANDARD COMMENT 6) FIRE ALARM SYSTEM CONNNECTIONS: The extinguishing system shall be connected to the fire alarm system, if provided, in accordance with NFPA 72. (IFC 904.3.5)
FYI(STANDARD COMMENT) LICENSED INSTALLER/SERVICE TECHNICIAN An On-Site Installer/Service Technicial shall supervise all on-site work on any fire protection system. This On-Site Installer shall have a current Installer Certificate (RBD Wallet Card), on his/her person, while on the job site.
FYI(STANDARD COMMENT 8) CERTIFICATE OF INSTALLATION: It is the installer's responsibility to certify through this form that the system has been properly installed and tested. The form is to be filled out in its entirety PRIOR TO THE ARRIVAL OF THE FIRE INSPECTOR that is conducting the final inspection and/or the acceptance test of the system. FINAL INSPECITONS WILL NOT BE CONDUCTED WITHOUT THIS FORM BEING COMPLETED.
FYI(STANDARD COMMENT 9) MANUFACTURER'S DATA The approved set of system plans, manufacture's product data sheets on all equipment being installed, and the installation permit are to be on site for all fire department inspections.
FYI(STANDARD COMMENT 10) INSPECTIONS Due to the dynamic nature of inspectors schedules, PLEASE call your inspection requests in with ample time to allow scheduling. Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( i.e. 20001234 - HM -2 or 20000012 - CN - 1) The CSFD Approved sets of plans are to be on site for all inspections.
FYI(STANDARD COMMENT 15) PLAN REVIEW/PERMIT FEES All fire department fees are to be paid prior to issuance of any permits. These fees must be paid directly to the Colorado Springs Fire Department - Development Review Enterprise - at 2880 International Circle - Suite 200-7.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
10/14/2013 FYI*****(STANDARD COMMENT) This project is: Cetis Group, 5025 Galley Rd: clean agent suppression system You can access our web site for the latest fire department plan review comments: 1. From www.springsgov.com, select CITY AGENCIES then FIRE 2. Click on FIRE CODE ENFORCEMENT. 3. Click on REVIEW PLANS STATUS in the gray box 4. Then select VIEW PLAN REVIEW STATUS. 5. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYI*****(STANDARD COMMENT 3) The special hazard suppression system is being installed by: CINTAS This plan review is based on the requirements found within the adopted International Building Code, International Fire Code and the most recent editions of the applicable NFPA standards.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
Disapproved(STANDARD COMMENT 20) DISAPPROVED COMMENTS: The following information and/or corrections are needed prior to completing a full plan review. PLEASE RESPOND IN WRITING ON LETTERHEAD TO EACH OF THE FOLLOWING COMMENTS: 1. Resubmittal includes battery calculations have 2 different current draws. I dont' know which is the correct set to be reviewing? 2. Response letter(s) to CSFD review comment is not provided. 3. cut sheets are so marked up I don't know which item is being called out and which is not. 4. Matrix appears to have been previously provided, however there is no identifying information to show where this is applicable to (ie where is the address, company, date, etc found in the title block)? 5. Scope of work is not clearly identified - what are you installing? 6. Provide a clean submittal with all review comments (current and previous) addressed via letterhead. Also review the disapproved plans for additional written comments prior to submittal of new plans.
Attention(STANDARD COMMENT 23) NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.
10/2/2013 FYI*****(STANDARD COMMENT) This project is: Cetis 5025 E Galley Rd New FM200 system Date of Plans: Not dated You can access our web site for the latest fire department plan review comments: 1. From www.springsgov.com, select CITY AGENCIES then FIRE 2. Click on FIRE CODE ENFORCEMENT. 3. Click on REVIEW PLANS STATUS in the gray box 4. Then select VIEW PLAN REVIEW STATUS. 5. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
Disapproved(STANDARD COMMENT 20) DISAPPROVED COMMENTS: The following information and/or corrections are needed prior to completing a full plan review. PLEASE RESPOND IN WRITING ON LETTERHEAD TO EACH OF THE FOLLOWING COMMENTS: 1. Battery calcs either have wrong part information or need current draws verifiable on spec sheets. Spec sheets must match p/n used in battery calcs. See the smoke detectors, bells and bell/horn/strobes Also review the disapproved plans for additional written comments prior to submittal of new plans.
9/17/2013 FYI*****(STANDARD COMMENT) This project is: Cetis Group, 5025 Galley Rd: clean agent suppression system You can access our web site for the latest fire department plan review comments: 1. From www.springsgov.com, select CITY AGENCIES then FIRE 2. Click on FIRE CODE ENFORCEMENT. 3. Click on REVIEW PLANS STATUS in the gray box 4. Then select VIEW PLAN REVIEW STATUS. 5. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
Disapproved(STANDARD COMMENT 20) DISAPPROVED COMMENTS: The following information and/or corrections are needed prior to completing a full plan review. PLEASE RESPOND IN WRITING ON LETTERHEAD TO EACH OF THE FOLLOWING COMMENTS: 1. Nozzle and piping layout was not provided as required. 2. Agent flow calculations were not provided. 3. Sequence of operations shall be provided in matrix format - the narrative form can be included, but a matrix is required. This is an incomplete submitted - reference the latest edition of NFPA 2001 and the CSFD Special Hazards Information Packet https://www.springsgov.com/SIB/files/Special_Hazard_Packet__2012[1](1).pdf for details on what is required when submitting these types of systems. Also review the disapproved plans for additional written comments prior to submittal of new plans.
Attention(STANDARD COMMENT 23) NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.


 