NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

FREEDOM MINISTRIES SUITE 120
05805 MARK DABLING BLVD

Review DateStatusComment(s)
1/7/2014 FYI*****(STANDARD COMMENT) REVISION: Revision Sequence: NOT MARKED Scope of Revision: CORRECTED SCOPE OF WORK TO INDICATE NOTIFICATION WAS REPLACED; ONLY ADDED TO ONE AREA, NOT ADDED TO ENTIRE SPACE. Date of Revision: 1/7/13 REVIEW DATE
1/2/2014 ApprovedContractor came to counter to ask if dialer with 2 phone lines could be "Grandfathered" in. Insp Embres said no since the old dialer had been completely demo'd and then new dialer insalled in the year 2013 with no permits. Does not meet existing/non-conforming.
12/27/2013 Approved*****ATTENTION INSPECTOR!!!!!!! FREEDOM MINISTRIES FIRE ALARM CAN NOT BE FINALED UNLESS BUILDING DIALER PERMIT IS RE-ISSUED AND FINAL ACCEPTANCE TESTED AT THE SAME TIME. 2013-1050 AND SCOPE OF WORK ON FREEDOM INCLUDES THE CHANGE FOR DEMO OF EXISTING DEVICES TO INSTALL NEW.
12/24/2013 ApprovedWork at Risk without fees approved by FPE Withee due to a dispute in fees and number of devices. Until that can be resolved with the plan reviewer that approved the plans and issued the fee sheet, fees will not be collected and plans will be held in the office.
FYI*****(STANDARD COMMENT 2) WORK AT RISK On ---12/24/13-- approval was granted by --FPR WITHEE--- for fire alarm work to begin without approved plans or permits. Any changes or modification required through plan review will be required. No inspections will be conducted without approved plans and permits.
12/19/2013 FYI*****(STANDARD COMMENT 1) This project is: Freedom Ministries 5825 Mark Dabling Bd Extend notification in to new space This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****(STANDARD COMMENT 5) DESIGNER/INSTALLER INFORMATION Fire Alarm system was designed by: SGFP Fire alarm system is being installed by: AES
FYI*****(STANDARD COMMENT 6) FIRE ALARM SYSTEM DESIGN: -----Single Family Residential Fire Alarm System -----Manual -----Automatic -----Dedicated Funtion: ----- _XX__Occupant Notification AUXILIARY FUNCTIONS: -----Elevator Recall -----Duct Detector -----Waterflow -----Door Release
Attention(STANDARD COMMENT) ADDITIONS AND REMODELS TO EXISTING SYSTEMS: Existing systems shall comply with current codes and standards for all areas occupied by the tenant, not just the area of remodel. (CSFD Administrative Ruling 2010-2)
FYI*****(STANDARD COMMENT) REVISION: Revision Sequence: Second Scope of Revision: Address code review comments Date of Revision: Date not changed
FYI*****(STANDARD COMMENT 7) Scope of Work: Adding 4009 panel, notification, duct detectors EXISTING CONDITIONS AS DECLARED: A OC; >300 OL; DIAL 9 TO GET OUTSIDE PHONE LINE; TEMPORAL; REQUIRED; MANUAL, AUTOMATIC; DUCT DETECTORS/DAMPERS, VOICE ALARM, SUPPRESSION MONITORING; DACT; B CLASS; 0 SURVIVABILITY
FYI(COMMERCIAL) MONITORING Off-site monitoring of this fire alarm system is required and shall be provided by an approved monitoring agency. The phone number to be used to report a fire emergency is (719) 444-7632.
FYI(STANDARD COMMENT 13) LICENSED INSTALLER/SERVICE TECHNICIAN An On-Site Installer/Service Technicial shall supervise all on-site work on any fire protection system. This On-Site Installer shall have a current Installer Certificate (RBD Wallet Card), on his/her person, while on the job site.
FYI(STANDARD COMMENT) RECORD OF COMPLETION: The Record of Completion (ROC) shall be filled out in accordance with 10.18.2 for new installations. All modifications made after the initial installation shall be recorded on a revised Record of Completion. All changes shall be shown and the revised ROC and shall include a revision date.
FYI(STANDARD COMMENT) PRE-TEST REQUIREMENT: Before requesting final approval of the installation, the installing contractor shall furnish a written statement that the system has been installed in accordance with approved plans and testing in accordance with the manufacturer's published instructions and the appropriate NFPA requirements. (10.18.1.3) CSFD requires a 100% pre-test - Evidence may be documented on the Record of Completion.
FYI(STANDARD COMMENT) ACCEPTANCE TESTING: At the time of this inspection the Fire Inspector will expect ALL devices involved in this fire alarm project to be tested. The installer should be aware of the fact that in a larger facility there may by a need to isolate the fire alarm system to only the area being tested. The alarm installer is to insure that building owner and/or manager and the General Contractor has been informed of the test criteria, time and date of the test, and have given their approval. Acceptance testing shall be completed in accordance with Chapter 14 of NFPA 72
Attention(STANDARD COMMENT 11) ROUGH-IN PERMIT AND INSPECTIONS: All Fire Alarm systems wiring installed within the City of Colorado Springs must be inspected by the Pikes Peak Regional Building Department PRIOR TO the Fire Final on the system. This will require the installing contractor to obtain a Rough-In Permit issued by the Regional Building Department. Please call RBD at 327-2880 for additional information on how to obtain this permit.
FYI(STANDARD COMMENT 10) INSPECTIONS Due to the dynamic nature of inspectors schedules, PLEASE call your inspection requests in with ample time to allow scheduling. Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( i.e. 20001234 - HM -2 or 20000012 - CN - 1) The CSFD Approved sets of plans are to be on site for all inspections.
FYI(STANDARD COMMENT 19) PLAN REVIEW/PERMIT FEES All fire department fees are to be paid prior to issuance of any permits. These fees must be paid directly to the Colorado Springs Fire Department - Development Review Enterprise - at 2880 International Circle - Suite 200-7.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
FYI*****(STANDARD COMMENT 27) DISAPPROVED ITEMS ADDRESSED The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1. As previously noted in another review, RBD has removed the "E" OC from this site. 2. Contractor/designer have stated there is no longer a hood system in this building.
12/11/2013 FYI*****(STANDARD COMMENT 1) This project is: Freedom Ministries, 5805 Mark Dabling Bl, Suite 120 This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
Disapproved*****(STANDARD COMMENT 19) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Non-separated/mixed occupancy buildings: 2009 IBC 508.3.1: the requirements of this code shall apply to each portion of the building based on occupancy class of that spaced EXCEPT that the most restrictive applicable provision of Chapter 9 shall apply to the building or portion thereof in which the nonseparated occupancies are located. This tenant requires a fire alarm system based on E occupancy class requirements. There are 2 options: 1 - this tenant must be separated from the other occupancies by rated construction OR 2 - the fire alarm system must be extended to the whole building. there is no record of plans being resubmitted to RBD/CSFD for a change to separated mixed use, therefore the fire alarm system needs to be extended throughout the building. 2. Plans do not appear to meet the fire alarm requirements for an E-occupancy per section 907.2.3. Also review the disapproved plans for additional written comments prior to submittal of new plans.
FYI(STANDARD COMMENT 20) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provid submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
Attention(STANDARD COMMENT 26) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, CFPS Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 / (F) 719-385-7330 dwithee@springsgov.com


 