NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

ELLICOTT MIDDLE SCHOOL DISTRICT 22 OUTSIDE CITY
00350 ELLICOTT HWY

Review DateStatusComment(s)
4/16/2014 FYI*****(STANDARD COMMENT 1) This project is: Ellicott Middle School 350 Ellicott Hy REV B This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
AttentionThis revision is adding duct detectors/dampers.
11/25/2013 FYI*****(STANDARD COMMENT 1) This project is: Ellicott Middle School, 350 Ellicott Hy This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****(STANDARD COMMENT 5) DESIGNER/INSTALLER INFORMATION Fire Alarm system was designed by: SIMPLEXGRINNELL Fire alarm system is being installed by: ENCORE ELECTRIC
FYI*****(STANDARD COMMENT 6) FIRE ALARM SYSTEM DESIGN: --XXX---Manual -XXX----Automatic AUXILIARY FUNCTIONS: -XXX----Elevator Recall -XXX----Duct Detector -XXX----Waterflow --XXX---Door Release Smoke detection other than for elevator recall is non-required. Clock/schedule system appears to be part of this fire alarm system.
FYI(COMMERCIAL) MONITORING Off-site monitoring of this fire alarm system is required and shall be provided by an approved monitoring agency. DACT COMMUNICATIONS WITH 2 PHONE LINES PERMITTED PER STATE OF COLORADO
FYI(STANDARD COMMENT 13) LICENSED INSTALLER/SERVICE TECHNICIAN An On-Site Installer/Service Technicial shall supervise all on-site work on any fire protection system. This On-Site Installer shall have a current Installer Certificate (RBD Wallet Card), on his/her person, while on the job site.
FYI(STANDARD COMMENT) RECORD OF COMPLETION: The Record of Completion (ROC) shall be filled out in accordance with 10.18.2 for new installations. All modifications made after the initial installation shall be recorded on a revised Record of Completion. All changes shall be shown and the revised ROC and shall include a revision date.
FYI(STANDARD COMMENT) PRE-TEST REQUIREMENT: Before requesting final approval of the installation, the installing contractor shall furnish a written statement that the system has been installed in accordance with approved plans and testing in accordance with the manufacturer's published instructions and the appropriate NFPA requirements. (10.18.1.3) CSFD requires a 100% pre-test - Evidence may be documented on the Record of Completion.
FYI(STANDARD COMMENT) ACCEPTANCE TESTING: At the time of this inspection the Fire Inspector will expect ALL devices involved in this fire alarm project to be tested. The installer should be aware of the fact that in a larger facility there may by a need to isolate the fire alarm system to only the area being tested. The alarm installer is to insure that building owner and/or manager and the General Contractor has been informed of the test criteria, time and date of the test, and have given their approval. Acceptance testing shall be completed in accordance with Chapter 14 of NFPA 72
FYI(STANDARD COMMENT 12) STATE PROJECTS ROUGH-IN PERMIT AND INSPECTIONS: All Fire Alarm systems wiring installed within the City of Colorado Springs must be inspected by the State Electrical Inspector PRIOR TO the Fire Final on the system. The State Electrical Inspector shall sign in the appropriate space on the CSFD permit card that the rough-inspection has been done and approved.
FYI(STANDARD COMMENT 10) INSPECTIONS Due to the dynamic nature of inspectors schedules, PLEASE call your inspection requests in with ample time to allow scheduling. Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( i.e. 20001234 - HM -2 or 20000012 - CN - 1) The CSFD Approved sets of plans are to be on site for all inspections.
FYI(STANDARD COMMENT 19) PLAN REVIEW/PERMIT FEES All fire department fees are to be paid prior to issuance of any permits. These fees must be paid directly to the Colorado Springs Fire Department - Development Review Enterprise - at 2880 International Circle - Suite 200-7.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, CFPS Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 / (F) 719-385-7330 dwithee@springsgov.com
10/10/2013 FYI*****(STANDARD COMMENT 1) This project is: Ellicott Middle School, 350 Ellicott Hy: new middle school This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****(STANDARD COMMENT 5) DESIGNER/INSTALLER INFORMATION Fire Alarm system was designed by: SIMPLEXGRINNELL Fire alarm system is being installed by: ENCORE ELECTRIC
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
Disapproved*****(STANDARD COMMENT 19) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Encore Electric is not licensed to work in El Paso County as a fire alarm contractor - reference Pikes Peak Regional Building Code section 208. It appears license was sought in 2012 but was never picked up. See Additional Comment. 2. Codes/editions for the design of this system must be corrected as noted on the plans. 3. Delay in transmission of AC power loss is not indicated as required by 10.6.9.3. 4. Clarify the intent for the placement of smoke detection. It appears you are trying to comply with section 807.4.3 of the 2006 IFC for corridors and placement of clothing/personal effects, however it also appears lockers are present. Additionally, there are random smoke detectors within administrative areas 5. Main lobby area - ceiling heights are not declared and smoke detection is not indicated - there isn't a note even to explain if it is open to the next level. 6. Corridor 178 main level area B - please clarify intent of a 110 candella strobe in the corridor. 7. Elevator - there are no sprinklers at the top of the hoistway and therefore detection is not permitted at the top of the hoistway. However, sprinklers are in the pit, and detection is required in the pit - plans must reflect this accordingly. 8. Upper level ARea C - plans show ceiling height os 26-feet. Provide engineering analysis or modeling to show the spot smoke detectors will not be affected by stratification within this space 9. Provide a code study permitting single technology for signal transmission means. 10. Security doors and magnetically held open doors are not indicated on the plans but are shown on the matrix - please clarify. Also review the disapproved plans for additional written comments prior to submittal of new plans.
Disapproved(STANDARD COMMENT 25) CONTRACTOR LICENSING. Our records indicate the license for this Fire Alarm Contractor is not current. Please contact the Contractor Licensing Office of the Regional Building Department AT 719-327-2887 to correct this problem. ---xxx--Encore is not a licensed FAC-B contractor
FYI(STANDARD COMMENT 20) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provid submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
Attention(STANDARD COMMENT 26) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, CFPS Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 / (F) 719-385-7330 dwithee@springsgov.com


 