RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

BAR LOUIE
03255 CINEMA PT

Review DateStatusComment(s)
7/3/2014 FYIRESUBMITTED: The plans have been re-submitted, and the disapproved issues have been addressed as follows: APPROVED **PLEASE NOTE** ALL COMMENTS FOUND ON PREVIOUS PLAN REVIEWS REMAIN ENFORCEABLE UNLESS OTHERWISE NOTED IN THIS REVIEW. 1) CO2 storage location shown on plan sheet M1 of 6. CO2 gas detection system shown and shall be installed per code and mfgr instructions. note #16. PPRBD has reviewed and released ventilation requirements for this facility July 2. 2) CO2 vessel spec sheets; carbomizer ASME; CHART 450 LB; Mechanical room #113. SEE ELECTRONIC DOCUMENTS
6/23/2014 FYIBar Louie, 3255 Cinema Pt: interior remodel - change in occupancy from B or A2 SYSTEMS: fire sprinkler for 1-hour substitution/occupancy/use; fire alarm for occupancy CN:Code: 09 IBC - 09 IFC -11 PPRBC /Class:A2 / Const: II-A /Stories: 2/Size:7784 /OL: 316 Additional Comments: SEPARATED MIXED USE - 1-HOUR FIRE BARRIER CARBON DIOXIDE 450 LB VESSEL REPORTED: NO ADDITIONAL INFORMATION AT THIS TIME You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
DisapprovedDEFICIENT SUBMITTAL: RESUBMIT WITH THE FOLLOWING DOCUMENTS/INFORMATION. REVIEW THESE PLAN COMMENTS; SEE M1 CO2 container specifications; LOCATION OF CO2 storage/use piping and distribution locations and specifications of piping Gas Detection system; cut sheets/specifications; installation location identified on plan Ventilation required per IMC/IFC 2009; AND PER ADMIN RULING Fill box location (exterior) and spec/sheet; valve vent to exterior
DisapprovedCO2 STORAGE LOCATION SHOW CO2 storage location #104 PREP AREA. SEE PLAN SHEET M200 FOR REDLINE COMMENTS ventilation, CO2 location, Monitoring-Detection per IFC Admin Ruling. SHOW Exterior fill port and specs on plan sheet Ventilation required Gas detection system required (Plan reviewer spoke with Mr. Cocagne, of Lingle Design 1/31/14 and sent email with Admin Ruling 2011-1 for direction on gas detection and ventilation requirements.)
DisapprovedCARBON DIOXIDE Facilities shall declare the storage and use of small Insulated Carbon Dioxide Systems used in Beverage Dispensing. Gaseous Carbon Dioxide is an asphyxiant gas and exposure to high concentrations may cause toxic effects including asphyxiation. To provide for the safety of building occupants and emergency personnel, ventilation in accordance with the IFC Sections 3007.2, 2704.3 or 2705.1.9 is required where concentrations of this gas are stored or present. All new or proposed building ventilation system designs shall submit for review and permit approval to the Pikes Peak Regional Building Department-MECHANICAL DEPARTMENT FOR REVIEW. *** ATTENTION**** 2704.3 VENTILATION Indoor storage areas and storage buildings shall be provided with mechanical exhaust ventilation or natural ventilation where natural ventilation can be shown to be acceptable for the materials as stored AND a Listed, approved CO2 detection system, in accordance with the IFC Administrative Ruling. System requirements. Exhaust ventilation systems shall comply with all of the following: 1. Installation shall be in accordance with the International Mechanical Code. 2. Mechanical ventilation shall be at a rate of not less than 1 cubic foot per minute per square foot of floor area over the storage area. 3. Systems shall operate continuously unless alternative designs are approved. 4. A manual shutoff control shall be provided outside of the room in a position adjacent to the access door to the room or in an approved location. The switch shall be of the break-glass type and shall be labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF. 5. Exhaust ventilation shall be designed to consider the density of the potential fumes or vapors released. For fumes or vapors that are heavier than air, exhaust shall be taken from a point within 12 inches of the floor.
DisapprovedVENTILATION 2704.3 CONTINUED 6. The location of both the exhaust and inlet air openings shall be designed to provide air movement across all portions of the floor or room to prevent the accumulation of vapors. 7. Exhaust ventilation shall not be recirculated within the room or building if the materials stored are capable of emitting hazardous vapors. ******************** ATTENTION*************************** PPRBD Mechanical has NOT released for permit these plans. SEE PLAN SHEET M1 FOR VENTILATION REDLINE COMMENTS VENTILATION AND GAS DETECTION ARE REQUIRED
ILABELING AND MARKING ** Stationary compressed gas containers, cylinders and tanks shall be marked with the name of the gas Markings shall be visible from any direction of approach. ** Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Piping systems shall be marked in accordance with ANSI A13.1. ** Markings used for piping systems shall consist of the content#s name and include a direction-of-flow arrow. ** Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at a minimum of every 20 feet or fraction thereof throughout the piping run. Portable containers, cylinders and tanks. Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Signs clearly establishing the location and identity of shut-off valves are to be provided. All inert piping systems shall be identified by appropriate labeling with the name of the gas. Warning signs shall be posed at each entrance to the room or enclosure where the bulk inert gas system is installed. Wording shall include: WARNING ---(name of gas) HIGH CONCENTRATION OF GAS MAY OCCUR IN THIS AREA AND MAY CAUSE ASPHYXIATION. VERIFY THAT OXYGEN CONCENTRATION IS ABOVE 19.5% BEFORE ENTERING AND DURING ACTIVITY IN THIS AREA.
FYIONE, 450 lb CARBON DIOXIDE VESSEL (CO2) CUBIC FEET = 3,933 scf Location: unidentified on plans; NO ADDITIONAL INFORMATION HAS BEEN PROVIDED IN PLANS. RESUBMIT PLANS WITH CO2 INFORMATION NFPA = 1-0-0 special = SA; OR 3-0-0 SA TLV-TWAs, 5000 ppm (ACGIH, 2004) TLV-TWA 15 MIN STEL 30,000 ppm High Pressure liquid and gas. Can cause rapid suffocation....CO2 IS AN ASPHYXIANT May cause frostbite. ****** ATTENTION ******* Indoor storage of compressed gases falling into categories such as asphyxiants, irritants can be hazardous regardless of the type of gas involved simply due to the hazards related to asphyxiation. VENTILATION SHALL BE MAINTAINED AND OPERATIONAL. See ventilation comments. The carbon dioxide shall be transferred---loaded and off loaded through a fill connection located directly adjacent to the tank at the exterior of building. *** fill connection IS REQUIRED to be located on exterior of building. NOT identified ATTENTION: Duplicate gauges shall be installed at the filling connection to enable the driver to fill the container and maintain the required pressure in the container. Pressure relief devices and vents shall be piped to discharge outside in a safe direction. ***NOT identified on or with plan set. ****************************** NOTE: Storage areas where an accumulation of inert gas could occur should be continuously monitored with an appropriate alarm system to indicate an oxygen deficient atmosphere. ****A CO2 detector or audible/visual alarm is not noted on plan sheets at this time. REQUIRED GAS DETECTION SYSTEM. SEE ADDITIONAL COMMENTS
AttentionTHE CHEMICAL INVENTORY, AS DECLARED, DOES NOT EXCEED THE ALLOWABLE THRESHOLDS FOR THE ANNUAL HAZARDOUS MATERIALS OPERATIONAL PERMIT. 450 LB CO2 (inert/asphyxiant = 3,933 scf ********** (permit threshold = 6,000 cf) *** This facility is NOT required to apply for the Annual Hazardous Materials Operational Permit at the CSFD ***This facility is required to have a Construction Hazmat Inspection. *** To Schedule the hazardous materials construction inspection please contact the Division of the Fire Marshal @ 719-385-5978.
IPiping shall be protected against physical damage. Signage shall be provided for piping and hose systems as follows: 1. Above-ground piping systems shall be marked in accordance with ANSI A13.1. 2. Station outlets shall be marked to indicate their intended usage. 3. Signs shall be posted, indicating clearly the location and identity of section shutoff valves.
FYILabeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
AttentionNOTE TO CONTRACTOR & FIRE INSPECTOR: Prior to scheduling the Fire Final please contact the Hazardous Materials Inspector to arrange a Hazardous Materials Inspection prior to final signature being provided.
FYICompressed gas containers, cylinders, tanks and systems shall not be placed in areas where they are capable of being damaged by falling objects. Compressed gas container, cylinder and tank valves shall be protected from physical damage by means of protective caps, collars or similar devices in accordance with Sections 3003.6.1 and 3003.6.2. Compressed gas containers, cylinders and tanks designed for protective caps, collars or other protective devices shall have the caps or devices in place except when the containers, cylinders or tanks are in use or are being serviced or filled.
FYIEquipment, machinery, and required detection and alarm systems associated with the use, storage, or handling of hazardous materials shall be listed or approved. This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
FYIMaterial Safety Data Sheets (MSDS) for all hazardous materials shall be either readily available on the premises as a paper copy, or where approved, shall be permitted to be readily retrievable by electronic access. Approved electronic access shall be as follows: 1. Media shall be USB Flash Drive. 2. Format shall be Microsoft Word 2000 or newer docu-ment, PDF, or other approved format. Where a Knox Box is located at a facility, one USB de-vice shall be stored in the Knox Box and one device shall be located in an approved location(s). All devices and content shall be maintained.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com

printer friendly version Printer friendly version