RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

LKQ KEYSTONE AUTOMOTIVE
01727 JET STREAM DR

Review DateStatusComment(s)
6/6/2014 FYIThis project is:LKQ Keystone Automotive, 1727 Jet Stream Dr Remodel SYSTEMS: Sprinklers, CN:Code: 09 IBC - 09 IFC - 11 PPRBC /Class: B, S1 / Const: II-B /Stories:1 /Size: 2600 /OL: 120 Date of Plans: 04/09/14 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
AttentionCONTROL AREA STORAGE TWO CONTROL AREAS IDENTIFIED: 1) MIXING ROOM (PRE FAB IN ACCORDANCE WITH NFPA 33) 2) REMAINDER OF BUILDING IN S1 AREA RACK 3404.3.4.1 Maximum allowable quantity per control area. For occupancies other than Group M wholesale and retail sales uses, indoor storage of flammable and combustible liquids shall not exceed the maximum allowable quantities per control area indicated in Table 2703.1.1(1) and shall not exceed the additional limitations set forth in this section. 3404.3.5 Storage in control areas. Storage of flammable and combustible liquids in control areas shall be in accordance with Sections 3404.3.5.1 through 3404.3.5.4. 3404.3.5.1 Basement storage. Class I liquids shall be allowed to be stored in basements in amounts not exceeding the maximum allowable quantity per control area for use-open systems in Table 2703.1.1(1), provided that automatic suppression and other fire protection are provided in accordance with Chapter 9. Class II and IIIA liquids shall also be allowed to be stored in basements, provided that automatic suppression and other fire protection are provided in accordance with Chapter 9. 3404.3.5.2 Storage pile heights. Containers having less than a 30-gallon (114 L) capacity which contain Class I or II liquids shall not be stacked more than 3 feet (914.4 mm) or two containers high, whichever is greater, unless stacked on fixed shelving or otherwise satisfactorily secured. Containers of Class I or II liquids having a capacity of 30 gallons (114 L) or more shall not be stored more than one container high. Containers shall be stored in an upright position. 3404.3.5.3 Storage distance from ceilings and roofs. Piles of containers or portable tanks shall not be stored closer than 3 feet (914 mm) to the nearest beam, chord, girder or other obstruction, and shall be 3 feet (914 mm) below sprinkler deflectors or discharge orifices of water spray or other overhead fire protection system. 3404.3.5.4 Combustible materials. In areas that are inaccessible to the public, Class I, II and IIIA liquids shall not be stored in the same pile or rack section as ordinary combustible commodities unless such materials are packaged together as kits.
AttentionMIXING ROOM (CONTROL AREA 1) ATTENTION: Mixing room shall be required to be in accordance with NFPA 33 Standard, Section 8.3 (current edition) *** Mixing room is required to be designed to contain a spill; mixing room is required to be electrically classified the same as enclosed spray booths; Mixing room shall not exceed 150 sf (mixing room is 90 sf). *** ATTENTION: Ventilation is required to meet 1 cf/min/square foot and be continuous ventilation AND IMC/IFC 2009, requirements. (PPRBD MECHANICAL AND ELECTRICAL DEPTS HAVE REVIEWED AND RELEASED THE PLANS FOR THE MIXING ROOM) ATTENTION Mixing room shall be equipped with an approved automatic fire suprression system. ATTENTION: Submit fire suppression system plans to Ms Dee Withee, CSFD, CONSTRUCTION SERVICES @ 719 385-7361.
AttentionANNUAL OPERATIONAL PERMIT - HAZARDOUS MATERIALS This facility exceeds the annual operational Hazardous Materials Permit and will be required to complete the permit application and inventory in the CSFD online website https://hammers.springsgov.com/submit see attached card This shall be completed prior to the construction final hazardous The annual permit is automatically renewed, and an annual fee and inspection is associated with this permit. ************************************************ATTENTION CONTRACTOR ******************************************* Please contact the DIVISION OF THE FIRE MARSHAL FOR QUESTIONS AND TO SCHEDULE THE HAZMAT CONSTRUCTION INSPECTION AND HAZMAT PERMIT INSPECTION @ 719 385-5978, HAZARDOUS MATERIALS SPECIALIST INSPECTOR, JAY WEIGHTMAN.
AttentionCHEMICAL INVENTORY AS DECLARED SEE ELECTRONIC DOCUMENTS CLASS II = 12.47 GAL CLASS IIIA = .13 GAL CLASS IIIB = 60 GAL CLASS IB = 183 GAL CLASS IC = 115 GAL MAQS IB & IC = 120 GAL (SPRINKLERED 240 GAL) COMB CLASS II = 120 GAL (SPRINKLERED 240 GAL) COMB CLASS IIIA = 330 GAL (SPRINKLERED 660) COMB CLASS IIIB = 13,200 GAL THE CHEMICAL INVENTORY, AS DECLARED, DOES NOT EXCEED THE MAXIMUM ALLOWABLE QUANTITIES (MAQ) THRESHOLDS FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS, AS DEFINED BY 2009 IFC TABLE 2703.1.1(1) AND/OR 2703.1.1(2). THE CHEMICAL INVENTORY, AS DECLARED, DOES EXCEED THE ALLOWABLE THRESHOLDS FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS, AS DEFINED BY 2009 IFC PERMIT TABLES 105.6.20, 105.6.8, OR 105.6.10. APPLICATION FOR HAZARDOUS MATERIALS ANNUAL PERMIT IS REQUIRED AT HTTPS://HAMMERS.SPRINGSGOV.COM/SUBMIT
FYILabeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
FYIFF - STORAGE, USE, AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS GENERAL - The storage and handling of flammable and combustible liquids shall be in accordance with the 2009 IFC. STORAGE - Where the quantity of liquid in 5-gallon and smaller containers, other than original sealed containers, exceeds a total of 10 gallons, such liquids shall be stored in a storage cabinet, liquid storage room or a room or building for using, dispensing and mixing liquids in quantities exceeding exempt amounts. See Fire Code. Open containers and glass containers shall not be used.
FYICONTAINER STORAGE AND FLAMMABLE LIQUID STORAGE CABINETS 3404.3 Container and portable tank storage. Storage of flammable and combustible liquids in closed containers that do not exceed 60 gallons (227 L) in individual capacity and portable tanks that do not exceed 660 gallons (2498 L) in individual capacity, and limited transfers incidental thereto, shall comply with Sections 3404.3.1 through 3404.3.8.5. 3404.3.1 Design, construction and capacity of containers and portable tanks. The design, construction and capacity of containers for the storage of Class I, II and IIIA liquids shall be in accordance with this section and Section 9.4 of NFPA 30. 3404.3.1.1 Approved containers. Only approved containers and portable tanks shall be used. 3404.3.2 Liquid storage cabinets. Where other sections of this code require that liquid containers be stored in storage cabinets, such cabinets and storage shall be in accordance with Sections 3404.3.2.1 through 3404.3.2.2. 3404.3.2.1 Design and construction of storage cabinets. Design and construction of liquid storage cabinets shall be in accordance with Sections 3404.3.2.1.1 through 3404.3.2.1.4. 3404.3.2.1.1 Materials. Cabinets shall be listed in accordance with UL 1275, or constructed of approved wood or metal in accordance with the following: 1. Unlisted metal cabinets shall be constructed of steel having a thickness of not less than 0.044 inch (1.12 mm) (18 gage). The cabinet, including the door, shall be double walled with 11/2-inch (38 mm) airspace between the walls. Joints shall be riveted or welded and shall be tight fitting. 2. Unlisted wooden cabinets, including doors, shall be constructed of not less than 1-inch (25 mm) exterior grade plywood. Joints shall be rabbeted and shall be fastened in two directions with wood screws. Door hinges shall be of steel or brass. Cabinets shall be painted with an intumescent-type paint. 3404.3.2.1.2 Labeling. Cabinets shall be provided with a conspicuous label in red letters on contrasting background which reads: FLAMMABLE-KEEP FIRE AWAY. 3404.3.2.1.3 Doors. Doors shall be well fitted, self-closing and equipped with a three-point latch. 3404.3.2.1.4 Bottom. The bottom of the cabinet shall be liquid tight to a height of at least 2 inches (51 mm). 3404.3.2.2 Capacity. The combined total quantity of liquids in a cabinet shall not exceed 120 gallons (454 L).
FYILABELING AND MARKING ** Stationary compressed gas containers, cylinders and tanks shall be marked with the name of the gas Markings shall be visible from any direction of approach. ** Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Piping systems shall be marked in accordance with ANSI A13.1. ** Markings used for piping systems shall consist of the content#s name and include a direction-of-flow arrow. ** Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at a minimum of every 20 feet or fraction thereof throughout the piping run. Signs clearly establishing the location and identity of shut-off valves are to be provided.
FYIADDITIONAL SUBMITTALS Fire extinguishing system shall be required in accordance with Table 903.2.13, of the IFC 2009, as amended. *****ATTENTION Special hazard suppression systems shall be required to submit for plan review and necessary permits to the CSFD, Fire Systems Plans Reviewer. ****Submit plans and application to the CSFD-DRE, 2880 International Circle. You may contact Ms. Withee, CSFD, Fire Systems Plans Reviewer, at 719-385-7361 for questions or additional information. Plan reviews are based on the requirements found within the 2009 editions of the International Building Code, International Fire Code and the most recent editions of the NFPA standards as applicable.
FYIMSDS Material Safety Data Sheets (MSDS) for all hazardous materials shall be either readily available on the premises as a paper copy, or where approved, shall be permitted to be readily retrievable by electronic access. Approved electronic access shall be as follows: 1. Media shall be USB Flash Drive. 2. Format shall be Microsoft Word 2000 or newer docu-ment, PDF, or other approved format. Where a Knox Box is located at a facility, one USB de-vice shall be stored in the Knox Box and one device shall be located in an approved location(s). All devices and content shall be maintained.
FYIShelving shall be of substantial construction, and shall be braced and anchored in accor-dance with the seismic design requirements of the Interna-tional Building Code for the seismic zone in which the material is located. Shelving shall be treated, coated or constructed of materials that are compatible with the hazardous materials stored. Shelves shall be provided with a lip or guard when used for the storage of individual containers. Exceptions: 1. Storage in hazardous material storage cabinets or laboratory furniture specifically designed for such use. 2. Storage of hazardous materials in amounts not requiring a permit in accordance with Section 2701.5. Shelf storage of hazardous materials shall be main-tained in an orderly manner.
FYIPersons responsible for the operation of areas in which hazardous materials are stored, dispensed, handled or used shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of a fire, leak or spill. Responsible persons shall be designated and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses and identification of the locations where hazardous materials are located, and shall have access to Material Safety Data Sheets and be knowledgeable in the site emergency response procedures.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com

printer friendly version Printer friendly version