RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

TRAPPERS RENDEZVOUS
05905 CORPORATE DR

Review DateStatusComment(s)
7/3/2014 FYIRESUBMITTED: The plans have been re-submitted, and the disapproved issues have been addressed as follows: APPROVED **PLEASE NOTE** ALL COMMENTS FOUND ON PREVIOUS PLAN REVIEWS REMAIN ENFORCEABLE UNLESS OTHERWISE NOTED IN THIS REVIEW. 1) CO2 VESSEL INSTALLED EXTERIOR OF BUILDING. SEE ELECTRONIC DOCUMENTS 2) THIS FACILITY IS REQUIRED TO HAVE A HAZARDOUS MATERIALS CONSTRUCTION FINAL INSPECTION. PLEASE CONTACT THE DFM @ 719-385-5978 TO SCHEDULE THE HAZMAT INSPECTION; HAZMAT SPECIALIST JAY WEIGHTMAN. 3) THIS FACILITY IS NOT REQUIRED TO ENROLL IN THE ANNUAL HAZARDOUS MATERIALS PERMIT PROGRAM. CHEMICAL INVENTORY IS BELOW PERMIT THRESHOLD.
FYIThis facility will store and fill the CO2 container on the exterior of the restaraunt adjacent to the building.
FYIONE, 500 lb CARBON DIOXIDE VESSEL (CO2) 4370. CUBIC FEET CHART INDUSTRIES is the supplier NFPA = 1-0-0 special = SA TLV-TWAs, 5000 ppm (ACGIH, 2004) TLV-TWA 15 MIN STEL 30,000 ppm High Pressure liquid and gas. Can cause rapid suffocation....CO2 IS AN ASPHYXIANT May cause frostbite. ****** ATTENTION ******* Indoor storage of compressed gases falling into categories such as asphyxiants, irritants can be hazardous regardless of the type of gas involved simply due to the hazards related to asphyxiation. ****THIS IS AN OUTDOOR INSTALLATION ****************************** NOTE: Storage areas where an accumulation of inert gas could occur should be continuously monitored with an appropriate alarm system to indicate an oxygen deficient atmosphere. (Recommended)
AttentionATTENTION EXTERIOR STORAGE REQUIREMENTS: **Compressed gas containers, cylinders and tanks, whether full or partially full, shall not be exposed to artificially created high temperatures exceeding 125F or sub-ambient (low) temperatures unless designed for use under the exposed conditions. ** Areas used for the storage, use and handling of compressed gas containers, cylinders, tanks and systems shall be secured against unauthorized entry and safeguarded in an approved manner. ** Compressed gas containers, cylinders, tanks and systems which could be exposed to physical damage shall be protected. Guard posts or other approved means shall be provided to protect compressed gas containers, cylinders, tanks and systems indoors and out-doors from vehicular damage and shall comply with IFC 2009 Section 312. ** Labeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
AttentionCARBON DIOXIDE Facilities shall declare the storage and use of small Insulated Carbon Dioxide Systems used in Beverage Dispensing. Gaseous Carbon Dioxide is an asphyxiant gas and exposure to high concentrations may cause toxic effects including asphyxiation. To provide for the safety of building occupants and emergency personnel, ventilation in accordance with the IFC Sections 3007.2, 2704.3 or 2705.1.9 is required where concentrations of this gas are stored or present. All new or proposed building ventilation system designs shall submit for review and permit approval to the Pikes Peak Regional Building Department. THIS IS AN OUTDOOR INSTALLATION
AttentionTHE CHEMICAL INVENTORY, AS DECLARED, DOES NOT EXCEED THE ALLOWABLE THRESHOLDS FOR THE ANNUAL HAZARDOUS MATERIALS OPERATIONAL PERMIT. 500 LB CO2 (inert/asphyxiant = 4370 scf ********** (permit threshold = 6,000 cf) *** This facility is NOT required to apply for the Annual Hazardous Materials Operational Permit at the CSFD *** To Schedule the hazardous materials construction inspection FOR THE CERTIFICATE OF OCCUPANCY FINALS please contact the Division of the Fire Marshal @ 719-385-5978. HAZMAT CONSTRUCTION FINAL INSPECTION REQUIRED.
AttentionLABELING AND MARKING ** Stationary compressed gas containers, cylinders and tanks shall be marked with the name of the gas Markings shall be visible from any direction of approach. ** Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Piping systems shall be marked in accordance with ANSI A13.1. ** Markings used for piping systems shall consist of the content#s name and include a direction-of-flow arrow. ** Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at a minimum of every 20 feet or fraction thereof throughout the piping run. Portable containers, cylinders and tanks. Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Signs clearly establishing the location and identity of shut-off valves are to be provided. All inert piping systems shall be identified by appropriate labeling with the name of the gas. Warning signs shall be posed at each entrance to the room or enclosure where the bulk inert gas system is installed. Wording shall include: WARNING ---(name of gas) HIGH CONCENTRATION OF GAS MAY OCCUR IN THIS AREA AND MAY CAUSE ASPHYXIATION. VERIFY THAT OXYGEN CONCENTRATION IS ABOVE 19.5% BEFORE ENTERING AND DURING ACTIVITY IN THIS AREA.
AttentionPiping shall be protected against physical damage. Signage shall be provided for piping and hose systems as follows: 1. Above-ground piping systems shall be marked in accordance with ANSI A13.1. 2. Station outlets shall be marked to indicate their intended usage. 3. Signs shall be posted, indicating clearly the location and identity of section shutoff valves.
FYILabeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
AttentionNOTE TO CONTRACTOR & FIRE INSPECTOR: Prior to scheduling the Fire Final please contact the Hazardous Materials Inspector to arrange a Hazardous Materials Inspection prior to final signature being provided.
FYIEquipment, machinery, and required detection and alarm systems associated with the use, storage, or handling of hazardous materials shall be listed or approved. This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
FYIA minimum of 1 set of Material Safety Data Sheets (MSDS), hard copy, must be readily availiable on the premises at all times.
6/2/2014 FYITrappers Rendezvous. 5905 Corporate Dr: interior remodel in dining area, addition of open exterior patio dining area SYSTEMS: fire sprinklers for occupancy/use; waterflow alarm CN:Code: 09 IBC - 09 IFC - 11 PPRBC /Class:A2 / Const: V-B /Stories:1 /Size: 5917 /OL: 375 Additional Comments: Interior occupant load = 272 no fire alarm required You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
Disapproved* CARBON DIOXIDE PIPING specifications. NOTE: IFC 2009, 2703.2.2 Piping, tubing, valves and fittings. Piping, tubing, valves and fittings conveying hazardous materials shall be designed and installed in accordance with approved standards and shall be in accordance with Sections 2703.2.2.1 and 2703.2.2.2. Piping, tubing, valves, fittings and related components shall be designed and fabricated from materials that are compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress and exposure to which they are subject. *** RESUBMIT PLANS AND PROVIDE THE FOLLOWING CO2 CONTAINER SIZE (LBS); CO2 SPECIFICATIONS CUT SHEETS CO2 LOCATION IDENTIFIED ON PLAN SHEET AND PIPING DISTRIBUTION SYSTEM**** CO2 FILL CONNECTION IDENTIFIED ON PLAN SHEET PIPING TUBING AND VALVE DESIGN SPECIFICATIONS (at least four times the rated pressure) DECLARE TYPE OF VENTILATION (COMPLIANCE WITH IMC/IFC) AND MONITORING-DETECTION SYSTEM. MONITORING DETECTION SYSTEM IS TO BE PROVIDED--SUBMIT THE MONITORING SENSOR ALARM UNIT SPECIFICATIONS/CUT SHEETS AND IDENTIFY LOCATION OF INSTALLATION. CSFD ADMININSTRATIVE RULING 2011-1 *** For further questions or information please contact the Division of the Fire Marshal main number at 719-385-5978 or Kay Yeager @ 719-385-7356.
DisapprovedCARBON DIOXIDE Facilities shall declare the storage and use of small Insulated Carbon Dioxide Systems used in Beverage Dispensing. Gaseous Carbon Dioxide is an asphyxiant gas and exposure to high concentrations may cause toxic effects including asphyxiation. To provide for the safety of building occupants and emergency personnel, ventilation in accordance with the IFC Sections 3007.2, 2704.3 or 2705.1.9 is required where concentrations of this gas are stored or present. All new or proposed building ventilation system designs shall submit for review and permit approval to the Pikes Peak Regional Building Department. *** ATTENTION**** 2704.3 VENTILATION Indoor storage areas and storage buildings shall be provided with mechanical exhaust ventilation or natural ventilation where natural ventilation can be shown to be acceptable for the materials as stored AND a Listed, approved CO2 detection system, in accordance with the IFC Administrative Ruling. System requirements. Exhaust ventilation systems shall comply with all of the following: 1. Installation shall be in accordance with the International Mechanical Code. 2. Mechanical ventilation shall be at a rate of not less than 1 cubic foot per minute per square foot of floor area over the storage area. 3. Systems shall operate continuously unless alternative designs are approved. 4. A manual shutoff control shall be provided outside of the room in a position adjacent to the access door to the room or in an approved location. The switch shall be of the break-glass type and shall be labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF. 5. Exhaust ventilation shall be designed to consider the density of the potential fumes or vapors released. For fumes or vapors that are heavier than air, exhaust shall be taken from a point within 12 inches of the floor.
DisapprovedVENTILATION 2704.3 CONTINUED 6. The location of both the exhaust and inlet air openings shall be designed to provide air movement across all portions of the floor or room to prevent the accumulation of vapors. 7. Exhaust ventilation shall not be recirculated within the room or building if the materials stored are capable of emitting hazardous vapors.
DisapprovedCARBON DIOXIDE GAS DETECTOPM AND ALARM SYSTEM Facilities shall declare the storage and use of small Insulated Carbon Dioxide Systems used in Beverage Dispensing. *** This facility proposes one 500 LB CO2 vessel, and is therefore required to comply with the 2009 IFC/IMC ventilation requirements for mechanical or natural ventilation. It is recommended that approved CO2 gas detection and alarm systems be installed in accordance with the following: a) A Listed (by an approved testing laboratory or organization) gas detection and alarm system that is capable of detecting and notifying the building occupants of a gas release that creates carbon dioxide vapors in excess of its Permissible Exposure Level (PEL) at 5,000 parts per million. b) The gas detection and alarm system shall initiate an audible alarm within the room or area in which the system is installed. Activation shall sound a local alarm to notify persons responsible for system operation of a hazardous condition in the area where installed. c) The automatic gas detection and alarm system shall be installed in accordance with the manufacturer's requirements and recommendations. Documentation shall be provided at the time of inspection. Note: Carbon dioxide is 1.5 times heavier than air. Vapors accumulate in low elevations, and in non-ventilated rooms not necessarily limited to the location of the container. The detector(s) should be located in areas where carbon dioxide from a leak will concentrate. Most manufacturers' gas detection sensors are recommended to be installed 12 inches to 24 inches above floor level.
DisapprovedCO2 STORAGE LOCATION NO IDENTIFIED ON PLANS. RESUBMIT AND SHOW CO2 STORAGE AND FILL PORT
FYINFPA = 1-0-0 special = SA; OR 3-0-0 SA TLV-TWAs, 5000 ppm (ACGIH, 2004) TLV-TWA 15 MIN STEL 30,000 ppm High Pressure liquid and gas. Can cause rapid suffocation....CO2 IS AN ASPHYXIANT May cause frostbite. ****** ATTENTION ******* Indoor storage of compressed gases falling into categories such as asphyxiants, irritants can be hazardous regardless of the type of gas involved simply due to the hazards related to asphyxiation. VENTILATION SHALL BE MAINTAINED AND OPERATIONAL. See ventilation comments. When carbon dioxide is transferred---loaded and off loaded through a fill connection located directly adjacent to the tank at the exterior of building. *** fill connection shall be located on exterior of building. ATTENTION: Duplicate gauges shall be installed at the filling connection to enable the driver to fill the container and maintain the required pressure in the container. Pressure relief devices and vents shall be piped to discharge outside in a safe direction. ****************************** NOTE: Storage areas where an accumulation of inert gas could occur should be continuously monitored with an appropriate alarm system to indicate an oxygen deficient atmosphere.
AttentionTHE CHEMICAL INVENTORY, AS DECLARED, DOES NOT EXCEED THE ALLOWABLE THRESHOLDS FOR THE ANNUAL HAZARDOUS MATERIALS OPERATIONAL PERMIT. 500 LB CO2 (inert/asphyxiant = BELOW ********** (permit threshold = 6,000 cf) *** This facility is NOT required to apply for the Annual Hazardous Materials Operational Permit at the CSFD ***This facility is required to have a Construction Hazmat Inspection. *** To Schedule the hazardous materials construction inspection please contact the Division of the Fire Marshal @ 719-385-5978.
ILABELING AND MARKING ** Stationary compressed gas containers, cylinders and tanks shall be marked with the name of the gas Markings shall be visible from any direction of approach. ** Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Piping systems shall be marked in accordance with ANSI A13.1. ** Markings used for piping systems shall consist of the content#s name and include a direction-of-flow arrow. ** Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at a minimum of every 20 feet or fraction thereof throughout the piping run. Portable containers, cylinders and tanks. Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Signs clearly establishing the location and identity of shut-off valves are to be provided. All inert piping systems shall be identified by appropriate labeling with the name of the gas. Warning signs shall be posed at each entrance to the room or enclosure where the bulk inert gas system is installed. Wording shall include: WARNING ---(name of gas) HIGH CONCENTRATION OF GAS MAY OCCUR IN THIS AREA AND MAY CAUSE ASPHYXIATION. VERIFY THAT OXYGEN CONCENTRATION IS ABOVE 19.5% BEFORE ENTERING AND DURING ACTIVITY IN THIS AREA.
IPiping shall be protected against physical damage. Signage shall be provided for piping and hose systems as follows: 1. Above-ground piping systems shall be marked in accordance with ANSI A13.1. 2. Station outlets shall be marked to indicate their intended usage. 3. Signs shall be posted, indicating clearly the location and identity of section shutoff valves.
FYICompressed gas containers, cylinders, tanks and systems shall not be placed in areas where they are capable of being damaged by falling objects. Compressed gas container, cylinder and tank valves shall be protected from physical damage by means of protective caps, collars or similar devices in accordance with Sections 3003.6.1 and 3003.6.2. Compressed gas containers, cylinders and tanks designed for protective caps, collars or other protective devices shall have the caps or devices in place except when the containers, cylinders or tanks are in use or are being serviced or filled.
FYILabeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
AttentionNOTE TO CONTRACTOR & FIRE INSPECTOR: Prior to scheduling the Fire Final please contact the Hazardous Materials Inspector to arrange a Hazardous Materials Inspection prior to final signature being provided.
FYIEquipment, machinery, and required detection and alarm systems associated with the use, storage, or handling of hazardous materials shall be listed or approved. This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
FYIMaterial Safety Data Sheets (MSDS) for all hazardous materials shall be either readily available on the premises as a paper copy, or where approved, shall be permitted to be readily retrievable by electronic access. Approved electronic access shall be as follows: 1. Media shall be USB Flash Drive. 2. Format shall be Microsoft Word 2000 or newer docu-ment, PDF, or other approved format. Where a Knox Box is located at a facility, one USB de-vice shall be stored in the Knox Box and one device shall be located in an approved location(s). All devices and content shall be maintained.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com

printer friendly version Printer friendly version