NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

SKY ZONE - UNIT 1750
01750 WOODMEN RD

Review DateStatusComment(s)
5/28/2014 FYI*****(STANDARD COMMENT 1) This project is: Sky Zone, 1750 E Woodmen Rd: This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****(STANDARD COMMENT) REVISION: Revision Sequence: 2 Scope of Revision: change in communications method from Radio to IP Date of Revision: 5/23/14 All previous approval review comments are applicable and enforeceable.
FYI(SINGLE-FAMILY) MONITORING Off-site monitoring of this fire alarm system is required and shall be provided by an approved monitoring agency. The phone number to be used to report a fire emergency is (719) 444-7632. METHOD: IP - ALL SHARED EQUIPMENT SHALL BE LISTED FOR THIER USE AND SHALL BE PROVIDED WITH THE REQUIRED PROVISIONS OF NFPA 72 SUCH AS BUT NOT LIMITED TO BACK UP POWER SUPPLIES.
5/20/2014 Attention5/20/14 rce *****ATTENTION!!!!! Phone call from Jin Kim stating there are cell towers on this building that are interfering with radio and these systems will need to be changed to IP. Information will be resubmitted but may not be reviewed and approved prior to final inspections already scheduled. He understands inspection will be PARTIAL only if the re-submitted documents have not yet been approved.
5/13/2014 FYI*****(STANDARD COMMENT 1) This project is: Sky Zone, 1750 E Woodmen Rd: This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****(STANDARD COMMENT) REVISION: Revision Sequence: 1 Scope of Revision: addition of duct detectors and a notification appliance Date of Revision: 5/8/14 All previous review comments are applicable and enforceable.
3/12/2014 FYI*****(STANDARD COMMENT 1) This project is: Sky Zone 1750 E Woodmen Rd This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
AttentionAdvised contractor regarding guards needed on Dodgeball and Sky Slam notification devices (due to damage from balls).
ApprovedDue to inaccessible areas behind nets in trampoline areas, some spacing on strobes is being allowed to net area only and not beyond. Second consideration for this decision is that in the open concept it is likely light and sound will be adequate throughout.
FYI*****(STANDARD COMMENT 5) DESIGNER/INSTALLER INFORMATION Fire Alarm system was designed by: CSSC Fire alarm system is being installed by: CSSC
FYI*****(STANDARD COMMENT 6) FIRE ALARM SYSTEM DESIGN: -----Single Family Residential Fire Alarm System --XX---Manual --XX---Automatic -----Dedicated Funtion: ----- AUXILIARY FUNCTIONS: -----Elevator Recall --XX---Duct Detector --XX---Waterflow -----Door Release
FYI*****(STANDARD COMMENT 7) Scope of Work: New FACP, smoke detector, duct detector, occupant notification and (1) manual pull station EXISTING CONDITIONS AS DECLARED: New System
Approved/Corrected*****(STANDARD COMMENT 8) The following RED-LINED items are to be corrected prior to final inspection: 1. Per 2009 Internation Fire Code 907.2 ONE Manual Pull Station is required.
Attention(COMMERCIAL) MONITORING Off-site monitoring of this fire alarm system is required and shall be provided by an approved monitoring agency. The phone number to be used to report a fire emergency is (719) 444-7632. *****ATTENTION!!!!! At the time of review, monitoring/communications is NOT part of this review or approval. Permitted contractor will either submit revised plans, or seperate permitting contractor will submit for additional permit. Submittals must outline what method of communication will be used and how it will conform to 2013 NFPA 72 26.6. MONITORING INFORMATION MUST BE SUBMITTED AND APPROVED BY CSFD PRIOR TO SCHEDULING FIRE FINAL ACCEPTANCE TEST.
FYI(STANDARD COMMENT 13) LICENSED INSTALLER/SERVICE TECHNICIAN An On-Site Installer/Service Technicial shall supervise all on-site work on any fire protection system. This On-Site Installer shall have a current Installer Certificate (RBD Wallet Card), on his/her person, while on the job site.
FYI(STANDARD COMMENT) RECORD OF COMPLETION: The Record of Completion (ROC) shall be filled out in accordance with 10.18.2 for new installations. All modifications made after the initial installation shall be recorded on a revised Record of Completion. All changes shall be shown and the revised ROC and shall include a revision date.
FYI(STANDARD COMMENT) PRE-TEST REQUIREMENT: Before requesting final approval of the installation, the installing contractor shall furnish a written statement that the system has been installed in accordance with approved plans and testing in accordance with the manufacturer's published instructions and the appropriate NFPA requirements. (10.18.1.3) CSFD requires a 100% pre-test - Evidence may be documented on the Record of Completion.
FYI(STANDARD COMMENT) ACCEPTANCE TESTING: At the time of this inspection the Fire Inspector will expect ALL devices involved in this fire alarm project to be tested. The installer should be aware of the fact that in a larger facility there may by a need to isolate the fire alarm system to only the area being tested. The alarm installer is to insure that building owner and/or manager and the General Contractor has been informed of the test criteria, time and date of the test, and have given their approval. Acceptance testing shall be completed in accordance with Chapter 14 of NFPA 72
Attention(STANDARD COMMENT 11) ROUGH-IN PERMIT AND INSPECTIONS: All Fire Alarm systems wiring installed within the City of Colorado Springs must be inspected by the Pikes Peak Regional Building Department PRIOR TO the Fire Final on the system. This will require the installing contractor to obtain a Rough-In Permit issued by the Regional Building Department. Please call RBD at 327-2880 for additional information on how to obtain this permit.
FYI(STANDARD COMMENT 10) INSPECTIONS Due to the dynamic nature of inspectors schedules, PLEASE call your inspection requests in with ample time to allow scheduling. Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( i.e. 20001234 - HM -2 or 20000012 - CN - 1) The CSFD Approved sets of plans are to be on site for all inspections.
FYI(STANDARD COMMENT 19) PLAN REVIEW/PERMIT FEES All fire department fees are to be paid prior to issuance of any permits. These fees must be paid directly to the Colorado Springs Fire Department - Development Review Enterprise - at 2880 International Circle - Suite 200-7.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
FYI(STANDARD COMMENT) RCE REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Rhonda Embres Fire Plans Examiner/Fire Code Inspector Colorado Springs Fire Department Division of the Fire Marshal 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7369 (F) 719-385-7330 rembres@springsgov.com


 