NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

PIKES PEAK LIBRARY DISTRICT
01175 CHAPEL HILLS DR

Review DateStatusComment(s)
5/22/2014 FYI*****(STANDARD COMMENT 1) This project is: Pikes Peak Library District, 1175 Chapel Hills Dr: This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
E-MailFrom: Jin Kim [mailto:jin@csscfire.net] Sent: Thursday, May 22, 2014 6:56 AM To: Withee, Doreen E Subject: RE: pikes peak library - 1175 chapel hills Morning Dee, Those are pendant mount smoke detectors for the Fire Smoke Dampers. In original submittal those where Duct Detectors but we found out we had nowhere to mount the duct detectors. The Heat and Smoke Detector are on top of the shaft since there is a sprinkler head in there. We know we can't shunt trip but with the sprinkler head in there the Heat and Smoke Detector were added. Jin Kim Fire Life Safety Design Manager Commercial Specialist of Southern Colorado Office (719) 638-7574 Cell (719) 231-9745 From: Withee, Doreen E [mailto:DWithee@springsgov.com] Sent: Wednesday, May 21, 2014 4:18 PM To: Jin Kim (jin@csscfire.net) Subject: pikes peak library - 1175 chapel hills Jin - I am reviewing the revisions and have some questions: Smoke detectors D21, D25-29 on sheet 6 - what is the purpose for these detectors? Smoke detectors D6-7 on sheet 7 - what is the purpose for these detectors? Smoke detectors D37-38, D55-56, 58-59, 69 on sheet 8- what is the purpose for these detectors? Why are there detectors at the top of the elevator shaft? Doreen E Withee Fire Protection Engineer II Colorado Springs Fire Department
FYI*****(STANDARD COMMENT) REVISION: Revision Sequence: 1 Scope of Revision: revisions reflecting the as-built condition for final inspection Date of Revision: 4.18.14 Elevator shaft is not enclosed, thus there are sprinklers and detection at the top.
12/26/2013 FYI*****(STANDARD COMMENT 1) This project is: Pikes Peak Library District, 1175 Chapel Hills Dr: This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****(STANDARD COMMENT 6) FIRE ALARM SYSTEM DESIGN: -XXX----Manual WITH VOICE EVAC AUXILIARY FUNCTIONS: --XXX---Elevator Recall ---XXX--Duct Detector --XXX---Waterflow EXISTING DACT COMMUNICATIONS WITH 2 PHONE LINES
Approved/Corrected*****(STANDARD COMMENT 8) The following RED-LINED items are to be corrected prior to final inspection: 1. Verify audible levels meet requirements of 2009 IFC 907.6.2.
FYI(COMMERCIAL) MONITORING Off-site monitoring of this fire alarm system is required and shall be provided by an approved monitoring agency. The phone number to be used to report a fire emergency is (719) 444-7632.
FYI(STANDARD COMMENT 13) LICENSED INSTALLER/SERVICE TECHNICIAN An On-Site Installer/Service Technicial shall supervise all on-site work on any fire protection system. This On-Site Installer shall have a current Installer Certificate (RBD Wallet Card), on his/her person, while on the job site.
FYI(STANDARD COMMENT) RECORD OF COMPLETION: The Record of Completion (ROC) shall be filled out in accordance with 10.18.2 for new installations. All modifications made after the initial installation shall be recorded on a revised Record of Completion. All changes shall be shown and the revised ROC and shall include a revision date.
FYI(STANDARD COMMENT) PRE-TEST REQUIREMENT: Before requesting final approval of the installation, the installing contractor shall furnish a written statement that the system has been installed in accordance with approved plans and testing in accordance with the manufacturer's published instructions and the appropriate NFPA requirements. (10.18.1.3) CSFD requires a 100% pre-test - Evidence may be documented on the Record of Completion.
FYI(STANDARD COMMENT) ACCEPTANCE TESTING: At the time of this inspection the Fire Inspector will expect ALL devices involved in this fire alarm project to be tested. The installer should be aware of the fact that in a larger facility there may by a need to isolate the fire alarm system to only the area being tested. The alarm installer is to insure that building owner and/or manager and the General Contractor has been informed of the test criteria, time and date of the test, and have given their approval. Acceptance testing shall be completed in accordance with Chapter 14 of NFPA 72
Attention(STANDARD COMMENT 11) ROUGH-IN PERMIT AND INSPECTIONS: All Fire Alarm systems wiring installed within the City of Colorado Springs must be inspected by the Pikes Peak Regional Building Department PRIOR TO the Fire Final on the system. This will require the installing contractor to obtain a Rough-In Permit issued by the Regional Building Department. Please call RBD at 327-2880 for additional information on how to obtain this permit.
FYI(STANDARD COMMENT 10) INSPECTIONS Due to the dynamic nature of inspectors schedules, PLEASE call your inspection requests in with ample time to allow scheduling. Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( i.e. 20001234 - HM -2 or 20000012 - CN - 1) The CSFD Approved sets of plans are to be on site for all inspections.
FYI(STANDARD COMMENT 19) PLAN REVIEW/PERMIT FEES All fire department fees are to be paid prior to issuance of any permits. These fees must be paid directly to the Colorado Springs Fire Department - Development Review Enterprise - at 2880 International Circle - Suite 200-7.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, CFPS Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 / (F) 719-385-7330 dwithee@springsgov.com
11/26/2013 FYI*****(STANDARD COMMENT 1) This project is: Pikes Peak Library District, 1175 Chapel Hills Dr This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
Disapproved*****(STANDARD COMMENT 19) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Ceiling heights are not provided - there is an atrium which is associated with ceilings in excess of 20-feet. 2. room names are missing from areas 3. Areas are lacking notification coverage 4. Elevators and smokes in the shaft - if the pit is fire sprinklered, then the smoke detector shall be provided in the pit - not at the top of the shaft as your plans depict. 5. this is an emergency communication system (voice evac) thus the ADS's must be defined and intelligibility requirements called out for each ADS. Also review the disapproved plans for additional written comments prior to submittal of new plans.
FYI(STANDARD COMMENT 20) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provid submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
Attention(STANDARD COMMENT 26) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, CFPS Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 / (F) 719-385-7330 dwithee@springsgov.com


 