NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING. System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.
CHEYENNE MOUNTAIN CARE CENTER 00835 TENDERFOOT HILL RD
| Review Date | Status | Comment(s) |
| 3/13/2013 |
FYI | ***** 20-HEAD LETTER:
Date Submitted: 03/13/13
Contractor: Cintas
Total number of heads affected : 8
Location of work: East "starred" wing
Bldg permit #: N/A
Flex Connections approved in this facility?: NO
Brand: if known
Equivalent Length: if known
UL 2443/FM 1637 Complaint: |
| 3/11/2013 |
Disapproved | *****20-HEAD LETTER DISAPPROVALS
--XX---The information you have provided is not complete, please provide the following:
--XX---RME signature required
|
|