NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

 
   

Review DateStatusComment(s)
3/29/2013 FYI*****(STANDARD COMMENT 1) This project is: UCCS Parking Garage, 1420 Austin Bluffs Parkway: new 4 level parking garage with activity field on top (no spectator seating) Date of Plans: 3.29.13 review date You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
Attention*****(STANDARD COMMENT 2) BUILDING DATA: Size of Bldg. --477208--- sq ft Construction Type --I-A---- (open parking using largest floor for fire flow requirements) Fire Sprinklers Y----- N----XXX- Fire Walls Y ----- N --xxx--- Required GPM: --3500--- gpm # of hydrant(s) required: ---4-- Max AVG spacing between hydrants: ---350-- ft Max hose lay: ---210-- ft
FYI*****(STANDARD COMMENT) FIRE FLOW/HYDRANT REQUIREMENTS MET: On this site the theoretical water flows are --4200-- gpm, and the numbers of hydrant(s) are -4---. This site, based upon the provided theoretical modeled fire flows, appear to meet the minimum flow requirements and/or the number of hydrant(s) for this structure.
Attention(STANDARD COMMENT) READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
Disapproved(DISAPPROVED) DEVELOPMENT PLAN According to the CSFD records for this project, the Development Plan for this site has not been approved by the fire department. This hydrant/water plan can not be approved until the D.P. has been approved by the CSFD.
FYI(STANDARD COMMENT) DISAPPROVED ITEMS ADDRESSED: The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1. Building data has been provided. 2. fire flow report has been provided. 3. water mains are identified as public mains.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
3/25/2013 FYI*****(STANDARD COMMENT 1) This project is: UCCS Parking Garage, 1420 Austin Bluffs Parkway Date of Plans: N/A You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYI*****(STANDARD COMMENT) SCOPE OF WORK: --XXX--WATER PLAN
Disapproved(DISAPPROVED) BUILDING DATA The "BUILDING DATA" information must be provided for each building, and should be indicated inside the footprint layout of the building, or just next to the footprint, and on each of your plan sheets that are to be signed by CSFD: Please refer to our Water Supplies Information packet for the required information/template.
Disapproved(DISAPPROVED) PUBLIC/PRIVATE All water lines are not labeled as to PUBLIC or PRIVATE systems - Please label correctly. Because of this the correct plan review and inspection fees may not be able to be determined at the time of this review, and additional fees may be required once the correct determination has been made.
Disapproved(DISAPPROVED) DEVELOPMENT PLAN According to the CSFD records for this project, the Development Plan for this site has not been approved by the fire department. This hydrant/water plan can not be approved until the D.P. has been approved by the CSFD.
Disapproved(DISAPPROVED) FIRE DEPARTMENT CONNECTION Your plans do not indicate, or have placed the Fire Department Connection (FDC) to the sprinkler systems in an unacceptable location.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)


 