RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

LOCKHEED MARTIN
02375 TELSTAR DR

Review DateStatusComment(s)
2/27/2013 FYILockheed Martin, 2375 Telstar Dr, Suite 150: interior remodel - partial change of occupancy SYSTEMS: Fire sprinkler for area; fire alarm for occupancy CN:Code: 09 IBC - 09 IFC - 11 PPRBC /Class: B/ Const: II-B /Stories: 1/Size: 20,407 THIS SCOPE /OL: 327 THIS SCOPE HAZMAT REVIEW FOR UPS-BATTERY ROOM see sheet A1 REVISE 2/15/13 67 GALLONS ELECTROLYTE You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYIBATTERIES SYSTEMS SHALL BE IN ACCORDANCE WITH SECTION 608 OF THE IFC 2009: 1. The batteries shall have venting caps to relieve pressure, which is often Hydrogen gas. 2. VRLA or other sealed non-venting caps shall be equipped with resealing flame arresting safety caps. 3. Lithium Ion and Lithium metal polymer batteries shall not require vented caps. 4. VRLA and Lithium -ion and lithium metal polymer battery systems shall be provided with a listed device or other approved method to preclude, detect or control Thermal runaway. 5. Battery systems shall be permitted in the same room or area as they equipment they support. 6. Battery systems shall be housed in a non-combustible locked cabinet or enclosure to prevent unauthorized personnel from accessing the system. 7. Enclosures of stationary battery systems shall comply with the IBC. When stationary batteries are installed in separate equipment room accessible only to authorized personnel, they shall be permitted to be installed on an open rack for ease of maintenance. 8. Spill control and a means of spill response shall be provided. 9. An approved method of control and cleaning up the spill shall be provided. 10. Ventilation shall be provided in accordance with the IMC. Ventilation systems shall ventilate the floor area of the room at a minimum of 1 cfm/sq. ft. and shall be provided on a continuous basis. 11. The ventilation system shall be designed to limit the maximum concentration of Hydrogen 1% of the total volume of the room. 12. Temperature Control shall be provided to maintain safe operating conditions of the batteries. 13. Signs and placards shall be appropriately posted. 14. Seismic protection shall be provided for the battery storage system in accordance with the IBC. 15. Approved smoke detection shall be provided. *** ALL ABOVE ITEMS ADDRESSED AND COMPLIANT PER IFC 2009, ON PLAN SHEET A1, DATED 2/15/13. ALSO ReReviewed by PPRBD and released for permit 2/22/13.
AttentionATTENTION ATTENTION 608.6.3 Mechanical ventilation systems shall be supervised at an approved central proprietary or remote station service or shall initiate an audible and visual signal at a constantly attended on-site location. ATTENTION ****** THIS IS REQUIRED TO BE COMPLIANT WITH CODE *** This section requires the supervision of both the required room and cabinets ventilation where mechanical systems are employed to provide notification of a system failure--to provide warning and reduce hydrogen concentration to build to hazardous levels. *** This item shall be compliant per plan sheet A4. Discussion with architect and owner states monitoring likely to go through on site security.
FYIStationary Battery Systems IFC 2009, SECTION 608 Stationary storage battery systems having an electrolyte capacity of more than 50 gallons for flooded lead-acid, nickel cadmium (Ni-Cd) and valve-regulated lead-acid (VRLA), or 1,000 pounds for lithium-ion and lithium metal polymer, used for facility standby power, emergency power or uninterrupted power supplies shall comply with section 608 and Table 608.1. This facility reports 67 gallons of electrolyte VRLA BATTERIES IN CABINET IN BATTERY ROOM
FYICHEMICAL INVENTORY, AS DECLARED INTERIOR UPS BATTERY ROOM 67 GALLONS ELECTROLYTE; VRLA BATTERIES IN CABINET ATTENTION OWNER: ****This facility exceeds the hazardous materials permit amount threshold for flammable and combustible liquids, and electrolytes, therefore, this facility is required to apply for a CSFD Annual Operational Permit This facility is enrolled in the permit program, please update your material inventory with the Hazmat Specialist, Inspector, Mr Jay Weightman at the time of your construction inspection. This facility will require a Hazardous Materials permit inspection for: ** Annual Operational Hazmat Permit (annual, automatically renewed by CSFD, fees apply *** THIS FACILITY WILL REQUIRE A HAZMAT CONSTRUCTION FINAL INSPECTION FOR PERMIT AND CERTIFICATE OF OCCUPANCY. To schedule your Hazmat Inspections-- please contact the Divsion of the Fire Marshal @ 719-385-5978.
AttentionEquipment, machinery, and required detection and alarm systems associated with the use, storage, or handling of hazardous materials shall be listed or approved. This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final. THIS INCLUDES THE HYDROGEN SENSOR, AND VENTILATION SYSTEMS. PLEASE BE PREPARED TO TEST THIS AT THE TIME OF YOUR CONSTRUCTION INSPECTION. HAVE ALL DOCUMENTS, AND CONTRACTORS NECESSARY AVAILABLE AT THE TIME OF INSPECTION.
FYILabeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final. Doors into electrical equipment rooms or buildings containing stationary battery systems shall be provided with approved signs. The signs shall state that: 1. The room contains energized battery systems. 2. The room contains energized electrical circuits. 3. The battery electrolyte solutions, where present, are corrosive liquids.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com

printer friendly version Printer friendly version