| Review Date | Status | Comment(s) |
| 2/22/2013 |
FYI | Burger King, 375 S Academy Bl: interior remodel and addition of exterior walk-in cooler
SYSTEMS: kitchen hood systems
CN:Code: 09 IBC - 09 IFC - 11 PPRBC /Class: A2 / Const: V-B /Stories: 1/Size:3625 /OL: 100
Hazmat Plan Review for CO2 for beverage dispensing: One 450 pound CO2 vessel CARBOMIZER
SEE ELECTRONIC DOCUMENTS
You can access our web site for the latest fire department plan review comments:
1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS
2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
|
| FYI | CO2 EXISTING system being relocated to new storage room #107due to renovation.
Initial plans were submitted with exhaust ventilation system at new storage location #107. Per PPRBD mechanical dept. instructed architect to install monitoring/detection system in lieu of ventilation due to energy code. Architect corrected plans, removed ventilation and installed monitoring-detection system per Mechanical Dept. direction. SEE PLAN SHEE A4 FOR REVISED PLANS, CO2 location, Monitoring-Detection per IFC Admin Ruling. These revisions and instructions were completed all prior to Hazmat Plan review 2/22/13.
1) Tank and piping specifications (CHART INDUSTRIES)
2) Exterior fill port and specs.
3) Monitoring-detection system will be installed per Chart Ind. as part of their installation
guidelines. CO2 CONTRACTOR: General Air
4) Mechanical/ventilation system revised. Per PPRBD Mechanical reviewed and released for permit revised ventilation. CO2 shown on plan sheet A4.
(Plan reviewer spoke with Tina Dorn of RVP who informed plan reviewer of the CO2 instructions) |
| FYI | ONE, 450 lb CARBON DIOXIDE VESSEL (CO2)
CUBIC FEET = 3,933 scf
Location: unidentified on plans
CHART INDUSTRIES is the supplier
NFPA = 1-0-0 special = SA
TLV-TWAs, 5000 ppm (ACGIH, 2004)
TLV-TWA 15 MIN STEL 30,000 ppm
High Pressure liquid and gas. Can cause rapid suffocation....CO2 IS AN ASPHYXIANT
May cause frostbite.
****** ATTENTION *******
Indoor storage of compressed gases falling into categories such as asphyxiants, irritants can be hazardous regardless of the type of gas involved simply due to the hazards related to asphyxiation.
VENTILATION SHALL BE MAINTAINED AND OPERATIONAL. See ventilation comments.
The carbon dioxide shall be transferred---loaded and off loaded through a fill connection located directly adjacent to the tank at the exterior of building.
*** fill connection shall be located on exterior of building. Not identified
ATTENTION: Duplicate gauges shall be installed at the filling connection to enable the driver to fill the container and maintain the required pressure in the container.
Pressure relief devices and vents shall be piped to discharge outside in a safe direction.
***Not identified on or with plan set.
******************************
NOTE: Storage areas where an accumulation of inert gas could occur should be continuously monitored with an appropriate alarm system to indicate an oxygen deficient atmosphere. (Recommended)
****A CO2 detector or audible/visual alarm is noted on plan sheet A4 dated February 8, 2013 |
| FYI | CARBON DIOXIDE
Facilities shall declare the storage and use of small Insulated Carbon Dioxide Systems used in Beverage Dispensing.
Gaseous Carbon Dioxide is an asphyxiant gas and exposure to high concentrations may cause toxic effects including asphyxiation. To provide for the safety of building occupants and emergency personnel, ventilation in accordance with the IFC Sections 3007.2, 2704.3 or 2705.1.9 is required where concentrations of this gas are stored or present.
All new or proposed building ventilation system designs shall submit for review and permit approval to the Pikes Peak Regional Building Department.
*** ATTENTION**** 2704.3 VENTILATION
Indoor storage areas and storage buildings shall be provided with mechanical exhaust ventilation or natural
ventilation where natural ventilation can be shown to be acceptable for the materials as stored
OR a Listed, approved CO2 detection system, in accordance with the IFC Administrative Ruling.
System requirements. Exhaust ventilation systems shall comply with all of the following:
1. Installation shall be in accordance with the International Mechanical Code.
2. Mechanical ventilation shall be at a rate of not less than 1 cubic foot per minute per square foot of floor area over the storage area.
3. Systems shall operate continuously unless alternative designs are approved.
4. A manual shutoff control shall be provided outside of the room in a position adjacent to the access door to the room or in an approved location. The switch shall be of the break-glass type and shall be labeled:
VENTILATION SYSTEM EMERGENCY SHUTOFF.
5. Exhaust ventilation shall be designed to consider the density of the potential fumes or vapors released. For
fumes or vapors that are heavier than air, exhaust shall be taken from a point within 12 inches of the floor.
|
| FYI | VENTILATION 2704.3 CONTINUED
6. The location of both the exhaust and inlet air openings shall be designed to provide air movement across all
portions of the floor or room to prevent the accumulation of vapors.
7. Exhaust ventilation shall not be recirculated within the room or building if the materials stored are capable of
emitting hazardous vapors.
******************** ATTENTION***************************
PPRBD Mechanical has released for permit these plans.
|
| Attention | THE CHEMICAL INVENTORY, AS DECLARED, EXCEEDS THE ALLOWABLE THRESHOLDS FOR THE ANNUAL HAZARDOUS MATERIALS OPERATIONAL PERMIT.
450 LB CO2 (inert/asphyxiant = 3,933 scf ********** (permit threshold = 6,000 cf)
*** This facility is NOT required to apply for the Annual Hazardous Materials Operational Permit at the CSFD online website: http://csfd.springsgov.com/hamish/
***This facility is required to have a Construction Hazmat Inspection.
*** To Schedule the hazardous materials construction inspection please contact the Division of the Fire Marshal @ 719-385-5978. *** For further questions or information please contact the Division of the Fire Marshal main number at 719-385-5978. |
| I | LABELING AND MARKING
** Stationary compressed gas containers, cylinders and tanks shall be marked with the name of the gas Markings shall be visible from any direction of approach.
** Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7.
Piping systems shall be marked in accordance with ANSI A13.1.
** Markings used for piping systems shall consist of the content#s name and include a direction-of-flow arrow.
** Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of
direction; and at a minimum of every 20 feet or fraction thereof throughout the piping run.
Portable containers, cylinders and tanks. Portable compressed gas containers, cylinders and tanks shall be
marked in accordance with CGA C-7.
Signs clearly establishing the location and identity of shut-off valves are to be provided.
All inert piping systems shall be identified by appropriate labeling with the name of the gas.
Warning signs shall be posed at each entrance to the room or enclosure where the bulk inert gas system is installed. Wording shall include:
WARNING ---(name of gas)
HIGH CONCENTRATION OF GAS MAY OCCUR
IN THIS AREA AND MAY CAUSE ASPHYXIATION.
VERIFY THAT OXYGEN CONCENTRATION IS ABOVE 19.5% BEFORE ENTERING
AND DURING ACTIVITY IN THIS AREA. |
| I | Piping shall be protected against physical damage.
Signage shall be provided for piping and hose systems as follows:
1. Above-ground piping systems shall be marked in
accordance with ANSI A13.1.
2. Station outlets shall be marked to indicate their intended
usage.
3. Signs shall be posted, indicating clearly the location and
identity of section shutoff valves. |
| FYI | Labeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final. |
| Attention | NOTE TO CONTRACTOR & FIRE INSPECTOR: Prior to scheduling the Fire Final please contact the Hazardous Materials Inspector to arrange a Hazardous Materials Inspection prior to final signature being provided. |
| FYI | Equipment, machinery, and required detection and alarm systems associated with the use, storage, or handling of hazardous materials shall be listed or approved. This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final. |
| FYI | A minimum of 1 set of Material Safety Data Sheets (MSDS), hard copy, must be readily availiable on the premises at all times. |