NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

NEW DAWN ASSISTED LIVING BUILDING C
04185 BRIARGATE PKWY

Review DateStatusComment(s)
10/17/2013 FYINew Dawn Assisted Living, Building C, 4185 Briargate Py: new assisted living facility - 16 beds SYSTEMS: fire sprinkler (13) for occupancy/use/area; fire alarm for occupancy (2010 NFPA) CN:Code: 09 IBC - 09 IFC - 11 PPRBC /Class: I2, B,A2 / Const: V-A /Stories: /Size:10,079 /OL: 177 FH:Required Flow: 1500 gpm /# Hydrants 1/On site flow: DV: 2012-0239 ATTENTION: See our web site for our latest fire department plan review comments. From the Pikes Peak Regional Building Department web site (www.pprbd.org), select "RELATED WEB SITES" in the upper right corner. Click on Colorado Springs FIRE PREVENTION. Then select PLAN REVIEW STATUS, click VIEW PLAN REVIEW STATUS. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYIEmergency and standby power systems required by this code or the International Building Code shall be installed in accordance with this code, NFPA 110 and NFPA 111. Existing installations shall be maintained in accordance with the original approval. 604.1.1 Stationary generators. Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200.
FYIABOVE GROUND FUEL TANKS The CSFD requires a Construction Permit for the installation of any aboveground fuel tank in excess of 60 gallons. (This tank declared as 220 gal by applicant. Flammable and combustible liquids shall comply with the IFC 2009 CHAPTERS 34 AND 27 as amended, and NFPA 30. It is the responsibility of the TANK INSTALLER to submit an application for the tank installation permit prior to installation. The tank installer shall submit to : Kay Yeager CSFD Office of the Fire Marshal 375 Printers Parkway Exterior tanks will be required to have vehicular protection diagrammed and installed in accordance with the 2009 IFC, Chapter 3. Any associated piping shall be diagramed and submitted as well. *********** 220 GALLON DIESEL DW INTEGRAL AST GENERATOR CONCRETE BLOCK WALL ENCLOSURE (provides vehicle protection
I*** ATTENTION*** TANK INSTALLATION PERMIT INSPECTION REQUIRED. ** This facility reports 0 gallons of electrolyte associated with generator CONTACT THE DIVISION OF THE FIRE MARSHAL @ 719-385-5978 TO SCHEDULE YOUR INSPECTIONS WITH HAZMAT SPECIALIST JAY WEIGHTMAN.
FYIBATTERIES As declared on this submittal, this facility will not contain electrolyte solution. This quantity of electrolyte solution DOES NOT exceed the max allowable volume per control area (500 gal) as defined by 2009 IFC Table 2703.1.1(2). (CORROSIVE) This quantity of electrolyte solution DOES NOT exceed the max allowable volume per control area (500 gal) as defined by 2009 IFC Table 2703.1.1(2). This quantity of electrolyte solution DOES NOT exceed the max allowable volume per control area for permit quantities of (100 gal) as defined in Sections 105 and 608 of the 2009 IFC as amended.
FYILabeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final. ************** ATTENTION: The NFPA ratings found on the MSDS for diesel and batteries shall be identified on the NFPA placard.
FYI{AST} A minimum 20B rated fire extinguisher shall be located no closer than 10 feet to the storage tank and no farther than 50 feet. A single fire extinguisher may provide coverage for more than one tank but the minimum and maximum travel distances shall be achieved.
1/30/2013 AttentionINTEGRAL GENERATOR TANK WITH GENERATOR. 1/30/13 PHONE CALL FROM TERRY POLSON PLANS SUBMITTED WITHOUT PERMIT APPLICATION FORMS AND SUPPORT DOCUMENTS RE TANK SPECS ETC. PER TERRY, 1/30/13: NO HAZMAT ON THIS SITE. ONLY A GENERATOR WITH TANK. PER YEAGER: PLAN REVIEW FOR HAZMAT WILL BE N/A. YEAGER WILL SIGN PLANS N/A. RESUBMIT TANK/GENERATOR WITH PERMIT APPLICATION AND DOCUMENTS UNDER DEFERRED SUBMITTAL-SEPARATE COVER. NO HAZMAT REVIEW. WEBSITE FOR PERMIT FORMS AND CHECKLIST FOR ATTACHMENTS AND PLAN DOCUMENTS. REDUCE SIZE SET OF PLANS FOR PERMIT APPLICATION. THIS WILL NOT DELAY YOUR CONSTRUCTION PLANS OR PERMIT. TERRY NOT SURE IF MORE THAN ONE GENERATOR AT THIS TIME. 1/30/13: PHONE CALL PER TERRY ONE GENERATOR ONLY AT BUILDING C.
FYINew Dawn Assisted Living, The Medical Pavillion at Briargate, FH:Required Flow: gpm /# Hydrants /On site flow: DV: Amendment to the original developmetn plan to adjust the location of Building D and adjust location of fire lanes. This amendment affects three buildings; Located northwest of Family PLace and Austin Bluffs Parkway. Additional Comments:


 