NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING. System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.
UCH MEMORIAL HEALTH CENTRAL MAIN 01400 BOULDER ST
| Review Date | Status | Comment(s) |
| 12/19/2012 |
FYI | ***** 5-DEVICE LETTER:
Date Submitted: 12/18/12
Date of Work: 12/18/12
Contractor: ELight
Scope : Adding notification and smoke damper and exhaust fan.
Current Draw: 8.824 AH
Battery Size:12V/12AH
Location of work: GI Procedure Rm 1734
Bldg permit #: I56401
|
| 12/17/2012 |
Disapproved | ***** 5-DEVICE LETTER DISAPPROVALS:
--XX--The information you have provided is not complete, please provide the following:
Size of batteries being provided.
|
| 12/10/2012 |
Disapproved | ***** 5-DEVICE LETTER DISAPPROVALS:
-----Multiple letters have been submitted for this scope of work/building permit, thus the total modifications exceed 5 devices.
-----Your company is currently restricted from use of this privilege through a ruling from Fire Board of Appeals.
-----Your company is currently not licensed to perform work on fire suppression systems, please contact Contractor Licensing at 719-327-2880 to correct this.
--XX---The information you have provided is not complete, please provide the following:
There is no Regional Building Permit issued for this project yet
|
|