RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

CARMIKE 13 CINEPLEX
01770 BRIARGATE BL

Review DateStatusComment(s)
1/10/2013 E-MailMr. Kauk, Per your and Mr. Edwards conversation this morning concerning the CO2 exhaust, we will omit the revised M1.1 & M2.1 sheets that were sent yesterday. Thanks, Ronny Rahn , AIA Artech 423.643.0705 direct 423.503.5330 cell www.artechdgn.com Artech strives to reduce, reuse & recycle. Please think before you print. ________________________________________ From: Russell Kauk [mailto:russell@pprbd.org] Sent: Wednesday, January 09, 2013 6:31 PM To: Ronny Rahn Cc: Kay Yeager Subject: Carmike Cinemas Ronny I've plotted out and looked at M1.1 & M2.1 that was forwarded to Kay Yeager. The ventilation that they've shown in Storage Room 105.8, is properly ventilated per the 2009 IMC Table 403.3, providing the space with ventilation air and return air. What you've added is a ducted return air from the space. Now that it has become the room in which they've placed the CO2 tank, it's still a storage room that requires ventilation (supply air) to serve the space, however, you should remove the return air as previously approved and just have the door undercut to allow the transfer of the supply air out of the room. Besides, they have an in-correct cfm shown for the return air. You're showing 50 cfm S.A. with 100 cfm R.A., not quite sure how that works. If you were to provide the ventilation based solely on the CO2 tank, they'd have to exhaust the space at a rate of 1 cfm/square foot, which we no longer want provided, since it becomes an issue with IECC and wasting energy. The only requirement for the CO2 tank is a vapor detector and alarm, installed per the manufacturer's installation instructions. The change on sheet M2.1 is EF-15, the exhaust cfms have increased, along with changes to some of the other characteristics in the schedule. Please give me a call at your earliest convenience, so we can discuss these changes to the approved mechanical plans Thanks Russ
1/9/2013 FYIThis project is: Carmike Cinemas, Chapel Hills Mall, 1770 Briargate Bl: demolition and addition of Cineplex SYSTEMS: fire sprinkler for occupancy/use; fire alarm for occupancy CN:Code: 09 IBC -09 IFC - 11 PPRBC /Class: A1 / Const:II-B /Stories: 1/Size: 57,271/OL: 3272 FH:Required Flow: 2500 gpm /# Hydrants 3/On site flow: TBD DV:Proposing to demolish the Kmart building and build a new 13-screen cinema in its place. Additional Comments: RAPID RESPONSE! Chapel Hills Shopping Center Subdivision No 6. HAZMAT PLAN REVIEW: ONE 750 LB CARBON DIOXIDE FOR BEVERAGE DISPENSING
FYIRESUBMITTED: The plans have been re-submitted, and the disapproved issues have been addressed as follows: APPROVED **PLEASE NOTE** ALL COMMENTS FOUND ON PREVIOUS PLAN REVIEWS REMAIN ENFORCEABLE UNLESS OTHERWISE NOTED IN THIS REVIEW. 1 VIA EMAIL RESUBMITTED PLAN SHEETS: E1.3 CO2 alarm added; M1.1 AND M2.1 ventilation and new storage location for CO2 container in Room 105.8. 2) Dedicated storage room with ventilation and ANALOX CO2 monitoring/detection system. 3) SEE SCANNED DOCUMENTS 4) REFRIGERANT: 3 circuits @ 6.10 lbs per circuit; R 410 A . 50%/50% R32/125; A1 refrigerant; NFPA = 2-0-0. 5) CONTRACTOR/OWNER IS RESPONSIBLE FOR SUBMITTING CO2 SPEC SHEETS FOR CONTAINER AND PIPING SYSTEM; AND FILL BOX CONNECTION PRIOR TO HAZMAT PERMIT INSPECTION FOR CERTIFICATE OF OCCUPANCY. 6) ATTENTION INSPECTOR 750 lbs of CO2 = 6,555.9441 scf. The CO2 system is an inert asphyxiant gas and is greater than the annual hazardous materials permit threshold of 6,000 scf. Therefore, this facility is required to be enrolled in the annual Hazardous Materials Permit program. CSFD Hazmat Specialist/Inspector and owner shall coordinate this permit.
FYIEquipment, machinery, and required detection and alarm systems associated with the use, storage, or handling of hazardous materials shall be listed or approved. This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final. *** CO2 SYSTEM SHALL BE REQUIRED TO BE TESTED
FYIKay, here#re the mechanical drawings. We tied the storage room into the restroom exhaust system to exhaust 1 CFM/Ft2 from the storage room with the CO2 cylinder. Thanks! Mike Whitfield Campbell & Associates 651 East Fourth Street
1/4/2013 FYIThis project is: Carmike Cinemas, Chapel Hills Mall, 1770 Briargate Bl: demolition and addition of Cineplex SYSTEMS: fire sprinkler for occupancy/use; fire alarm for occupancy CN:Code: 09 IBC -09 IFC - 11 PPRBC /Class: A1 / Const:II-B /Stories: 1/Size: 57,271/OL: 3272 FH:Required Flow: 2500 gpm /# Hydrants 3/On site flow: TBD DV:Proposing to demolish the Kmart building and build a new 13-screen cinema in its place. Additional Comments: RAPID RESPONSE! Chapel Hills Shopping Center Subdivision No 6. HAZMAT PLAN REVIEW: ONE 750 LB CARBON DIOXIDE FOR BEVERAGE DISPENSING ATTENTION: See our web site for our latest plan review comments for your job at: www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work.
FYILABELING AND MARKING ** Stationary compressed gas containers, cylinders and tanks shall be marked with the name of the gas Markings shall be visible from any direction of approach. ** Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Piping systems shall be marked in accordance with ANSI A13.1. ** Markings used for piping systems shall consist of the content#s name and include a direction-of-flow arrow. ** Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at a minimum of every 20 feet or fraction thereof throughout the piping run. Portable containers, cylinders and tanks. Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Signs clearly establishing the location and identity of shut-off valves are to be provided. All inert piping systems shall be identified by appropriate labeling with the name of the gas. Warning signs shall be posed at each entrance to the room or enclosure where the bulk inert gas system is installed. Wording shall include: WARNING ---(name of gas) HIGH CONCENTRATION OF GAS MAY OCCUR IN THIS AREA AND MAY CAUSE ASPHYXIATION. VERIFY THAT OXYGEN CONCENTRATION IS ABOVE 19.5% BEFORE ENTERING AND DURING ACTIVITY IN THIS AREA. Labeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
FYIPiping shall be protected against physical damage. Signage shall be provided for piping and hose systems as follows: 1. Above-ground piping systems shall be marked in accordance with ANSI A13.1. 2. Station outlets shall be marked to indicate their intended usage. 3. Signs shall be posted, indicating clearly the location and identity of section shutoff valves. *****REFRIGERATION PIPING********
FYIATTENTION CO2, REFRIGERATION, OTHER LABELING AND MARKING ** Stationary compressed gas containers, cylinders and tanks shall be marked with the name of the gas Markings shall be visible from any direction of approach. ** Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Piping systems shall be marked in accordance with ANSI A13.1. ** Markings used for piping systems shall consist of the content#s name and include a direction-of-flow arrow. ** Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at a minimum of every 20 feet or fraction thereof throughout the piping run. Portable containers, cylinders and tanks. Portable compressed gas containers, cylinders and tanks shall be marked in accordance with CGA C-7. Signs clearly establishing the location and identity of shut-off valves are to be provided. All inert piping systems shall be identified by appropriate labeling with the name of the gas. Warning signs shall be posed at each entrance to the room or enclosure where the bulk inert gas system is installed. Wording shall include: WARNING ---(name of gas) HIGH CONCENTRATION OF GAS MAY OCCUR IN THIS AREA AND MAY CAUSE ASPHYXIATION. VERIFY THAT OXYGEN CONCENTRATION IS ABOVE 19.5% BEFORE ENTERING AND DURING ACTIVITY IN THIS AREA.
FYIMSDS 407.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be either readily available on the premises as a paper copy, or where approved, shall be permitted to be readi-ly retrievable by electronic access. Approved electronic access shall be as follows: 1. Media shall be USB Flash Drive. 2. Format shall be Microsoft Word 2000 or newer docu-ment, PDF, or other approved format. Where a Knox Box is located at a facility, one USB de-vice shall be stored in the Knox Box and one device shall be located in an approved location(s). All devices and content shall be maintained.
FYICARBON DIOXIDE SEE ALSO REDLINE COMMENTS Facilities shall declare the storage and use of small Insulated Carbon Dioxide Systems used in Beverage Dispensing. Gaseous Carbon Dioxide is an asphyxiant gas and exposure to high concentrations may cause toxic effects including asphyxiation. To provide for the safety of building occupants and emergency personnel, ventilation in accordance with the IFC Sections 3007.2, 2704.3 or 2705.1.9 is required where concentrations of this gas are stored or present. ATTENTION*** THIS CO2 SYSTEMS >100 LBS, REQUIRE VENTILATION IN ACCORDANCE WITH THE IMC/IFC 2009. VENTILATION REQS. ARE SETFORTH IN IFC 2009, 3007.2; 2704.3 OR 2705.1.9 AND IMC 2009, SECTION 502.8.1, 502.8.1.1 All new or proposed building ventilation system designs shall submit for review to the Pikes Peak Regional Building Department.CARBON DIOXIDE GAS DETECTION AND ALARM SYSTEM Facilities shall declare the storage and use of small Insulated Carbon Dioxide Systems used in Beverage Dispensing. This facility is required to comply with the 2009 IFC/IMC.*** ONE OF THE FOLLOWING SHALL BE REQUIRED 1) Ventilation requirements complying with mechanical exhaust ventilation in accordance with the IMC 2009 2) Natural ventilation in accordance with the IMC 2009 3) Provide an approved-LISTED CO2 gas detection and alarm system in accordance with the following: 3a) A Listed (by an approved testing laboratory or organization) gas detection and alarm system that is capable of detecting and notifying the building occupants of a gas release that creates carbon dioxide vapors in excess of its Permissible Exposure Level (PEL) at 5,000 parts per million. 3b) The gas detection and alarm system shall initiate an audible alarm within the room or area in which the system is installed. Activation shall sound a local alarm to notify persons responsible for system operation of a hazardous condition in the area where installed. 3c) The automatic gas detection and alarm system shall be installed in accordance with the manufacturer's requirements and recommendations. Documentation shall be provided at the time of inspection. Note: Carbon dioxide is 1.5 times heavier than air. Vapors accumulate in low elevations, and in non-ventilated rooms not necessarily limited to the location of the container. The detector(s) should be located in areas where carbon dioxide from a leak will concentrate. Most manufacturers' gas detection sensors are recommended to be installed 12 inches to 24 inches above floor level.
FYIONE, CARBON DIOXIDE VESSEL (CO2) SHOWN NO ADDITIONAL INFORMATION WAS PROVIDED. SUBMIT QUANTITY, SIZE IN GALLONS/LBS, LOCATION, FILL PORT, CONTAINER SPECIFICATIONS, PIPING SPECIFICATIONS, VENDOR NAME. NFPA = 3-0-0 special = SA (liquified) NFPA = 1-0-0 special = SA (gas) TLV-TWAs, 5000 ppm (ACGIH, 2004) TLV-TWA 15 MIN STEL 30,000 ppm High Pressure liquid and gas. Can cause rapid suffocation....CO2 IS AN ASPHYXIANT May cause frostbite. ****** ATTENTION ******* Indoor storage of compressed gases falling into categories such as asphyxiants, irritants can be hazardous regardless of the type of gas involved simply due to the hazards related to asphyxiation. VENTILATION SHALL BE MAINTAINED AND OPERATIONAL. See ventilation comments. The carbon dioxide shall be transferred---loaded and off loaded through a fill connection located directly adjacent to the tank at the exterior of building. *** fill connection noted exterior of building. OK ATTENTION: Duplicate gauges shall be installed at the filling connection to enable the driver to fill the container and maintain the required pressure in the container. Pressure relief devices and vents shall be piped to discharge outside in a safe direction. ****************************** NOTE: Storage areas where an accumulation of inert gas could occur should be continuously monitored with an appropriate alarm system to indicate an oxygen deficient atmosphere. (Recommend only, not required when ventilation requirements are compliant)
AttentionATTENTION: This item must be provided to the CSFD PRIOR to requesting your fire finals for occupancy. HMMP - A Hazardous Materials Management Plan (HMMP) must be developed, submitted, and continuously maintained for this location. The information contained within the HMMP is required in order to complete the current project plan review. Guidance on the format and required information for the HMMP can be found on the CSFD Web Site and in an Information Packet available from the CSFD Office of the Fire Marshal.
Disapproved * CARBON DIOXIDE PIPING specifications. NOTE: IFC 2009, 2703.2.2 Piping, tubing, valves and fittings. Piping, tubing, valves and fittings conveying hazardous materials shall be designed and installed in accordance with approved standards and shall be in accordance with Sections 2703.2.2.1 and 2703.2.2.2. Piping, tubing, valves, fittings and related components shall be designed and fabricated from materials that are compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress and exposure to which they are subject. *** RESUBMIT PLANS AND PROVIDE THE FOLLOWING CO2 CONTAINER SIZE (LBS); CO2 SPECIFICATIONS CUT SHEETS CO2 LOCATION IDENTIFIED ON PLAN SHEET; CO2 FILL CONNECTION IDENTIFIED ON PLAN SHEET PIPING TUBING AND VALVE DESIGN SPECIFICATIONS DECLARE VENTILATION OR MONITORING-DETECTION SYSTEM. PROVIDE IF MONITORING DETECTION SYSTEM IS TO BE PROVIDED, SUBMIT THE UNIT SPECIFICATIONS/CUT SHEETS AND IDENTIFY LOCATION OF INSTALLATION *** For further questions or information please contact the Division of the Fire Marshal main number at 719-385-5978 or Kay Yeager @ 719-385-7356.
FYILabeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.
AttentionNOTE TO FIRE INSPECTOR: Prior to scheduling the Fire Final please contact the Hazardous Materials Inspector to arrange a Hazardous Materials Inspection prior to final signature being provided.
AttentionEquipment, machinery, and required detection and alarm systems associated with the use, storage, or handling of hazardous materials shall be listed or approved. This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com

printer friendly version Printer friendly version