RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

ADVANCED AUTO PARTS
00725 CHEYENNE MEADOWS RD

Review DateStatusComment(s)
2/20/2013 FYIRESUBMITTED: The plans have been re-submitted, and the disapproved issues have been addressed as follows: APPROVED **PLEASE NOTE** ALL COMMENTS FOUND ON PREVIOUS PLAN REVIEWS REMAIN ENFORCEABLE UNLESS OTHERWISE NOTED IN THIS REVIEW. 1) APPROVED-Items were submitted. * provide tank specifications * provide site layout map large enough to review/read * Provide permit application completed on the correct form (Plan reviewer walked him through website location) * provide Listings; DW or SW, secondary containment, installation information. * resubmit permit application and plans with the above information.
FYITanks storing Class I, II and IIIA liquids inside buildings shall be equipped with a device or other means to prevent overflow into the building including, but not limited to: a float valve; a preset meter on the fill line; a valve actuated by the weight of the tank's contents; a low-head pump that is incapable of producing overflow; or a liquid-tight overflow pipe at least one pipe size larger than the fill pipe and discharging by gravity back to the outside source of liquid or to an approved location. This tank shall store class IIIB liquid (used oil).
2/6/2013 Disapproved2/6/13 Deficient submittal. Incorrect permit application form was submitted. (generator) No information regarding tank, specifications or installation was provided site map (provided and too small to review) Plan reviewer contacted Gary League GC, to discuss disapproval due to deficient submittal. * provide tank specifications * provide site layout map large enough to review/read * Provide permit application completed on the correct form (Plan reviewer walked him through website location) * provide Listings; DW or SW, secondary containment, installation information. * resubmit permit application and plans with the above information.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com