| Review Date | Status | Comment(s) |
| 11/16/2012 |
Phone Call | Received a phone call from Greg at Classic Homes requesting a denial so they could upload the corrected items from zoning's review and then hopefully get approvals. |
| 11/6/2012 |
FYI | *****(STANDARD COMMENT 1) This project is: Private Residence, 5580 Wilson Rd: single family home
Date of Plans: 10.30.12
You can access our web site for the latest fire department plan review comments:
1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS
2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
|
| FYI | (STANDARD COMMENT) REVIEWS:
Colorado Springs Fire Department plan reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents.
The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
(105.4.4) |
| Disapproved | (STANDARD COMMENT) NO RESIDENTIAL PLAN REVIEW CHECKLIST
Please copy, fill out, and submit the "Residential Plan Review Submittal Form" for all hillside home plans submitted to CSFD. Without this requested information we can not do a complete review of your submittals. |
| Disapproved | (STANDARD COMMENT) HYDRANT LOCATIONS NOT PROVIDED OR NOTED
Your plans do not indicate where the existing hydrants are located. |
| Disapproved | (DISAPPROVED) FIRE FLOW REPORT NOT PROVIDED
Provide confirmation on the fire flow results from Colorado Springs Utilities. A copy of their report for this area is required to be provided with your plan submittals.
When multiple fire flows are provided from CSU, please indicate all flows on your submitted plans.
NOTE - To request a fire flow report, please go to: http://www.csu.org/business/businesswithus/documents/item10501.pdf |
| Disapproved | (STANDARD COMMENT) ZONING APPROVAL
The City Zoning approved site plan for this site was NOT submitted with this submittal. An approved site plan must be attached to each set of building plans. |
| FYI | (STANDARD COMMENT) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS.
It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting. |
| FYI | (STANDARD COMMENT) CORRECTIONS
All corrections and comments are to be submitted back to CSFD in writing, or provid submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax or verbally. |