NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

WOODMEN RIDGE APARTMENTS CLUBHOUSE RECREATION BLDG
05520 WOODMEN RIDGE VW

Review DateStatusComment(s)
4/18/2013 FYI*****(STANDARD COMMENT 1) This project is: Woodmen Ridge Apartments, 5592 Woodmen Ridge Vw: new apartment building Date of Plans: 4.4.13 This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****(STANDARD COMMENT 6) The fire sprinkler system is being installed by: RANGER FIRE CSFD does not allow any combustibles into a building until a sprinkler system has passed it's final acceptance test performed by CSFD Inspector's.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, CFPS Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 / (F) 719-385-7330 dwithee@springsgov.com
Disapproved*****(STANDARD COMMENT 42) DISAPPROVED COMMENTS: The following information and/or corrections are needed prior to conducting a full plan review. PLEASE RESPOND IN WRITING ON LETTERHEAD TO EACH OF THE FOLLOWING COMMENTS: 1. Water Supply was not reduced by 10% as required in the hydraulic calculations - the water supply curve shall be accompanied by a secondary parallel curve under which the demand point must fall! 2. Building Type I - you have 3 remote areas, and you suddenly change the water supply infomration on the 3rd calculations. If you are calculated all the buildings back to Hydrant A, why not use the same hydraulic information for that node (3000 gpm @ 20 psi residual, 75 psi static) for all the calculations? If you are going to calc to the same point for all buildings, use the same water supply information for all the calculations. If you are going to use different water supplies, then you must use the worst case water supply information for each water supply, then calc to the point of conection to that water main using the longest fire line for the building type, etc. Also review the disapproved plans for additional written comments prior to submittal of new plans.
Disapproved(STANDARD COMMENT 44) CONTRACTOR LICENSING: The plans can not be reviewed at this time. Our records indicate the license for this Fire Suppression Contractor is not current. Please contact the Contractor Licensing Office of the Regional Building Department to correct this problem. ---xxx--NICET Expired November 2012
Attention(STANDARD COMMENT 45) THE DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.


 