NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING. System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.
ITT INDUSTRIES - B 05009 CENTENNIAL BL
| Review Date | Status | Comment(s) |
| 10/31/2012 |
FYI | ***** 5-DEVICE LETTER:
Date Submitted: 10/31/12
Date of Work: 11/01/12
Contractor: CSSC
Scope : Add 1 horn/strobe and 2 strobes
Current Draw:2.330AH
Battery Size: 12V/7.5AH
Location of work: Elexis tenant space
Bldg permit #:I49771
|
| 10/17/2012 |
Disapproved | ***** 5-DEVICE LETTER DISAPPROVALS:
---XX--This work requires a building permit
|
|