NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING. System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.
BROADMOOR TAVERN 00001 LAKE AV
| Review Date | Status | Comment(s) |
| 2/6/2013 |
FYI | ***** 5-DEVICE LETTER:
Date Submitted: 02/06/13
Date of Work: 02/06/13
Contractor: SGFP
Scope : Adding duct detectors
Current Draw: 78.123 AH
Battery Size: 12V/110AH
Location of work: Tavern
Bldg permit #:I48765
|
| 2/4/2013 |
Disapproved | ***** 5-DEVICE LETTER DISAPPROVALS:
--XX---The information you have provided is not complete, please provide the following:
RBD Permit #
Drawing
|
|