RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

THE HERB SHOP - UNIT 110
03020 COLORADO AV

Review DateStatusComment(s)
11/5/2012 FYIRESUBMITTED: The plans have been re-submitted, and the disapproved issues have been addressed as follows: **PLEASE NOTE** ALL COMMENTS FOUND ON PREVIOUS PLAN REVIEWS REMAIN ENFORCEABLE UNLESS OTHERWISE NOTED IN THIS REVIEW. 1) FOR CO2 GENERATOR: Mechanical EXHAUST VENTILATION is the redesign and installation to mitigate the potential for CO2 gas release. PPRBD mechanical dept. re reviewed and released for permit the ventilation system see plan sheet M1.0. Exhaust fan 2 provided CO2 sensor contorl with adjustable setting set @ 1500 ppm . locate @ 24" AFF and interlockd with EF-2 WITH RTU-2 FAN. (CO2 sensor interlocked with mechanical exhaust ventilation.) 2) SEE ELECTRONIC DOCUMENTS FOR CHEM INVENTORY, CO2 GENERATOR SPECS, AND CO2 DECLARATION. 3) UL listing: not provided in brochure cut sheets. Plan reviewer contacted website and obtained mfgr website information indicating that products are UL/ETL listed components SEE ELECTRONIC DOCUMENTS.
10/18/2012 FYI*****(STANDARD COMMENT) This project is: The Herb Shop, 3020 W Colorado Av, Suite 110: remodel, partial change of occupancy Date of Plans: 9.13.12 CARBON DIOXIDE GENERATOR FUELED BY PORTABLE PROPANE CYLINDER You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
DisapprovedCARBON DIOXIDE GENERATOR PLEASE RESUBMIT PLANS WITH THE MANUFACTURERS SPECIFICATIONS, INSTALLATION MANUALS, INSTRUCTIONS AND "LISTINGS" FOR THIS DEVICE. PROVIDE MANUFACTURER'S CUT SHEETS DEMONSTRATE THAT THIS DEVICE IS LISTED FOR PROPANE FUEL ALSO. ** SAFETY INTERLOCKS TO SHUT DOWN AT A SET CONCENTRATION?
DisapprovedCARBON DIOXIDE GAS DETECTION AND ALARM SYSTEM AND/OR VENTILATION Facilities shall declare the storage and use of small Insulated Carbon Dioxide Systems used in Beverage Dispensing or similar operations. *** This facility proposes to install a CO2 GENERATOR FUELED BY PROPANE, therefore, it is required to comply with the 2009 IFC/IMC ONE OF THE FOLLOWING OPTIONS: 1) ventilation requirements for mechanical EXHAUST or 2) ventilation for NATURAL ventilation or 3) provide an approved CO2 gas detection and alarm system in accordance with the following: a) A Listed (by an approved testing laboratory or organization) gas detection and alarm system that is capable of detecting and notifying the building occupants of a gas release that creates carbon dioxide vapors in excess of its Permissible Exposure Level (PEL) at 5,000 parts per million. b) The gas detection and alarm system shall initiate an audible alarm within the room or area in which the system is installed. Activation shall sound a local alarm to notify persons responsible for system operation of a hazardous condition in the area where installed. c) The automatic gas detection and alarm system shall be installed in accordance with the manufacturer's requirements and recommendations. Documentation shall be provided at the time of inspection. Note: Carbon dioxide is 1.5 times heavier than air. Vapors accumulate in low elevations, and in non-ventilated rooms not necessarily limited to the location of the container. The detector(s) should be located in areas where carbon dioxide from a leak will concentrate. Most manufacturers' gas detection sensors are recommended to be installed 12 inches to 24 inches above floor level.
AttentionCHEMICAL INVENTORY SEE ELECTRONIC DOCUMENTS All materials are below the MAQs and the CSFD annual operational permit thresholds. No permit required Due to the CO2 generator device and propane, a Hazardous Materials Construction Inspection is required prior to the Certificate of Occupancy. Please contact the CSFD Div of the Fire Marshal @ 719-385-5978 to schedule the hazradous materials inspection. *** CARBON DIOXIDE GENERATOR FUELED BY PROPANE ONE PROPANE CYLINDER @ 4.1 gal w.c. ?
AttentionVENTILATION Due to the presence of a CO2 generator ventilation per the IMC AND IFC 2009, may be required or monitoring alarm-detection system per the Administrative Ruling see ADDITIONAL COMMENTS FOR CO2 REQUREMENTS *** PPRBD has reviewed and released for permit mechanical plan set. However, the HAZMAT reviewer will need to speak with Mechanical to determine if Mechanical Dept was aware of the presence of Carbon Dioxide.
FYIHAZARDOUS MATERIALS STORAGE CABINETS Where storage cabinets are used to increase maximum allowable quantity per control area or to comply with chapter 27, such cabinets shall be in accordance with IFC 2009, as amended, Sections 2703.8.7.1 and 2703.8.7.2. The interior of cabinets shall be treated, coated or constructed of materials that are nonreactive with the hazardous material stored. Such treatment, coating or construction shall include the entire interior of the cabinet. Cabinets shall either be listed in accordance with UL 1275 as suitable for the intended storage or constructed in accordance with the following: 1. Cabinets shall be of steel having a thickness of not less than 0.0478 inch (1.2 mm) (No. 18 gage). The cabinet, including the door, shall be double walled with a 11/2-inch (38 mm) airspace between the walls. Joints shall be riveted or welded and shall be tight fitting. Doors shall be well fitted, self-closing and equipped with a self-latching device. 2. The bottoms of cabinets utilized for the storage of liquids shall be liquid tight to a minimum height of 2 inches (51 mm). Electrical equipment and devices within cabinets used for the storage of hazardous gases or liquids shall be in accordance with NFPA 70. Cabinets shall be clearly identified in an approved manner with red letters on a contrasting background to read: HAZARDOUS-KEEP FIRE AWAY. ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ CONTAINMENT PALLETS For spill control and secondary containment for storage in accordance with the exception in Section 2704.2, containment pallets shall comply with all of the following: 1 A liquid-tight sump accessible for visual inspection shall be provided. 2. The sump shall be designed to contain not less than 66 gallons (250 L). 3. Exposed surfaces shall be compatible with material stored.
FYILABELING Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with the IFC 2009, as amended, Section 2703.5. Labeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing com-pressed gases shall be conspicuously labeled: COMPRESSED GAS.
FYIMSDS Material Safety Data Sheets (MSDS) for all hazardous materials shall be either readily available on the premises as a paper copy, or where approved, shall be permitted to be readily retrievable by electronic access. Approved electronic access shall be as follows: 1. Media shall be USB Flash Drive. 2. Format shall be Microsoft Word 2000 or newer docu-ment, PDF, or other approved format. Where a Knox Box is located at a facility, one USB de-vice shall be stored in the Knox Box and one device shall be located in an approved location(s). All devices and content shall be maintained.
FYIShelving shall be of substantial construction, and shall be braced and anchored in accor-dance with the seismic design requirements of the Interna-tional Building Code for the seismic zone in which the material is located. Shelving shall be treated, coated or constructed of materials that are compatible with the hazardous materials stored. Shelves shall be provided with a lip or guard when used for the storage of individual containers. Exceptions: 1. Storage in hazardous material storage cabinets or laboratory furniture specifically designed for such use. 2. Storage of hazardous materials in amounts not requiring a permit in accordance with Section 2701.5. Shelf storage of hazardous materials shall be main-tained in an orderly manner.
FYIIncompatible materials in storage and storage of materials that are incompatible with materials in use shall be separated when the stored materials are in containers having a capacity of more than 5 pounds (2 kg) or 0.5 gallon (2 L). Separation shall be accomplished by: 1. Segregating incompatible materials in storage by a distance of not less than 20 feet (6096 mm). 2. Isolating incompatible materials in storage by a noncombustible partition extending not less than 18 inches (457 mm) above and to the sides of the stored material. 3. Storing liquid and solid materials in hazardous ma-terial storage cabinets. 4. Storing compressed gases in gas cabinets or exhausted enclosures in accordance with Sections Materials that are incompatible shall not be stored within the same cabinet or exhausted enclosure. ***ATTENTION: MSDS for these materials indicate incompatibilities with certain materials/chemicals. Pay close attention to the Oxidizers --- separate from other materials. *** Recommend approved storage cabinets and secondary containment pallets for the storage of on site materials.
FYIPersons responsible for the operation of areas in which hazardous materials are stored, dispensed, handled or used shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of a fire, leak or spill. Responsible persons shall be designated and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses and identification of the locations where hazardous materials are located, and shall have access to Material Safety Data Sheets and be knowledgeable in the site emergency response procedures.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com

printer friendly version Printer friendly version