| Review Date | Status | Comment(s) |
| 1/9/2013 |
FYI | *****(STANDARD COMMENT 1) This project is: Indigo Ranch North at Stetson Ridge Filing No 9. Located north and east of Dublin and Peterson.
Date of Plans:
You can access our web site for the latest fire department plan review comments:
1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS
2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project. |
| FYI | *****(STANDARD COMMENT) FIRE FLOW/HYDRANT REQUIREMENTS MET:
On this site the theoretical water flows are -2600--- gpm, and the numbers of hydrant(s) are --ADEQUATE-.
This site, based upon the provided theoretical modeled fire flows, appear to meet the minimum flow requirements and/or the number of hydrant(s) for this structure. |
| Attention | (STANDARD COMMENT) READY FOR SIGNATURES:
The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
|
| FYI | (STANDARD COMMENT 6) This is a PUBLIC water system. |
| 12/10/2012 |
FYI | *****(STANDARD COMMENT 1) This project is: Indigo Ranch North at Stetson Ridge Filing No 9. Located north and east of Dublin and Peterson.
Date of Plans: 11.1.12
You can access our web site for the latest fire department plan review comments:
1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS
2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project. |
| Attention | *****(STANDARD COMMENT 2) BUILDING DATA:
Size of Bldg. --6100--- sq ft MAXIMUM
Construction Type ----V-B--
Required GPM: --2000--- gpm
# of hydrant(s) required: --2---
Max AVG spacing between hydrants: --450--- ft
Max hose lay: ----225- ft
|
| FYI | *****(STANDARD COMMENT) SCOPE OF WORK:
--XXX---WATER PLAN |
| Disapproved | DISAPPROVED
The following information and/or corrections are needed prior to completing a full plan review:
1. Please note that the available fire flow is what limits building size, along with other restrictions by other departments (lot coverage, height, etc), not the CSFD - we are only enforcing the adopted codes which require a specific fire flow to be provided based on the size of a building. If the fire flow is not available, the construction type need to be adjusted to a less combustible type or the size of the building needs to be reduced or broken up by fire walls.
Also:
1) Review all redline comments and address each one.
2) Return ALL red lined plan sets for each re-review. |
| Disapproved | (DISAPPROVED) FIRE FLOW REPORT
Provide confirmation on the fire flow results from Colorado Springs Utilities. A copy of their report for this area is required to be provided with your plan submittals.
When multiple fire flows are provided from CSU, please indicate all flows on your submitted plans.
NOTE - To request a fire flow report, please go to: http://www.csu.org/business/businesswithus/documents/item10501.pdf
|
| FYI | (STANDARD COMMENT) REVIEWS:
Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents.
The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
(105.4.4) |