NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

PINERY AT THE HILL
00775 BIJOU ST

Review DateStatusComment(s)
1/15/2013 FYIPinery on the Hill, 775 W Bijou: Interior remodel and addition - upgrade to finish SYSTEMS: fire sprinkler for occupancy/use/area; fire alarm for occupancy CN:Code: 09 IBC - 09 IFC - 11 PPRBC /Class:A2, A3, B, S1 / Const: V-A /Stories: 2/Size:19,419 /OL: 639 FH:Required Flow: 1500 gpm /# Hydrants 1/On site flow: DV:Proposing a complete renovation inside and out with a partial second floor addition of 5670sf as well as various site modifications. Non use variance to allow a retaining wall over 6 feet. Additional Comments: SEE ALSO 2008-0722 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
ApprovedMSDS 407.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be either readily available on the premises as a paper copy, or where approved, shall be permitted to be readi-ly retrievable by electronic access. Approved electronic access shall be as follows: 1. Media shall be USB Flash Drive. 2. Format shall be Microsoft Word 2000 or newer docu-ment, PDF, or other approved format. Where a Knox Box is located at a facility, one USB de-vice shall be stored in the Knox Box and one device shall be located in an approved location(s). All devices and content shall be maintained.
AttentionCHEMICAL INVENTORY SEE ELECTRONIC DOCUMENTS All materials are BELOW The MAQs and the CSFD annual operational permit thresholds. NO ANNUAL HAZARDOUS MATERIALS PERMIT REQUIRED NO HAZMAT CONSTRUCTION INSPECTION REQUIRED
FYICARBON DIOXIDE CO2 DECLARATION = 70 LBS This is below the 100 lb THRESHOLD IDENTIFIED IN THE ADMINISTRATIVE RULING REQUIRING MONITORING-DETECTION OR VENTILATION. CARBON DIOXIDE GAS DETECTION AND ALARM SYSTEM AND/OR VENTILATION Facilities shall declare the storage and use of small Insulated Carbon Dioxide Systems used in Beverage Dispensing or similar operations. .ADMIN RULING 2009 IFC/IMC ONE OF THE FOLLOWING OPTIONS: 1) ventilation requirements for mechanical EXHAUST or 2) ventilation for NATURAL ventilation or 3) provide an approved CO2 gas detection and alarm system in accordance with the following: NO FURTHER ACTION.
FYIHAZARDOUS MATERIALS STORAGE CABINETS Where storage cabinets are used to increase maximum allowable quantity per control area or to comply with chapter 27, such cabinets shall be in accordance with IFC 2009, as amended, Sections 2703.8.7.1 and 2703.8.7.2. The interior of cabinets shall be treated, coated or constructed of materials that are nonreactive with the hazardous material stored. Such treatment, coating or construction shall include the entire interior of the cabinet. Cabinets shall either be listed in accordance with UL 1275 as suitable for the intended storage or constructed in accordance with the following: 1. Cabinets shall be of steel having a thickness of not less than 0.0478 inch (1.2 mm) (No. 18 gage). The cabinet, including the door, shall be double walled with a 11/2-inch (38 mm) airspace between the walls. Joints shall be riveted or welded and shall be tight fitting. Doors shall be well fitted, self-closing and equipped with a self-latching device. 2. The bottoms of cabinets utilized for the storage of liquids shall be liquid tight to a minimum height of 2 inches (51 mm). Electrical equipment and devices within cabinets used for the storage of hazardous gases or liquids shall be in accordance with NFPA 70. Cabinets shall be clearly identified in an approved manner with red letters on a contrasting background to read: HAZARDOUS-KEEP FIRE AWAY. ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ CONTAINMENT PALLETS For spill control and secondary containment for storage in accordance with the exception in Section 2704.2, containment pallets shall comply with all of the following: 1 A liquid-tight sump accessible for visual inspection shall be provided. 2. The sump shall be designed to contain not less than 66 gallons (250 L). 3. Exposed surfaces shall be compatible with material stored.
FYILABELING Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with the IFC 2009, as amended, Section 2703.5. Labeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing com-pressed gases shall be conspicuously labeled: COMPRESSED GAS.
FYIMSDS Material Safety Data Sheets (MSDS) for all hazardous materials shall be either readily available on the premises as a paper copy, or where approved, shall be permitted to be readily retrievable by electronic access. Approved electronic access shall be as follows: 1. Media shall be USB Flash Drive. 2. Format shall be Microsoft Word 2000 or newer docu-ment, PDF, or other approved format. Where a Knox Box is located at a facility, one USB de-vice shall be stored in the Knox Box and one device shall be located in an approved location(s). All devices and content shall be maintained.
FYIShelving shall be of substantial construction, and shall be braced and anchored in accor-dance with the seismic design requirements of the Interna-tional Building Code for the seismic zone in which the material is located. Shelving shall be treated, coated or constructed of materials that are compatible with the hazardous materials stored. Shelves shall be provided with a lip or guard when used for the storage of individual containers. Exceptions: 1. Storage in hazardous material storage cabinets or laboratory furniture specifically designed for such use. 2. Storage of hazardous materials in amounts not requiring a permit in accordance with Section 2701.5. Shelf storage of hazardous materials shall be main-tained in an orderly manner.
FYIIncompatible materials in storage and storage of materials that are incompatible with materials in use shall be separated when the stored materials are in containers having a capacity of more than 5 pounds (2 kg) or 0.5 gallon (2 L). Separation shall be accomplished by: 1. Segregating incompatible materials in storage by a distance of not less than 20 feet (6096 mm). 2. Isolating incompatible materials in storage by a noncombustible partition extending not less than 18 inches (457 mm) above and to the sides of the stored material. 3. Storing liquid and solid materials in hazardous ma-terial storage cabinets. 4. Storing compressed gases in gas cabinets or exhausted enclosures in accordance with Sections Materials that are incompatible shall not be stored within the same cabinet or exhausted enclosure. ***ATTENTION: MSDS for these materials indicate incompatibilities with certain materials/chemicals. Pay close attention to the Oxidizers --- separate from other materials. *** Recommend approved storage cabinets and secondary containment pallets for the storage of on site materials.
FYIPersons responsible for the operation of areas in which hazardous materials are stored, dispensed, handled or used shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of a fire, leak or spill. Responsible persons shall be designated and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses and identification of the locations where hazardous materials are located, and shall have access to Material Safety Data Sheets and be knowledgeable in the site emergency response procedures.


 