NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

 
   

Review DateStatusComment(s)
11/16/2012 Approvedplans are signed
10/26/2012 Attention(STANDARD COMMENT) READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
10/2/2012 FYI*****(STANDARD COMMENT 1) This project is: Woodmen Ridge Apartments Filing 1. Located southwest of Powers and Woodmen, north of the Villas Sport. Date of Plans: 8.16.12 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
Attention*****(STANDARD COMMENT 2) BUILDING DATA: Size of Bldg. --29,350--- sq ft (BLDGS 1,3-4, 10-13) Construction Type ---V-B--- Fire Sprinklers Y-XXX---- N----- Fire Walls Y ----- N --XXX-- Required GPM: -2500---- gpm # of hydrant(s) required: -3---- Max AVG spacing between hydrants: --450--- ft Max hose lay: --225-- ft Size of Bldg. --26,984--- sq ft (BLDGS 2, 5-9) Construction Type ---V-B--- Fire Sprinklers Y-XXX---- N----- Fire Walls Y ----- N --XXX-- Required GPM: -2250---- gpm # of hydrant(s) required: -3---- Max AVG spacing between hydrants: --450--- ft Max hose lay: --225-- ft Size of Bldg. -7061--- sq ft CLUBHOUSE Construction Type ---V-B--- Fire Sprinklers Y----- N--XXX--- Required GPM: -2250---- gpm # of hydrant(s) required: -3---- Max AVG spacing between hydrants: --450--- ft Max hose lay: --225-- ft
DisapprovedDISAPPROVED The following information and/or corrections are needed prior to completing a full plan review: 1. Fire flows noted on the plans for each hydrant(in the table and in the hydrant labels) do not match the CSU report. Please clarify. Also: 1) Review all redline comments and address each one. 2) Return ALL red lined plan sets for each re-review.
Disapproved(DISAPPROVED) FIRE DEPARTMENT CONNECTION Your plans do not indicate, or have placed the Fire Department Connection (FDC) to the sprinkler systems in an unacceptable location.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)


 