| Review Date | Status | Comment(s) |
| 10/2/2012 |
FYI | El Paso County Sheriffs Office 27 E Vermijo Ave Remodel
SYSTEMS: Alarms,halon in basement; standpipes
CN:Code: 09 EBC - 09 IFC - 11 PPRBC /Class: B/A-3 / Const: I-B /Stories: 5 + BASEMENT /Size: 65080 /OL: 1232
FH:Required Flow: gpm /# Hydrants /On site flow:
Install EM Generator and associated subbase storage tank; 608 gallon diesel; DW UL LISTED
ATTENTION: See our web site for our latest plan review comments for your job at:
www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work.
|
| FYI | TANK
Tank Description: ONE DOUBLE WALL, UL 142 LISTED TANK, 608 Gallons
Contents: DIESEL
Type of containment: DOUBLE WALL steel tank
SPEC SHEET DECLARES COMPLIANCE WITH NFPA 30, 37 & 110
EXTERIOR LOCATION
*** Class II combusitble liquid |
| FYI | GENERATOR: is a CUMMINS MODEL fueled by diesel.
LOCATION: NORTH SIDE OF BUILDING WITHIN FENCED AREA
|
| Attention | CLEARANCES:
The tank must be located a minimum of 15 feet from the a property line that is or can be built upon, including the opposite side of a public way and 5 feet from the exterior of a building.
Per NFPA 110, Chapter 7, a minimum of 3 foot clearance free of any obstructions shall be provided around the generator.
Per the plans, these distances are met. |
| FYI | Provide for vehicle protection of tank in one of the following forms:
1) Provide Bollards- concrete filled Steel, Schedule 40, 4 inches outer diameter buried a minimum of 3 ft underground, extending a minimum of 3 ft above grade spaced at a minimum of 4 ft on center. Shall be anchored in a concrete foundation 15" diameter x 3 feet deep. Bollards shall be spaced away from the tank a distance equal or greater than their height above grade. Bollards shall not be more than 4 feet on-center.
2) Provide Concrete Road Barriers (Jersey Barriers) as approved by the Fire Code Inspector (4' apart, 4' from tanks. See 2003 IFC Section 312.3 for height and impact resistivity requirements).
3) CMU Block Screen Walls may be an acceptable method of vehicular protection. When CMU screen walls are considered for vehicular protection, they shall be proven to meet the height/impact resistivity requirements of 2003 IFC Section 312.
*Standard traffic curbs are not recognized by the Fire Code as an acceptable method of vehicular protection.
**Bollards are noted on plan sheet |
| FYI | Application for permit to the Colorado Div. of Oil and Public Safety was provided.
|
| FYI | BATTERIES
Declared amount of electrolyte: = 8 gallons (2 batteries)
This quantity of electrolyte solution DOES NOT exceed the permit quantity (100 gal) as defined in Sections 105 and 608 of the 2009 IFC as amended.
The general provisions required by 2009 IFC Chapters 27 and 31 (Sections 2701, 2703 and 3101) in addition to the comments included in this review with respect to secondary containment, spill control and the neutralization of this material upon release. |
| I | Please contact the Div of the Fire Marshal @ 719 385-5978 to arrange for a hazmat tank installation permit inspection. Fire Inspection approval is required prior to filling of a tank. |
| Attention | Tank Location: This tank is located EXTERIOR, at the north side of the building and a fence surrounding the tank/generator. |
| Attention | Tank venting, piping, and valving shall comply with 2009 IFC Chapter 34 as allowed and applicable to the materials and methods chosen.
Emergency shutoff valves (in installed piping runs) shall consist of a 1/4-turn valve approx 5' from the tank, and a 1/4-turn valve approx 5' from the use point. These valves shall be labelled such that they are easily identifiable.
Emergency shutoff valves that are installed as part of a complete turn-key assembly (such as a generator) shall have a clearly identified fuel shut-off.
**LABEL ALL EMERGENCY SHUT OFF VALVES: IDENTIFY PURPOSE OF VALVE, DIRECTION OF TURNOFF. |
| FYI | Individual storage tanks containing Class I, II, or IIIA liquids shall be placarded in accordance with NFPA 704. |
| FYI | IFC 2009, AS AMENDED
EMERGENCY AND STANDBY POWER SYSTEMS
CHAPTER 6
**** Emergency and standby power systems shall be installed in accordance with the ICC Electrical Code, NFPA 110 and NFPA 111. Existing installations shall be maintained in accordance with the original approval.
**** Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200. |
| Attention | IDENTIFY EMERGENCY SHUT OFF/ SHUT DOWN
Clearly identify and label shutoff and shutdown at generator or alarm panels, as provided for this system, and as applicable. |
| FYI | ALL PIPING from tank shall be labeled in accordance with ANSI A13.1 requirements. |
| FYI | Signs shall be posted prohibiting open flames and smoking. |
| FYI | {AST} Vent pipes shall be extended to a safe outdoor location and equipped iwth approved flame arrestors. |
| FYI | Tank vents shall not be manifolded. |
| FYI | A minimum 20B rated fire extinguisher shall be located no closer than 10 feet to the storage tank and no farther than 50 feet. A single fire extinguisher may provide coverage for more than one tank but the minimum and maximum travel distances shall be achieved.
** provide a fire extinguisher compliant with above. |
| FYI | The storage, use and/or dispensing of hazardous liquids shall be in accordance with all applicable provisions of the 2009 International Fire Code including (but not limited to) Chapters 22, 27, and 34 and the applicable provisions of NFPA Standards 30, 37, and 110. |