MORNINGSTAR MOUNTAIN SHADOWS
05355 CENTENNIAL BL

Review DateStatusComment(s)
10/3/2012 ApprovedRevised plans brought in for signature for a REMOTE FDC - however, the location will not change, it's pipe routing will go from above ground to underground.
9/14/2012 ApprovedPlans approved and signed.
ApprovedCSU flow reports provided. Node A: 2300gpm at 76psi Node B: 2800gpm at 79psi Node C: 2700gpm at 73psi. All node information provided on plans.
6/5/2012 FYI*****(STANDARD COMMENT 1) This project is: Morningstar Mountain Shadows 5355 Centennial Blvd. New assisted living and memory care building. Date of Plans: 6.1.12 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
Disapproved(DISAPPROVED) FIRE FLOW REPORT Provide confirmation on the fire flow results from Colorado Springs Utilities. A copy of their report for this area is required to be provided with your plan submittals. When multiple fire flows are provided from CSU, please indicate all flows on your submitted plans. NOTE - To request a fire flow report, please go to: http://www.csu.org/business/businesswithus/documents/item10501.pdf
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)


 