NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

NOODLES AND COMPANY STORE 159
02455 MONTEBELLO SQUARE DR

Review DateStatusComment(s)
11/19/2012 ApprovedContractor sent a copy of the flow test results that were submitted with the plans. They are less than 5 years old and will be accepted for sign-off of the fire hydrant portion of this project. A copy will be scanned.
8/27/2012 ApprovedRevised plans (8/16/12 on Sheet C1.1) to show modified fire line location as well as modified elevations. No pipe size changes. One additional bend. Client spoke with DEM previously. Plans acceptable.
5/17/2012 FYI*****(STANDARD COMMENT 1) This project is: Noodles and Company, 2455 Montebello Square Drive: new restaurant - CORE/SHELL ONLY Date of Plans: 5.17.12 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
Attention*****(STANDARD COMMENT 2) BUILDING DATA: Size of Bldg. ---2800-- sq ft Construction Type ---V-B--- Fire Sprinklers Y--XXX--- N----- Fire Walls Y ----- N --XXX--- Required GPM: ---1500-- gpm # of hydrant(s) required: --1-- Max AVG spacing between hydrants: ---500-- ft Max hose lay: ---250-- ft
FYI*****(STANDARD COMMENT) SCOPE OF WORK: -----MAIN EXTENSION -----UTILITY SERVICE PLAN -----DOMESTIC ONLY - NO FIRE INSPECTION REQUIRED -----FIRE/DOMESTIC - ---XXX--WATER PLAN
FYI*****(STANDARD COMMENT) FIRE FLOW/HYDRANT REQUIREMENTS MET: On this site the theoretical water flows are --2600-- gpm, and the numbers of hydrant(s) are ---1-. This site, based upon the provided theoretical modeled fire flows, appear to meet the minimum flow requirements and/or the number of hydrant(s) for this structure.
FYI(STANDARD COMMENT 8) GENERAL INSPECTIONS/PLANS & SCHEDULING Minimum notice of one week is required for all inspections. PLEASE plan ahead - call your inspections in with ample time to allow adequate scheduling. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( For Example: 2005-1234- HS-2) The CSFD APPROVED sets of plans SHALL be on site for all inspections.
FYI(STANDARD COMMENT 11) JAH - SCHEDULING INSPECTIONS: Your assigned Inspector is Jeff Hanenberg. Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
4/26/2012 FYI*****(STANDARD COMMENT 1) This project is: Restaurant, 2455 Montebello Square Drive. Date of Plans: 4.13.12 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYI*****(13) FIRE DEPARTMENT CONNECTION: FDCs shall be located in a CSFD approved location. The FDC shall be located on the front entrance and/or addressed side of the structure, fully visible and recognizable from the street. FDCs shall be location such that it is not blocked by any means or located behind parked vehicles and such that fire apparatus and hoses connected to the FDC do not obstruct access to building for other fire apparatus. FDCsshall be located within 40-ft of an approved fire department access road. There shall be a fire hydrant capable of supplying the fire flow requirements for the sprinkler system within 100 feet of the FDC. FDCs shall be mounted not less than 18-inches and not more than 4-foot above the level of the adjacent grade or access level. (NFPA 14:6.4.6) NOTE: FDC IS PERMITTED TO EXCEED 100-FT TO A FIRE HYDRANT FOR THIS PROJECT. ADDING A HYDRANT, PLACES ONE WITHIN 120-FEET OF AN EXISTING FIRE HYDRANT, ADDING SIGNIFICANT COST TO A SMALL STRUCTURE, THAT IS NOT REQUIRED TO BE FIRE SPRINKLERED BASED ON SQUARE FOOTAGE (OCCUPANT LOAD IS NOT YET KNOWN)
DisapprovedDISAPPROVED The following information and/or corrections are needed prior to completing a full plan review: 1. fill in the blanks on the node and fire flow in the fire department signature block. 2. provide building data - see additional comment. Also: 1) Review all redline comments and address each one. 2) Return ALL red lined plan sets for each re-review.
Disapproved(DISAPPROVED) BUILDING DATA The "BUILDING DATA" information must be provided for each building, and should be indicated inside the footprint layout of the building, or just next to the footprint, and on each of your plan sheets that are to be signed by CSFD: Please refer to our Water Supplies Information packet for the required information/template.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)


 