NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

MYRON STRATTON ADMINISTRATION BLDG
00555 GOLD PASS HT

Review DateStatusComment(s)
1/16/2013 Approved
FYI*****(STANDARD COMMENT) REVISION: Revision Sequence: 1 Scope of Revision: NEW ARRANGEMENT FOR FIRE LINE SERVICE DUE TO EXISTING CONDITIONS NOT BEING WHAT THEY WERE THOUGHT TO BE Date of Revision:
Attention(STANDARD COMMENT) READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
3/21/2012 ApprovedPlans submitted, signed, and copy for file (includes garage/storage shed)
3/8/2012 FYI*****(STANDARD COMMENT 1) This project is:Myron Stratton Home, Administrative Building. 555 Gold Pass Heights Date of Plans:2.21.12 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYI*****(STANDARD COMMENT) SCOPE OF WORK: -----MAIN EXTENSION -----UTILITY SERVICE PLAN -----DOMESTIC ONLY - NO FIRE INSPECTION REQUIRED -----FIRE/DOMESTIC - ---XXX--WATER PLAN
Attention*****(STANDARD COMMENT 2) BUILDING DATA: Size of Bldg. --50,202--- sq ft Construction Type --II-B---- Fire Sprinklers Y-XXX--- N----- Fire Walls Y ----- N ---XXX-- Required GPM: ---2500-- gpm # of hydrant(s) required: ---3-- Max AVG spacing between hydrants: --450--- ft Max hose lay: ---225-- ft
FYI*****(STANDARD COMMENT) FIRE FLOW/HYDRANT REQUIREMENTS MET: On this site the theoretical water flows are -3000--- gpm (SIMULTANEOUS FLOWS), and the numbers of hydrant(s) are -3---. This site, based upon the provided theoretical modeled fire flows, appear to meet the minimum flow requirements and/or the number of hydrant(s) for this structure.
Attention(STANDARD COMMENT) READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
FYI(STANDARD COMMENT 3) HYDRANT PAINTING REQUIREMENT: Fire hydrants shall be painted in compliance with 2009 IFC Table C105.2. By using this scheme, emergency response crews are provided a quick way to decipher how much water is available from a specific hydrant. The gpm of the hydrant are determined by an actual water flow test, and it is imperative the testing and color coding is accurate.
FYI(STANDARD COMMENT) FIRE FLOW TESTING: PRIOR TO THE TIME OF FIRE FINAL INSPECTIONS, it is be the responsibility of the owners, GC, or site manager to have all new and existing fire hydrants, and/or private water systems flow tested. Previous tests dated within the past 5 years will be accepted. ALL HYDRANT TESTS SHALL BE CONDUCTED BEFORE ON-SITE CONSTRUCTION IS STARTED!!! PUBLIC/CITY OWNED HYDRANTS: Contact SEAN HIGBEE, CSU at 668-4595 or via email at shigbee@csu.org to schedule an ACTUAL flow test. Be sure to provide them with a CSFD plan review number to include with their flow reports. CSFD need not be present when City Utilities flow tests hydrants as we will accept their reports. PLEASE ALLOW 1-2 WEEKS NOTICE PRIVATE HYDRANTS: Contact your assigned inspector below to schedule a flow test of PRIVATE OWNED hydrants. A contractor capable of performing the test will be required as CSFD Inspectors WITNESS only. CSFD will not accept flow tests we have not witnessed.
FYI(STANDARD COMMENT 5) This is a PRIVATE system
FYI*****(13) FIRE DEPARTMENT CONNECTION: FDCs shall be located in a CSFD approved location. The FDC shall be located on the front entrance and/or addressed side of the structure, fully visible and recognizable from the street. FDCs shall be location such that it is not blocked by any means or located behind parked vehicles and such that fire apparatus and hoses connected to the FDC do not obstruct access to building for other fire apparatus. FDCsshall be located within 40-ft of an approved fire department access road. There shall be a fire hydrant capable of supplying the fire flow requirements for the sprinkler system within 100 feet of the FDC. FDCs shall be mounted not less than 18-inches and not more than 4-foot above the level of the adjacent grade or access level. (NFPA 14:6.4.6) NOTE: PREFERRED ALTERNATE LOCATIONS ARE RECOMMENDED, HOWEVER, THE PROPOSED LOCATION IS ACCEPTABLE.
FYI(STANDARD COMMENT 8) GENERAL INSPECTIONS/PLANS & SCHEDULING Minimum notice of one week is required for all inspections. PLEASE plan ahead - call your inspections in with ample time to allow adequate scheduling. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( For Example: 2005-1234- HS-2) The CSFD APPROVED sets of plans SHALL be on site for all inspections.
FYI(STANDARD COMMENT 11) INSPECTOR HANENBERG: Your assigned Inspector is Jeff Hanenberg. You may contact him at 719-385-7359 to schedule all construction related inspection activities.
FYI(STANDARD COMMENT) DISAPPROVED ITEMS ADDRESSED: The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1. Development plan indicates the square footage is to be 36,500 while the water plans shows 50,202. Please clarify the discrepancy. DP REVISED, CORRECT SQUARE FOOTAGE IS 50,202. 2. Fire flow report was not provided. PROVIDED 3. Is this building already fire sprinklered? Or are sprinklers to be retrofitted in? If retrofitting, where is the fire line service? NEW BUILDING, NEW SYSTEM 4. Is the FDC new or existing? NEW
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
2/22/2012 FYI*****(STANDARD COMMENT 1) This project is: Myron Stratton Home, Administrative Building. 555 Gold Pass Heights Date of Plans: 2.21.12 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
DisapprovedDISAPPROVED The following information and/or corrections are needed prior to completing a full plan review: 1. Development plan indicates the square footage is to be 36,500 while the water plans shows 50,202. Please clarify the discrepancy. 2. Fire flow report was not provided. 3. Is this building already fire sprinklered? Or are sprinklers to be retrofitted in? If retrofitting, where is the fire line service? 4. Is the FDC new or existing? 5. Required fire flow is 2500 gpm. Also: 1) Review all redline comments and address each one. 2) Return ALL red lined plan sets for each re-review.
Disapproved(DISAPPROVED) FIRE FLOW REPORT Provide confirmation on the fire flow results from Colorado Springs Utilities. A copy of their report for this area is required to be provided with your plan submittals. When multiple fire flows are provided from CSU, please indicate all flows on your submitted plans. NOTE - To request a fire flow report, please go to: http://www.csu.org/business/businesswithus/documents/item10501.pdf
Disapproved(DISAPPROVED) FIRE FLOW NOT ADEQUATE The fire flow calculations provided do not meet the minimum flow requirements for the structure proposed. Please contact CSU and request a "simultaneous fire flow report." The simultaneous fire flow report is a special report, which takes considerable more time and effort to prepare, and is typically not performed unless specifically requested. CSU will provide this report in cases such as this, and hopefully the fire flows will exceed the code required minimums. If the simultaneous flows do not meet the required amounts, contact the CSFD for additional assistance with your project
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)


 