NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

MEDICAL OFFICE - MAIN
01380 FILLMORE ST

Review DateStatusComment(s)
10/4/2013 FYI(STANDARD COMMENT 10) INSPECTIONS Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities. You will need to schedule an inspection at the time of Framing and a final inspection near completion. Due to the dynamic nature of inspectors schedules, PLEASE call your inspection requests in with ample time to allow scheduling. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( i.e. 2013-1234 - HS-1) The CSFD Approved sets of plans are to be on site for all inspections.
FYI(STANDARD COMMENT) DISAPPROVED ITEMS ADDRESSED: The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1. The plan North hydrant was deleted from the project and the FDC was relocated without regard to the distance from the remaining hydrant. the intersection of Simms/T-Gap is permanently blocked off. To eliminate the relocate of the remaining proposed hydrant, and yet another iteration of this plan and subsequent review, the FDC SHALL BE LOCATED ON THE SOUTHEAST CORNER with the horn/strobe located visible from Fillmore Street (as the building is addressed off Fillmore and responding companies will be responding along Fillmore). this solution allows for signature of plans and building permit to be issued upon insertion into the architectural set.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2009 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
9/17/2013 FYI*****(STANDARD COMMENT 1) This project is: Simms Medical Office, 1380 Simms Road: new medical office building You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
DisapprovedDISAPPROVED The following information and/or corrections are needed prior to completing a full plan review: 1. The fire flow report you provided only shows the model for one of the proposed hydrants, not both of the proposed hydrants. The plan North hydrant is not on the report. 2. Is there an intersection at Simms Rd and Templeton Gap? It is not well shown - if this an intersection meeting City Traffic standards, then the FDC may remain where noted, otherwise the FDC will have to be located on the front entry side of the building. You have continued to ignore my written requirements for the Plan Review Application to be submitted for all reviews. This is your formal notice. Plans submitted without the water plan review application http://www.springsgov.com/units/fire/Packets/Water_Plan_Review_Application.pdf will NOT be reviewed and will be rejected. Also: 1) Review all redline comments and address each one. 2) Return ALL red lined plan sets for each re-review.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2009 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
6/7/2013 FYI*****(STANDARD COMMENT 1) This project is: Simms Medical Office, 3012 Simms Road. Located at the northeast corner of Templeton Gap, Fillmore and Simms. Date of Plans: 5.29.13 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
Attention*****(STANDARD COMMENT 2) BUILDING DATA: Size of Bldg. ---8000-- sq ft Construction Type ---V-B--- Fire Sprinklers YXXX----- N----- Fire Walls Y ----- N --XXX--- Required GPM: ---1500-- gpm # of hydrant(s) required: ---1-- Max AVG spacing between hydrants: --500--- ft Max hose lay: --250--- ft
FYI*****(STANDARD COMMENT) SCOPE OF WORK: --XXX---UTILITY SERVICE PLAN ---XXX--FIRE/DOMESTIC - -XXX----WATER PLAN
DisapprovedDISAPPROVED The following information and/or corrections are needed prior to completing a full plan review: 1. Identify the front entrance and FDC location. 2. Identify the fire line - you are showing service lines, but I don't see where a fire line is called out. 3. Fire flow report was not provided. Also: 1) Review all redline comments and address each one. 2) Return ALL red lined plan sets for each re-review.
Disapproved(DISAPPROVED) FIRE FLOW REPORT Provide confirmation on the fire flow results from Colorado Springs Utilities. A copy of their report for this area is required to be provided with your plan submittals. When multiple fire flows are provided from CSU, please indicate all flows on your submitted plans. NOTE - To request a fire flow report, please go to: https://www.csu.org/Pages/construction-drawing-review.aspx
Disapproved(DISAPPROVED) FIRE DEPARTMENT CONNECTION Your plans do not indicate, or have placed the Fire Department Connection (FDC) to the sprinkler systems in an unacceptable location.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)


 