NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

ADVANCED HEALTH CARE OF CS
00055 PARKSIDE DR

Review DateStatusComment(s)
4/30/2013 FYIAdvanced Healthcare of Colorado Springs, Transitional Rehabilitation Facility, 55 S. Parkside Drive: new skilled nursing facility - STATE LICENSED/PARALLEL REVIEW SYSTEMS: fire sprinkler for area/occupancy/use; fire alarm for occupancy CN:Code: 09 IBC - 09 IFC - 11 PPRBC /Class:I-2 / Const: V-A /Stories: 1/Size: 29,634 /OL: 217 Additional Comments: The previous development plan expired and the applicant had to go through the process all over again. Hence the new file number. HAZMAT PLAN REVIEW FOR DIESEL GENERATOR ***REINSPECTION FEE TO APPLY PER INSPECTOR/HAZMAT SPECIALIST JAY WEIGHTMAN. +$132 ATTENTION: See our web site for our latest fire department plan review comments. From the Pikes Peak Regional Building Department web site (www.pprbd.org), select "RELATED WEB SITES" in the upper right corner. Click on Colorado Springs FIRE PREVENTION. Then select PLAN REVIEW STATUS, click VIEW PLAN REVIEW STATUS. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYIEmergency and standby power systems required by this code or the International Building Code shall be installed in accordance with this code, NFPA 110 and NFPA 111. Existing installations shall be maintained in accordance with the original approval. 604.1.1 Stationary generators. Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200. Fuel oil storage inside buildings shall comply with Sections 603.3.2.1 through 603.3.2.5 or Chapter 34. 603.3.2.4 Installation. Tanks and piping systems shall be installed and separated from other uses in accordance with Section 915 and Chapter 13 both of the International Mechanical Code, as applicable.
AttentionTANK LOCATION EXTERIOR BY LOADING ZONE DW UL 142 ABOVEGROUND STORAGE TANK (INTEGRAL) CUMMINS SEE ELECTRONIC DOCUMENTS CMU ENCLOSURE SURROUNDS GENERATOR (SECURITY AND VEHICLE PROTECTION) **** LABEL EXTERIOR WALL OR DOOR TO THIS ENCLOSURE WITH A NFPA 704 PLACARD. SEE INSPECTOR FOR ADDITIONAL REQUIREMENTS.
I*** ATTENTION*** ANNUAL HAZARDOUS MATERIALS PERMIT IS REQUIRED DUE TO MEDICAL GAS; AND DIESEL TANK @ 344 GALLONS TANK INSTALLATION PERMIT INSPECTION REQUIRED. ** This facility REPORTED ZERO ELECTROLYTE OR BATTERIES ON APPLICATION. CONTACT THE DIVISION OF THE FIRE MARSHAL @ 719-385-5978 TO SCHEDULE YOUR INSPECTIONS WITH HAZMAT SPECIALIST JAY WEIGHTMAN.
IBATTERIES NOT declared on this submittal: telectrolyte solution for an aggragate volume of ? gallons. Not declared nor number of batteries. REPORT AMOUNTS TO INSPECTOR AT THE TIME OF INSPECTION.
FYIABOVE GROUND FUEL TANKS The CSFD requires a Construction Permit for the installation of any aboveground fuel tank in excess of 60 gallons. (This tank declared as 344 gal by applicant, dbl. walled tank integrated onto generator). Flammable and combustible liquids shall comply with the IFC 2009 CHAPTERS 34 AND 27 as amended, and NFPA 30. It is the responsibility of the TANK INSTALLER to submit an application for the tank installation permit prior to installation. The tank installer shall submit to : Kay Yeager CSFD Office of the Fire Marshal 375 Printers Parkway CSFD received tank permit application and the ROCKY MOUNTAIN CUMMINS tank manufacturer's cut sheets, a declaration of contained volume, a declaration of tank contents and a site plan of the tank location with respect to walls, other structures, property lines, drive lanes, etc., and MSDS for the diesel contents. Exterior tanks will be required to have vehicular protection diagrammed and installed in accordance with the 2009 IFC, Chapter 3. Any associated piping shall be diagramed and submitted as well. ***********
FYIInstallation consists of one 375 GAL AST, double wall UL listed 142 / 2200 generator set. Contains #2 Diesel fuel. SEE ELECTRONIC DOCUMENTS AT LOADING DOCK; RAISED, NO VEHICLE IMPACT CUMMINS Double wall tank specification diagram provided (see electronic documents)
FYILabeling - An NFPA 704 compliant Hazard Placard is required for each pedestrian entry door rooms containing hazardous materials in excess of the exempt amounts (this door could be interior or exterior) and all such doors shall be included. The minimum size of the Hazard Placard shall be 15" by 15". This requirement is subject to verification at the time of the Hazardous materials Inspection prior to signing the Fire Final. ************** ATTENTION: The NFPA ratings found on the MSDS for diesel and batteries shall be identified on the NFPA placard.
FYI{AST} Individual storage tanks containing Class I, II, or IIIA liquids shall be placarded in accordance with NFPA 704.
FYI{AST} A minimum 20B rated fire extinguisher shall be located no closer than 10 feet to the storage tank and no farther than 50 feet. A single fire extinguisher may provide coverage for more than one tank but the minimum and maximum travel distances shall be achieved.


 