| Review Date | Status | Comment(s) |
| 12/1/2009 |
FYI | *****(STANDARD COMMENT 102) The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows:
1. RBD has completed their review and provided the necessary information.
|
| 11/17/2009 |
FYI | *****(STANDARD COMMENT 1) This project is: Woodcraft, 750 Garden of the Gods Rd, Suite 130: Interior Finish
You can access our web site for the latest fire department plan review comments:
1. From www.pprbd.org, select "RELATED WEB SITES" in the upper right corner.
2. Click on Colorado Springs FIRE PREVENTION.
3. Then select VIEW PLAN REVIEW STATUS.
4. Scroll down to the correct address.
5. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
|
| FYI | (STANDARD COMMENT 2) REVIEWS:
Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents.
The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD.
|
| Disapproved | (STANDARD COMMENT 100) PLANS DISAPPROVED:
The following information and/or corrections are needed prior to conducting a full plan review
1. RBD construction REVIEW is required prior to CSFD approvals. Please note RBD need not approve the plans before CSFD, however, the cody study is not properly filled out and thus I cannot perform a complete review at this time. I need to know the size of this space, the occupant load, construction type, etc.
All corrections and comments shall be submitted back to CSFD in writing, or provide submittal sheets/drawings/ blueprints etc. as requested, which will allow us to complete our review. We do not accept plan review corrections over the phone, via fax, or verbally.
|
| FYI | (STANDARD COMMENT 3) PERMITS
Insure all applicable permits are obtained from the Regional Building Department and the Colorado Springs Fire Department for the work that is being done at this site.
|
| FYI | (STANDARD COMMENT 4) RE-REVIEWS (commercial construction plans only)
Re-reviews may be submitted back to the CSFD by direct submittal at the Construction Services counter, or through the Regional Building Department's routing system.
|
| FYI | (STANDARD COMMENT 32) SUITE NUMBERS
Provide suite numbers as per fire code. In malls or shopping center suites-4" high w/ 1/2" stroke and visible at 50 feet, hotel rooms 2" high w/ 1/4" stroke, and office suites 2" high w/ 1/4" stroke.
Suite numbers shall be provided on the rear doors of multi-tenant strip centers as well.
|
| FYI | (STANDARD COMMENT 41) KNOX (TM) ENTRY FOR EXISTING BUILDINGS
Existing KNOX (TM) Box shall be updated to provide a minimum of 2 sets of labeled keys for all doors and tenants.
|
| FYI | (STANDARD COMMENT 82) FIRE PROTECTION SYSTEM PLANS
Applicable Fire Protection System (fire alarm, fire sprinkler, fixed fire) plans shall be submitted to the CSFD Construction Services office in the Development Review Enterprise at the Regional Development Center 2880 International Circle
|
| FYI | (STANDARD COMMENT 90) INSPECTIONS
A minimum of a 2-business day notice is required for all inspections. Please have your eight digit "Fire Department Plan Review Number" ready when calling to schedule an inspection.
|
| FYI | (STANDARD COMMENT 93) KHJ - SCHEDULING INSPECTIONS: STATIONS 1, 2, 3, 4, 5, 9, 13, 16
Colorado Springs Fire Department Inspectors schedule their own inspections. Based upon geographic location of this project, your assigned Inspector is Kris Johnson. You may contact him at 719-385-7257 to schedule all construction related inspection activities.
When calling, please have your complete CSFD plan review number(s) ready for each inspection request.
( i.e. 2005-1234-CN-1 or 2005-0012-SP-1)
|
| FYI | (STANDARD COMMENT 101) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS.
IT IS THE RESPONSIBILITY OF THE DESIGNER/ARCHITECT TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE ADOPTED CODES/STANDARDS AND INCORRECT INFORMATION PRIO TO RESUBMITTING.
|