| Review Date | Status | Comment(s) |
| 11/2/2009 |
FYI | *****(STANDARD COMMENT 1) This project is: Charis Christian Center - 720 Elkton Dr. Addition to two existing buildings, creating one larger building.
ATTENTION: See our web site for our latest plan review comments for your job at:
www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work. smc - 1-02/rev 2-07
|
| Attention | The information being given on this review is based on information being given on the plan indicating this entire structure (existing and addition) will be fire sprinklered.
|
| Attention | *****(STANDARD COMMENT 2) HYDRANT/BUILDING DATA:
Size of Bldg. -26178- sq ft
Construction Type -III-B-
Fire Sprinklers Y--
50% reduction shown on plans - NOTE: 1500 gpm is CSFD minimum flow
Required GPM: -3500- gpm
# of hydrant(s) required: -4-
Max AVG spacing between hydrants: -350- ft
Max hose lay: -210- ft
|
| Disapproved | DISAPPROVED: The following information and/or corrections are needed prior to completing a full plan review:
1) We need copy for CSFD records
2) We need CSU Theoretical flow report
3) Required fire flow is 3500 GPM on 4 hydrants. If structure is completely sprinklered a 50% reduction may be granted. This would result in 1750 GPM on 2 hydrants. Hydrant 799 C is within required spacing and it appears it is within the 100' spacing from the FDC as indicated on the south, street facing side of structure. Hydrant 1121 C may be within required spacing depending on barriers and landscaping separating parking lot and structure.
Also:
1) Review all redline comments and address each one.
2) Return ALL red lined plan sets for each re-review.
NOTE: The disapproved items may not constitute a complete list of violations. The designer is to conduct a complete re-review of the plans for additional violations of the standard and incorrect information prior to resubmitting. |
| Attention | READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
***NEW: Walk-in hours for mylar signatures are: Tuesday and Thursdays from 8am-11am.
If you need other assistance, contact Kristen McClellan at 719.385.7347 to schedule an appointment.
klm 6-08 |
| Disapproved | *****(STANDARD COMMENT 17) DEVELOPMENT PLAN: According to the CSFD records for this project, the Development Plan for this site has not been approved by the fire department. This hydrant/water plan can not be approved until the D.P. has been approved by the CSFD.
smc -1-05 |
| Disapproved | *****(STANDARD COMMENT 25) FIRE FLOW: Provide confirmation on the fire flow results from Colorado Springs Utilities. A copy of their report for this area is required to be provided with your plan submittals.
When multiple fire flows are provided from CSU, please indicate all flows on your submitted plans.
Contact the city water department for specific information on water line sizing, water line and hydrant specifications, plan review for water/hydrant systems, water system modeling, water flow information, water flow testing, etc.
NOTE - If you do not have the MODELED fire flow data, contact Keta Donegan, 668-8733 or FAX 668-5651 - she will provide the necessary flow information to you. ATTENTION - Allow 3 business days for Keta to provide the fire flow data. 1/04 dem. |
| FYI | *****(STANDARD COMMENT 3) HYDRANT PAINTING REQUIREMENT: Fire hydrants shall be painted in compliance with Colorado Springs Utilities color coding standards. By using these standards the emergency response crews are provided a quick way to decipher how much water is available from a specific hydrant. The gpm of the hydrant are determined by an actual water flow test, and it is imperative the testing and color coding is accurate. smc 9-07 |
| FYI | *****(STANDARD COMMENT 4) ON SITE FIRE HYDRANT FLOWS:
PRIOR TO THE TIME OF FIRE FINAL INSPECTIONS, on all new construction sites, it will be the responsibility of the owners, GC, or site manager, to have all new and existing fire hydrants, and private water systems flow tested. Per the IFC, all hydrants are to be installed and in service prior to any construction.
**ALL HYDRANT TESTS SHALL BE CONDUCTED BEFORE ON-SITE CONSTRUCTION IS STARTED!!!
As with any new or revised fire protection system, the Fire Department will need to witness all tests to verify the system will meet the fire flow requirements established during the plan review process. If this test occurs without Fire personnel on site, it will be deemed unacceptable by the inspector and will delay the final fire approval. (IFC 2003, Chapter 1) RJG 1/06
Contact SEAN HIGBEE, CSU at 668-4595 to schedule an ACTUAL flow test of CITY OWNED/PUBLIC hydrants. Be sure to provide them with a CSFD plan review number to include with their flow reports.
Contact CSFD Fire Prevention t 385-5982 to schedule a flow test of PRIVATE OWNED hydrants. A contractor capable of performing the test will be required as CSFD Inspectors WITNESS only. dem 1/04 rev smc-9-06 |
| FYI | *****(STANDARD COMMENT 6) This is a PUBLIC water system. |
| FYI | *****(STANDARD COMMENT 8) GENERAL INSPECTIONS/PLANS & SCHEDULING. Minimum notice of two business days is required for all inspections. Due to work loads, holidays, meetings, vacations, etc...the CSFD cannot guarantee a two business day turnaround on all inspections. PLEASE help yourself by helping us - call your inspections in with ample time to allow adequate scheduling.
When calling, please have your complete CSFD plan review number(s) ready for each inspection request.
( For Example: 2005-1234- HS-2)
The CSFD APPROVED sets of plans SHALL be on site for all inspections.
|
| FYI | *****(STANDARD COMMENT 12) INSPECTOR JOHNSON:
Your assigned Inspector is Kris Johnson. You may contact him at 719-385-7257 to schedule all construction related inspection activities.
|
| FYI | *****(STANDARD COMMENT 14) If you have any specific questions or concerns about these comments, please feel free to contact me at:
Rhonda Embres
Fire Inspector
Colorado Springs Fire Department
TEL 719-385-7369
FAX 719-385-7385
kthiessen@springsgov.com
**New Walk-In hours are Tuesday and Thursday from 8-11 am. Walk-Ins are for mylar signatures, re-reviews and question about layouts, fire flow, etc. |