| Review Date | Status | Comment(s) |
| 1/5/2010 |
FYI | *****(STANDARD COMMENT 1) This project is: Restroom Facility, 715 Prospect Lake Dr: New precast restroom
You can access our web site for the latest fire department plan review comments:
1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS
3. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
|
| FYI | (STANDARD COMMENT 19) EXISTING HYDRANTS ACCEPTABLE
The existing fire hydrants appear to be acceptable.
NOTE: EXISTING HYDRANTS DO NOT PROVIDE THE MINIMUM 1500 GPM, HOWEVER, THE RISK IS VERY LOW CONSIDERING THE SIZE, CONSTRUCTION AND USE OF THIS STRUCTURE. CSFD IS NOT REQUIRING SIMULTANEOUS FLOWS OR ADDITIONAL HYDRANTS MEETING THE 1500 GPM REQUIREMENT.
|
| FYI | (STANDARD COMMENT 33) STRUCTURES MORE THAN 100-FEET FROM THE ROAD:
Approved numeric addresses shall be represented by numbers that are a minimum of 5-inches high with no less then ½-inch stroke and contrast with their background so as to be plainly visible and legible from a distance of at least 100-feet from the structure.
Option 1: install a remote address sign clearly posted at all street entrances to the structure.
Option 2: Increase the size of the numbers/letters to be plainly visible and legible from the street.
|
| FYI | (STANDARD COMMENT 90) INSPECTIONS
A minimum of a 2-business day notice is required for all inspections. Please have your eight digit "Fire Department Plan Review Number" ready when calling to schedule an inspection.
|
| FYI | (STANDARD COMMENT 93) KHJ - SCHEDULING INSPECTIONS: STATIONS 1, 2, 3, 4, 5, 9, 13, 16
Colorado Springs Fire Department Inspectors schedule their own inspections. Based upon geographic location of this project, your assigned Inspector is Kris Johnson. You may contact him at 719-385-7257 to schedule all construction related inspection activities.
When calling, please have your complete CSFD plan review number(s) ready for each inspection request.
( i.e. 2005-1234-CN-1 or 2005-0012-SP-1)
|
| 10/26/2009 |
FYI | *****(STANDARD COMMENT 1) This project is: Restroom Facility, 715 Prospect Lake Dr: New precast restroom
You can access our web site for the latest fire department plan review comments:
1. From www.pprbd.org, select "RELATED WEB SITES" in the upper right corner.
2. Click on Colorado Springs FIRE PREVENTION.
3. Then select VIEW PLAN REVIEW STATUS.
4. Scroll down to the correct address.
5. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
|
| FYI | (STANDARD COMMENT 4) RE-REVIEWS (commercial construction plans only)
Re-reviews may be submitted back to the CSFD by direct submittal at the Construction Services counter, or through the Regional Building Department's routing system.
|
| Disapproved | (STANDARD COMMENT 10) DEVELOPMENT PLAN
Attach copies of the "City Approved" development plan to each set of construction plans submitted to the Colorado Springs Fire Department for review.
|
| Disapproved | (STANDARD COMMENT 15) WATER PLANS
The City APPROVED" fire hydrant and water main plans are to be ATTACHED to all sets of construction plans for CSFD plan reviews.
|
| FYI | (STANDARD COMMENT 16) EXISTING HYDRANTS
If it is felt that the existing fire hydrants will provide adequate fire flow and will be the correct number of required hydrants, the applicant will need to contact Keta Donegan with COLORADO SPRINGS UTILITIES at (719) 668-8733 or by FAX at (719) 668-5651 to request a theoretical fire flow calculation and fire hydrant location map.
Keta will need the following information to process your request:
1) Gross square footage of the structure (including all floor levels, basements, and attached canopies)
2) Type of construction determined by the Regional Building Department
3) Requesters name
4) Requestors company name
5) Phone and fax numbers of the requestor
6) Project address
7) Project cross streets
8) Public Hydrant numbers of the closest fire hydrants (you can find this number in white lettering on top of the hydrant)
ATTENTION: ALLOW A MINIMUM OF 3 DAYS FOR ALL FIRE FLOW CALCULATIONS
|
| Disapproved | *****(STANDARD COMMENT 17) HYDRANT REQUIREMENTS:
Size of Structure (gross square footage) -568- sq ft;
Type of construction -V-B-;
Is building sprinkled Y -- N -XXX-;
GPM requirements -1500- gpm;
Number of hydrant(s) required; -1-
Max. spacing between hydrants -500- ft;
Max. hose lay -250- ft;
|