NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING. System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.
GSA SALLYPORT 00415 PIKES PEAK AV
| Review Date | Status | Comment(s) |
| 10/26/2009 |
FYI | *****(STANDARD COMMENT 1) This project is: GSA Immigration and Customs Enforcement, 415 E Pikes Peak, Suite 115: Sallyport tenant finish
You can access our web site for the latest fire department plan review comments:
1. From www.pprbd.org, select "RELATED WEB SITES" in the upper right corner.
2. Click on Colorado Springs FIRE PREVENTION.
3. Then select VIEW PLAN REVIEW STATUS.
4. Scroll down to the correct address.
5. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
|
| FYI | (STANDARD COMMENT 2) REVIEWS:
Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents.
The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD.
|
| FYI | (STANDARD COMMENT 3) PERMITS
Insure all applicable permits are obtained from the Regional Building Department and the Colorado Springs Fire Department for the work that is being done at this site.
|
| FYI | (STANDARD COMMENT 22) FIRE EXTINGUISHER - COMMERCIAL BUILDINGS
A "2A -10B:C" fire extinguisher is to be installed in LOW TO MODERATE HAZARD OCCUPANCIES at a rate of 1 unit per 3,000 square feet, AND a maximum of a 75-ft travel distance to an extinguisher.
Remember that all extinguishers must be installed in highly visible and accessible locations, never in a dead-end area, and always try to place them near an exit path-way or at an exit(s). Mount 4" off floor to a maximum of 5 ft. to the top of the fire extinguisher. (HINT: About waist high is perfect)
ATTENTION: "FIRE EXTINGUISHER" signs may need to be posted to properly identify where the units are located if they're not highly visible.
|
| FYI | (STANDARD COMMENT 32) SUITE NUMBERS
Provide suite numbers as per fire code. In malls or shopping center suites-4" high w/ 1/2" stroke and visible at 50 feet, hotel rooms 2" high w/ 1/4" stroke, and office suites 2" high w/ 1/4" stroke.
Suite numbers shall be provided on the rear doors of multi-tenant strip centers as well.
|
| FYI | (STANDARD COMMENT 41) KNOX (TM) ENTRY FOR EXISTING BUILDINGS
Existing KNOX (TM) Box shall be updated to provide a minimum of 2 sets of labeled keys for all doors and tenants.
|
| FYI | (STANDARD COMMENT 82) FIRE PROTECTION SYSTEM PLANS
Applicable Fire Protection System (fire alarm, fire sprinkler, fixed fire) plans shall be submitted to the CSFD Construction Services office in the Development Review Enterprise at the Regional Development Center 2880 International Circle
|
| FYI | (STANDARD COMMENT 90) INSPECTIONS
A minimum of a 2-business day notice is required for all inspections. Please have your eight digit "Fire Department Plan Review Number" ready when calling to schedule an inspection.
|
| FYI | (STANDARD COMMENT 93) KHJ - SCHEDULING INSPECTIONS: STATIONS 1, 2, 3, 4, 5, 9, 13, 16
Colorado Springs Fire Department Inspectors schedule their own inspections. Based upon geographic location of this project, your assigned Inspector is Kris Johnson. You may contact him at 719-385-7257 to schedule all construction related inspection activities.
When calling, please have your complete CSFD plan review number(s) ready for each inspection request.
( i.e. 2005-1234-CN-1 or 2005-0012-SP-1)
|
|