| Review Date | Status | Comment(s) |
| 3/10/2010 |
Attention | Address changed from 5 to 8 Marsheffel. This is confirmed on the RBD website for this plan. |
| 2/10/2010 |
FYI | HAZMAT REVIEW COMPLETED SEE HM COMMENTS KAY 2/10/10 FOR DW |
| 11/6/2009 |
Disapproved | HazMat need to review these plans. |
| 10/14/2009 |
FYI | *****(STANDARD COMMENT 1) This project is: Mercaptan Tank Enclosure, 5 Marksheffel Rd: New vault around existing mercaptan tanks
You can access our web site for the latest fire department plan review comments:
1. From www.pprbd.org, select "RELATED WEB SITES" in the upper right corner.
2. Click on Colorado Springs FIRE PREVENTION.
3. Then select VIEW PLAN REVIEW STATUS.
4. Scroll down to the correct address.
5. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
|
| FYI | (STANDARD COMMENT 2) REVIEWS:
Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents.
The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD.
|
| FYI | (STANDARD COMMENT 3) PERMITS
Insure all applicable permits are obtained from the Regional Building Department and the Colorado Springs Fire Department for the work that is being done at this site.
|
| FYI | (STANDARD COMMENT 19) EXISTING HYDRANTS ACCEPTABLE
The existing fire hydrants appear to be acceptable.
|
| FYI | (STANDARD COMMENT 90) INSPECTIONS
A minimum of a 2-business day notice is required for all inspections. Please have your eight digit "Fire Department Plan Review Number" ready when calling to schedule an inspection.
|
| FYI | (STANDARD COMMENT 92) JAH - SCHEDULING INSPECTIONS: FIRE STATIONS 6, 7, 8, 11, UCCS:
Colorado Springs Fire Department Inspectors schedule their own inspections. Based upon geographic location of this project, your assigned Inspector is Jeff Hanenberg. You may call 719-385-7359 to schedule all construction related inspection activities.
When calling, please have your complete CSFD plan review number(s) ready for each inspection request.
( i.e. 2005-1234-CN-1 or 2005-0012-SP-1)
|