NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

CTI
01096 ELKTON DR

Review DateStatusComment(s)
11/5/2009 FYI*****(STANDARD COMMENT 1) This project is: ATTENTION: See our web site for our latest plan review comments for your job at: www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work. smc - 1-02/rev 2-07
FYIRE-REVIEW: The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1. Plans have been revised to show the hydrant supporting the FDC is tapped directly to the main, and not on the main also feeding the fire sprinklers. ATTENTION CONTRACTORS: ISSUES LISTED AS "ISSUE RESOLVED" OR "ISSUE APPROVED" ARE ONLY ITEMS FINALIZED FOR PLAN REVIEW. PLAN REVIEW COMMENTS ARE SUBJECT TO FINAL INSPECTIONS, AND "ON SITE" FIRE FLOW TESTS WILL BE REQUIRED PRIOR TO FINALIZING ANY STRUCTURE FOR OCCUPANCY.
10/13/2009 FYI*****(STANDARD COMMENT 1) This project is: Office Warehouse, 1096 Elkton Dr: ATTENTION: See our web site for our latest plan review comments for your job at: www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work. smc - 1-02/rev 2-07
Disapproved*****(STANDARD COMMENT 25) FIRE FLOW: Provide conformation on the fire flow results from Colorado Springs Utilities. A copy of their report for this area is required to be provided with your plan submittals. When multiple fire flows are provided from CSU, please indicate all flows on your submitted plans. Contact the city water department for specific information on water line sizing, water line and hydrant specifications, plan review for water/hydrant systems, water system modeling, water flow information, water flow testing, etc. NOTE - If you do not have the MODELED fire flow data, contact Keta Donegan, 668-8733 or FAX 668-5651 - she will provide the necessary flow information to you. ATTENTION - Allow 3 business days for Keta to provide the fire flow data. 1/04 dem.
Disapproved*****(STANDARD COMMENT 18) DEAD END MAINS: Unless approved, dead end mains shall not be used when all of the following are located on a single tap main: 1. Automatic fire sprinkler systems. 2. Fire hydrants supporting the Fire Department Connection. 3. Fire hydrants required for external fire protection.


 