NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

ROCKY MOUNTAIN AUTO BROKERS - MAIN
04912 CARRARA PT

Review DateStatusComment(s)
2/2/2010 ApprovedRevised plans submitted for a change in building construction type. Revised approved water plans included.
1/27/2010 DisapprovedPlans were resubmitted however I don't know what I am supposed to be looking at. It appears the construction type has been changed from II-B to V-B. This has a huge effect on your required fire flows, number and spacing of required fire hydrants. Plans are disapproved, as well and the fire hydrant plans.
10/7/2009 FYI*****(STANDARD COMMENT 1) This project is: Rocky Mountain Auto Brokers, 4912 Carrara Pt. You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select "RELATED WEB SITES" in the upper right corner. 2. Click on Colorado Springs FIRE PREVENTION. 3. Then select VIEW PLAN REVIEW STATUS. 4. Scroll down to the correct address. 5. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYI*****(STANDARD COMMENT 102) The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1. Approved development plan attached 2. approved water plan attached 3. Letter attached (reference edocs) stating there will be no oil changes, servicing, etc of motor vehicles - area to be used strictly for wash/detailing, tires/rims and accessories.
9/22/2009 FYI*****(STANDARD COMMENT 1) This project is: Rocky Mountain Auto Brokers, 4912 Carrara Pt. You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select "RELATED WEB SITES" in the upper right corner. 2. Click on Colorado Springs FIRE PREVENTION. 3. Then select VIEW PLAN REVIEW STATUS. 4. Scroll down to the correct address. 5. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
AttentionPrevious comments have not been addressed.
Disapproved"S1" OCCUPANCY - Provide a detailed explanation of the exact types of work being done in this facility. Clearly state if there will be welding, or automotive repair within this facility. If there are hazardous materials used for this process, provide detailed information as is listed in our haz-mat HMMP requirements. Fill out and submit our "Hazardous Materials Permit Amount Certification Form." Your haz-mat must be under the exempt amounts for this facility to be considered as a S occupancy. This is per UBC Table 307.7(1) and see Section 406.6.
Disapproved(STANDARD COMMENT 10) DEVELOPMENT PLAN Attach copies of the "City Approved" development plan to each set of construction plans submitted to the Colorado Springs Fire Department for review.
Disapproved(STANDARD COMMENT 15) WATER PLANS The City APPROVED" fire hydrant and water main plans are to be ATTACHED to all sets of construction plans for CSFD plan reviews.
8/27/2009 FYI*****(STANDARD COMMENT 1) This project is: Rocky Mountain Auto Brokers at Powers Autopark. You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select "RELATED WEB SITES" in the upper right corner. 2. Click on Colorado Springs FIRE PREVENTION. 3. Then select VIEW PLAN REVIEW STATUS. 4. Scroll down to the correct address. 5. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
FYI(STANDARD COMMENT 2) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD.
FYI(STANDARD COMMENT 3) PERMITS Insure all applicable permits are obtained from the Regional Building Department and the Colorado Springs Fire Department for the work that is being done at this site.
Disapproved(STANDARD COMMENT 10) DEVELOPMENT PLAN Attach copies of the "City Approved" development plan to each set of construction plans submitted to the Colorado Springs Fire Department for review.
Disapproved(STANDARD COMMENT 15) WATER PLANS The City APPROVED" fire hydrant and water main plans are to be ATTACHED to all sets of construction plans for CSFD plan reviews.
Disapproved "S1" OCCUPANCY - Provide a detailed explanation of the exact types of work being done in this facility. Clearly state if there will be welding, or automotive repair within this facility. If there are hazardous materials used for this process, provide detailed information as is listed in our haz-mat HMMP requirements.
Disapproved(STANDARD COMMENT 70) HAZARDOUS MATERIAL- SUBMIT INFORMATION Provide listed information on the haz-mat permit amount certification form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility. Provide information on all types, quantities (both in use and in storage), used at the site. This would include swimming pool/spa/whirlpool chemicals. Be aware of motor oils, washer fluids, any soaps in the wash bay (irritants). Where are you storing used motor oil? PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS, AND FILL OUT THE REQUESTED INFORMATION. All forms and packets are available at http://www.springsgov.com/Page.aspx?NavID=1094.
FYI(STANDARD COMMENT 21) FIRE EXTINGUISHERS - HAZARDOUS AREAS In HIGH-HAZARD OCCUPANCIES a "4A - 40B:C" extinguisher at a rate of 1 unit per 1500 square feet and a 50-foot travel distance is required. Install at least one extinguisher per floor/level. Placement of fire extinguishers inside of hazardous rooms and/or areas is NOT an acceptable location for these appliances. Remember that all extinguishers must be installed in highly visible and accessible locations, never in a dead-end area, and always try to place them near an exit path-way or at an exit(s). Mount 4" off floor to a maximum of 5 ft. to the top of the fire extinguisher. (HINT: About waist high is perfect) ATTENTION: "FIRE EXTINGUISHER" signs may need to be posted to properly identify where the units are located if they're not highly visible.
FYI(STANDARD COMMENT 22) FIRE EXTINGUISHER - COMMERCIAL BUILDINGS A "2A -10B:C" fire extinguisher is to be installed in LOW TO MODERATE HAZARD OCCUPANCIES at a rate of 1 unit per 3,000 square feet, AND a maximum of a 75-ft travel distance to an extinguisher. Remember that all extinguishers must be installed in highly visible and accessible locations, never in a dead-end area, and always try to place them near an exit path-way or at an exit(s). Mount 4" off floor to a maximum of 5 ft. to the top of the fire extinguisher. (HINT: About waist high is perfect) ATTENTION: "FIRE EXTINGUISHER" signs may need to be posted to properly identify where the units are located if they're not highly visible.
FYI*****(STANDARD COMMENT 50) OCCUPANT LOAD THE OCCUPANT LOAD FOR THIS FACILITY IS: 64 The occupant load, calculated by the Regional Building Department shall be posted in a visible location. This determined number shall not be exceeded under any circumstance.
FYIHIGH PILED-NOT APPROVED. This facility will not be permitted to stock over 12 feet, and proper "NO STACKING OVER 12' " signs must be posted throughout the warehouse/stock room as per CSFD requirements. Proper documentation must be either printed directly on the plans themselves and/or attached to the approved sets of construction plans. Provide CSFD with the proper form stating that the owner understands this signage is to be posted. Forms available from CSFD Fire Prevention. This documentation must be from the owners of the business, and signed by the owners. These forms go into our files and copies are attached to the plans. If, in the future, the issue of the type of stacking allowed in this facility is disputed, we will have hard evidence that the owners of the business did agree to the restrictions and limitations the fire code and the CSFD have placed on the stacking and storage being accomplished at this site. IFC 2311 as ammended. smc 1-08
FYI(STANDARD COMMENT 71) HAZ-MAT REVIEW REQUIRED It appears that hazardous materials may be located on site. Your plans have been forwarded to the HazMat reviewer. If hazardous materials exceed exempt amounts, you will also be required to submit a Hazardous Material Management Plan for annual permitting. Additional tank installation permits and plan reviews may also be required. Check with the CSFD for details.
FYI*****(STANDARD COMMENT 73) HAZ-MAT CERT FORM The hazardous materials amount certification form has been completed, submitted and attached to the building plans. This form states that there WILL NOT be excessive amounts of hazardous materials at this facility.
FYI(STANDARD COMMENT 90) INSPECTIONS A minimum of a 2-business day notice is required for all inspections. Please have your eight digit "Fire Department Plan Review Number" ready when calling to schedule an inspection.
FYI(STANDARD COMMENT 92) SCHEDULING INSPECTIONS INSPECTOR HANENBERG: FIRE STATIONS 6, 7, 8, 11, UCCS: Colorado Springs Fire Department Inspectors schedule their own inspections. Based upon geographic location of this project, your assigned Inspector is Jeff Hanenberg. You may call 719-385-7359 to schedule all construction related inspection activities. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( i.e. 2005-1234-CN-1 or 2005-0012-SP-1)
FYI(STANDARD COMMENT 101) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. IT IS THE RESPONSIBILITY OF THE DESIGNER/ARCHITECT TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE ADOPTED CODES/STANDARDS AND INCORRECT INFORMATION PRIO TO RESUBMITTING.


 