NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

HARVEST DISTRIBUTION
04395 BUCKINGHAM DR

Review DateStatusComment(s)
10/27/2009 ApprovedRevised plans dropped off for correction in address. No change in system. Plans are still approved
6/24/2009 FYI*****(STANDARD COMMENT 1) This project is: Harvest Distribution, 4360 Buckingham Drive. Paint Booth ATTENTION: See our web site for our latest plan review comments for your job at: www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work.
FYI*****(STANDARD COMMENT 5) The special hazard suppression system is being installed by: Cintas This plan review is based on the requirements found within the 2003 editions of the International Building Code, International Fire Code and the most recent editions of the NFPA standards as applicable.
FYI*****(STANDARD COMMENT 6) SPECIAL HAZARD SUPPRESSION SYSTEM DESIGN: Type of System: Spray Booth Size of System: 4 - IS 45ABC tanks, 1 - IS 18 ABC tank, 16 - TF ABC nozzels, one Duct Nozzel Hazard Protected:paint booth
FYI(PAINT BOOTH) DRY CHEMICAL, CO2, CLEAN AGENT: The system shall be capable of discharging its contents into the entire protected area simultaneously. (NFPA 33:9.5)
FYI(PAINT BOOTH) MAKE-UP AND EXHAUST AIR: Air make-up systems and spray area exhaust systems shall remain functioning during any fire alarm condition. Exception: Where the type of automatic fire protection system requires air shut down Exception: Powder-coating systems. (NFPA 33:9.3)
FYI(PAINT BOOTH) AUTOMATIC SPRINKLERS: Sprinklers shalla be permittd to be covered by cellophane bags having a thickness of 0.08mm (0.003 in) or less or by thin paper bags. These coverings shall be replaced frequently so that heavy deposits of residue do not accumulate. (NFPA 33:9.4.7.1)
FYI(PAINT BOOTH) ELECTROSTATIC SPRAY APPLICATION: Automated liquid electrostatic spray application equipment shall be further protected by listed optical flame detection, and shall accomplish all of the following: a. Activate a local alarm b. Transmit an alarm to fire alarm system if provided c. Shut down coating material delivery system d. Shut down all spray application systems e. Stop any conveyors into/out of spray area f. Disconnect power to the high voltage elements in the spray area and de-energize the system. (NFPA 33:9.8)
FYI(PAINT BOOTH) POWDER COATING: Automated powder application equipment shall be further protected by listed optical flame detection, and shall accomplish all of the following: a. Stop any conveyors into/out of the spray area. b. Shut off Ventilation c. Shut off application, transfer and powder collection equipment d. Close segregation dampers in associated ductwork e. Disconnect power to the high voltage elements in the spray area and de-energize the system. (NFPA 33:9.7)
FYI(PAINT BOOTH) DRY CHEMICAL FUEL SHUT-OFF: Where systems protect hazards that are normally heated, the power or fuel supply to heaters shall be shut off automatically upon actuation of the extinguishing systems. Where systems protected hazards that have flowing flammable or combustible fluids or gases, the system shall be provided with automatic means to ensure shuroff of power and fuel valves upon operation of the extinguishing systems. All shutoff systems shall require manual resetting. (NFPA 17:5.5.1-2)
FYI(STANDARD COMMENT) INDICATION OF SYSTEM ACTIVATION: An audible OR visual indication shall be provided that the system has operated, that personnel response is needed, and that the system is inneed of recharge. (IFC 904.3.4; NFPA 17:5.7.3; NFPA 17A: 5.2.1.8)
FYI(STANDARD COMMENT) FIRE ALARM SYSTEM CONNNECTIONS: The extinguishing system shall be connected to the fire alarm system, if provided, in accordance with NFPA 72. (NFPA 17:5.7.4; NFPA 17A: 5.2.1.9)
FYI(STANDARD COMMENT) MANUAL PULL STATIONS: A readily accessible means for manual activation shall be installed at an approved location in the path of egress. Pull stations for multiple system shall be installed in the same location. All manual pull stations shall be permanently and clearly identified as to the hazard and/or system they protect. (IFC 904.11.1; 2002 NFPA 17:5.7.1.7; 17A 4.4.2.5 and 5.2.1.10; 2001:4.3.3.6, 4.3.3.10)
FYI(STANDARD COMMENT) NOZZLES: All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease, vapors, moisture or other foreign materials into the piping. (NFPA 17: 4.3.1.5; NFPA 17A 4.3.1.5; 2001:4.2.5.4)
FYI(STANDARD COMMENT) MULTIPLE HAZARDS: Where two or more hazards can be simultaneously involved in fire by reason of their proximity, they shall be protected by one of the following methods: 1. Individual systems installed to operate simultaneously OR 2. A single system designed to portect all hazards that can be simultaneously involved. (NFPA 17:5.2.1; NFPA 17A: 5.1.5)
FYI(STANDARD COMMENT 8) CERTIFICATE OF INSTALLATION: Attached to these approved plans is the "Certificate of Installation". It is the installer's responsibility to certify through this form that the system has been properly installed and tested. The form is to be filled out in its entirety PRIOR TO THE ARRIVAL OF THE FIRE INSPECTOR that is conducting the final inspection and/or the acceptance test of the system. FINAL INSPECITONS WILL NOT BE CONDUCTED WITHOUT THIS FORM BEING COMPLETED.
FYI(STANDARD COMMENT 9) MANUFACTURER'S DATA The approved set of extinguishing system plans, manufacture's product data sheets on all equipment being installed, and the installation permit are to be on site for all fire department inspections.
FYI(STANDARD COMMENT 10) INSPECTIONS A minimum of 2-business days notice is required for all inspections. Please have your eight digit "Fire Department Plan Review Number" ready when calling to schedule an inspection. This number can be obtained from the General Contractor and/or is found in a blue stamp on the front or the back of the approved set of plans.
FYI(STANDARD COMMENT) KHJ - SCHEDULING INSPECTIONS: Starting October 3, 2005, Fire Inspectors will be scheduling their own calendars. Your assigned Inspector is Kris Johnson. You may contact him at 719-385-7257 to schedule all construction related inspection activities
FYI(STANDARD COMMENT) PAINT BOOTH - SCHEDULING INSPECTIONS: Please call the Office of the Fire Marshal at 385-5978 to schedule your suppression system inspection for Paint Booths. A Hazardous Materials Fire Inspector will complete the inspection process.
FYI(STANDARD COMMENT 2) ATTENTION: CSFD FEES. All fire department fees are to be paid prior to issuance of any permits. These fees must be paid directly to the Colorado Springs Fire Department - Development Review Enterprise - at 2880 International Circle - Suite 200-7.


 