| Review Date | Status | Comment(s) |
| 11/4/2009 |
Approved | Plans revised to relocate a fire hydrant and adjust required fire flows. |
| 5/6/2009 |
Approved | Mylars Signed, Plans Approved. |
| 4/30/2009 |
FYI | *****(STANDARD COMMENT 1) This project is: Moving one hydrant for the proposed expansion of Al Serra Volkswagen, 1580 Auto Mall Loop.
SYSTEMS: None.
CN:Code: 03 IBC - 03 IFC - 05 PPRBC /Class: B and S-1 / Const: II-B /Stories: 1 /Size: 14945 /OL:
FH:Required Flow: 2000 gpm /# 2 Hydrants /On site flow: 2300 and 2000 gpm
DV: Proposing to modify the existing Hummer building and convert it to Volkswagen Sales. Proposed SQ FT will be 14,945. largest fire area is 9729 sq ft.
ATTENTION: See our web site for our latest plan review comments for your job at:
www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work. smc - 1-02/rev 2-07
|
| Attention | READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
***NEW: Walk-in hours for mylar signatures are: Tuesday and Thursdays from 8am-11am.
If you need other assistance, contact Kristen McClellan at 719.385.7347 to schedule an appointment.
klm 6-08 |
| Approved/Corrected | RE-REVIEW: The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows:
1. The plans were revised to only show the moving of one hydrant.
2. The CSU Fire Flow report is provided and to available flow now meets the requirements of the reduced fire area of 9729 sq ft.
ATTENTION CONTRACTORS: ISSUES LISTED AS "ISSUE RESOLVED" OR "ISSUE APPROVED" ARE ONLY ITEMS FINALIZED FOR PLAN REVIEW. PLAN REVIEW COMMENTS ARE SUBJECT TO FINAL INSPECTIONS, AND "ON SITE" FIRE FLOW TESTS WILL BE REQUIRED PRIOR TO FINALIZING ANY STRUCTURE FOR OCCUPANCY.
|
| Attention | *****(STANDARD COMMENT 2) HYDRANT/BUILDING DATA:
Size of Bldg. 9729 sq ft largest fire area
Construction Type II-B
Fire Sprinklers No
Required GPM: 2000 gpm
# of hydrant(s) required: 2
Max AVG spacing between hydrants: 450 ft
Max hose lay: 225 ft
|
| 3/26/2009 |
FYI | *****(STANDARD COMMENT 1) This project is: Adding one hydrant and moving another for the proposed expansion of Al Serra Hummer 1580 Auto Mall Loop.
SYSTEMS: None.
CN:Code: IBC - IFC - PPRBC /Class: / Const: II-B /Stories: 1 /Size: 14945 /OL:
FH:Required Flow: 2500 gpm /# 3 Hydrants /On site flow:
DV: Proposing to modify the existing Hummer building and convert it to Volkswagen Sales. Proposed SQ FT will be 14,945.
ATTENTION: See our web site for our latest plan review comments for your job at:
www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work. smc - 1-02/rev 2-07
|
| Attention | *****(STANDARD COMMENT 2) HYDRANT/BUILDING DATA:
Size of Bldg. 14945sq ft
Construction Type -- II-B
Fire Sprinklers NO
50% reduction shown on plans - NOTE: 1500 gpm is CSFD minimum flow
Required GPM: 2500 gpm
# of hydrant(s) required: 3
Max AVG spacing between hydrants: 450 ft
Max hose lay: 225 ft
|
| Disapproved | DISAPPROVED: The following information and/or corrections are needed prior to completing a full plan review:
1. Provided the CSU Flow reports for the Hydrants listed on re-lines.
Also:
1) Review all redline comments and address each one.
2) Return ALL red lined plan sets for each re-review.
NOTE: The disapproved items may not constitute a complete list of violations. The designer is to conduct a complete re-review of the plans for additional violations of the standard and incorrect information prior to resubmitting. |
| Attention | READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
***NEW: Walk-in hours for mylar signatures are: Tuesday and Thursdays from 8am-11am.
If you need other assistance, contact Kristen McClellan at 719.385.7347 to schedule an appointment.
klm 6-08 |
| Disapproved | *****(STANDARD COMMENT 25) FIRE FLOW: Provide conformation on the fire flow results from Colorado Springs Utilities. A copy of their report for this area is required to be provided with your plan submittals.
When multiple fire flows are provided from CSU, please indicate all flows on your submitted plans.
Contact the city water department for specific information on water line sizing, water line and hydrant specifications, plan review for water/hydrant systems, water system modeling, water flow information, water flow testing, etc.
NOTE - If you do not have the MODELED fire flow data, contact Keta Donegan, 668-8733 or FAX 668-5651 - she will provide the necessary flow information to you. ATTENTION - Allow 3 business days for Keta to provide the fire flow data. 1/04 dem. |
| FYI | *****(STANDARD COMMENT 3) HYDRANT PAINTING REQUIREMENT: Fire hydrants shall be painted in compliance with Colorado Springs Utilities color coding standards. By using these standards the emergency response crews are provided a quick way to decipher how much water is available from a specific hydrant. The gpm of the hydrant are determined by an actual water flow test, and it is imperative the testing and color coding is accurate. smc 9-07 |
| FYI | *****(STANDARD COMMENT 4) ON SITE FIRE HYDRANT FLOWS:
PRIOR TO THE TIME OF FIRE FINAL INSPECTIONS, on all new construction sites, it will be the responsibility of the owners, GC, or site manager, to have all new and existing fire hydrants, and private water systems flow tested. Per the IFC, all hydrants are to be installed and in service prior to any construction.
**ALL HYDRANT TESTS SHALL BE CONDUCTED BEFORE ON-SITE CONSTRUCTION IS STARTED!!!
As with any new or revised fire protection system, the Fire Department will need to witness all tests to verify the system will meet the fire flow requirements established during the plan review process. If this test occurs without Fire personnel on site, it will be deemed unacceptable by the inspector and will delay the final fire approval. (IFC 2003, Chapter 1) RJG 1/06
Contact SEAN HIGBEE, CSU at 668-4595 to schedule an ACTUAL flow test of CITY OWNED/PUBLIC hydrants. Be sure to provide them with a CSFD plan review number to include with their flow reports.
Contact CSFD Fire Prevention t 385-5982 to schedule a flow test of PRIVATE OWNED hydrants. A contractor capable of performing the test will be required as CSFD Inspectors WITNESS only. dem 1/04 rev smc-9-06 |
| FYI | *****(STANDARD COMMENT 5) This is a PRIVATE system |
| FYI | *****(STANDARD COMMENT 8) GENERAL INSPECTIONS/PLANS & SCHEDULING. Minimum notice of two business days is required for all inspections. Due to work loads, holidays, meetings, vacations, etc...the CSFD cannot guarantee a two business day turnaround on all inspections. PLEASE help yourself by helping us - call your inspections in with ample time to allow adequate scheduling.
When calling, please have your complete CSFD plan review number(s) ready for each inspection request.
( For Example: 2005-1234- HS-2)
The CSFD APPROVED sets of plans SHALL be on site for all inspections.
|
| FYI | *****(STANDARD COMMENT 9) INSPECTOR CHADWELL: STATIONS 10, 15, 17, 20:
Your assigned Inspector is David Chadwell. You may contact him at 719-385-7323 to schedule all construction related inspection activities.
vc-11-05
|
| FYI | *****(STANDARD COMMENT 13) CSFD FEES. Fees for the water submittal will be collected when the building permit is paid. The building permit paid and issued at:
2880 International Circle,
Colorado Springs, CO
80910
vc -01-07 |
| FYI | *****(STANDARD COMMENT 14) If you have any specific questions or concerns about these comments, please feel free to contact me at:
Jonathan R. Milam
Fire Code Examiner
Colorado Springs Fire Department
TEL 719-385-7324
FAX 719-385-7385
fdklm@springsgov.com
**New Walk-In hours are Tuesday and Thursday from 8-11 am. Walk-Ins are for mylar signatures, re-reviews and question about layouts, fire flow, etc. |