NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

STEINMART
05326 NEVADA AV

Review DateStatusComment(s)
10/19/2012 FYI*****(STANDARD COMMENT 1) This project is: Steinmart, 5326 N Nevada Av: new retail store Date of Plans: 10.16.12 You can access our web site for the latest fire department plan review comments: 1. From www.pprbd.org, select PLAN REVIEW then FIND PLANS next COLORADO SPRINGS 2. Scroll down to the correct address. You may then select APPROVED/DISAPPROVED to view comments associated with that particular project.
Attention*****(STANDARD COMMENT 2) BUILDING DATA: Size of Bldg. --31733--- sq ft Construction Type --II-B---- Fire Sprinklers Y---XXX-- N----- Fire Walls Y ----- N -XXX---- Required GPM: ---2000-- gpm # of hydrant(s) required: ---2-- Max AVG spacing between hydrants: ---450-- ft Max hose lay: ---225-- ft
FYI*****(STANDARD COMMENT) FIRE FLOW/HYDRANT REQUIREMENTS MET: On this site the theoretical water flows are --4500-- gpm, and the numbers of hydrant(s) are --2--. This site, based upon the provided theoretical modeled fire flows, appear to meet the minimum flow requirements and/or the number of hydrant(s) for this structure.
Attention(STANDARD COMMENT) READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
FYI(STANDARD COMMENT 6) This is a PUBLIC water system.
FYI*****(13) FIRE DEPARTMENT CONNECTION: FDCs shall be located in a CSFD approved location. The FDC shall be located on the front entrance and/or addressed side of the structure, fully visible and recognizable from the street. FDCs shall be location such that it is not blocked by any means or located behind parked vehicles and such that fire apparatus and hoses connected to the FDC do not obstruct access to building for other fire apparatus. FDCsshall be located within 40-ft of an approved fire department access road. There shall be a fire hydrant capable of supplying the fire flow requirements for the sprinkler system within 100 feet of the FDC. FDCs shall be mounted not less than 18-inches and not more than 4-foot above the level of the adjacent grade or access level. (NFPA 14:6.4.6)
FYI(STANDARD COMMENT 11) JAH - SCHEDULING INSPECTIONS: Your assigned Inspector is Jeff Hanenberg. Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the 2003 International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
10/29/2008 ApprovedRevised plans were submitted due to changes in building construction type - no affect on the required fire flow. Plans are re-approved/signed. Utility service plans were also submitted - those are also approved.
9/30/2008 ApprovedPlans Approved
9/30/2008 DisapprovedDISAPPROVED: The following information and/or corrections are needed prior to completing a full plan review: 1) I need to see original red-lines when submitting for re-reviews. Please bring them when getting final signatures. For reviewer: Verify the FDC for the following were relocated as shown on red-lines: Pad A, Pad E, and Building B. Also, ensure the plan review numbers 2008-0985 thru 2008-1002 show an approved FH. Also: 1) Review all redline comments and address each one. 2) Return ALL red lined plan sets for each re-review. NOTE: The disapproved items may not constitute a complete list of violations. The designer is to conduct a complete re-review of the plans for additional violations of the standard and incorrect information prior to resubmitting.
FYIRE-REVIEW: The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1) hydrant labels were added on 50 scale drawings 2) Hydrant J will remain 3) title sheet and signature blocks provided. 4) CSFD Plan Review Numbers were added to the building data:
AttentionREADY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature. ***NEW: Walk-in hours for mylar signatures are: Tuesday and Thursdays from 8am-11am. If you need other assistance, contact Kristen McClellan at 719.385.7347 to schedule an appointment. klm 6-08
9/30/2008 FYI*****(STANDARD COMMENT 1) This project is: Minor B, University Village Filing No. 1, Northwest of Nevada and Garden of the Gods Rd. ATTENTION: See our web site for our latest plan review comments for your job at: www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work. smc - 1-02/rev 2-07
Attention*****(STANDARD COMMENT 2) HYDRANT/BUILDING DATA: Size of Bldg. 20107 sq ft Construction Type II-B Fire Sprinklers Y(x) N-- 50% reduction shown on plans - NOTE: 1500 gpm is CSFD minimum flow Required GPM: 1500 gpm # of hydrant(s) required: 1 Max AVG spacing between hydrants: 500 ft Max hose lay: 250 ft
DisapprovedDISAPPROVED: The following information and/or corrections are needed prior to completing a full plan review: 1) Add Hydrant Labels (A, B, etc) to hydrants on 50 scale drawings 2) Hydrant J is optional, not required. 3) Provide title sheet and signature blocks for final approval 4) The following buildings and pads require the FDC to be relocated as shown on red-lined plans: Pad A, Pad E, and Building B. 5) Add the following CSFD Plan Review Numbers to the building data: Pad A: 2008-0985-FH-1 Pad B: 2008-0986-FH-1 Building A: 2008-0987-FH-1 Pad C: 2008-0988-FH-1 Pad E: 2008-0989-FH-1 Building B:2008-0990-FH-1 Building G: 2008-0991-FH-1 Building H: 2008-0992-FH-1 Building E: 2008-0993-FH-1 Building F: 2008-0994-FH-1 Building C: 2008-0995-FH-1 Building D: 2008-0996-FH-1 Pad D: 2008-0997-FH-1 Major E: 2008-0998-FH-1 Building I: 2008-0999-FH-1 Minor A: 2008-1000-FH-1 Building J:2008-1001-FH-1 Minor B: 2008-1002-FH-1 6) FYI: FDC's can not be blocked by parking or landscaping. Note: The FDC on Building E is approved at 110'. Note: All square footages provided for pads are the estimated size of the future building. Any change in these square footages must be approved by CSFD. Also: 1) Review all redline comments and address each one. 2) Return ALL red lined plan sets for each re-review. NOTE: The disapproved items may not constitute a complete list of violations. The designer is to conduct a complete re-review of the plans for additional violations of the standard and incorrect information prior to resubmitting.
FYI*****(STANDARD COMMENT 3) HYDRANT PAINTING REQUIREMENT: Fire hydrants shall be painted in compliance with Colorado Springs Utilities color coding standards. By using these standards the emergency response crews are provided a quick way to decipher how much water is available from a specific hydrant. The gpm of the hydrant are determined by an actual water flow test, and it is imperative the testing and color coding is accurate. smc 9-07
FYI*****(STANDARD COMMENT 4) ON SITE FIRE HYDRANT FLOWS: PRIOR TO THE TIME OF FIRE FINAL INSPECTIONS, on all new construction sites, it will be the responsibility of the owners, GC, or site manager, to have all new and existing fire hydrants, and private water systems flow tested. Per the IFC, all hydrants are to be installed and in service prior to any construction. **ALL HYDRANT TESTS SHALL BE CONDUCTED BEFORE ON-SITE CONSTRUCTION IS STARTED!!! As with any new or revised fire protection system, the Fire Department will need to witness all tests to verify the system will meet the fire flow requirements established during the plan review process. If this test occurs without Fire personnel on site, it will be deemed unacceptable by the inspector and will delay the final fire approval. (IFC 2003, Chapter 1) RJG 1/06 Contact SEAN HIGBEE, CSU at 668-4595 to schedule an ACTUAL flow test of CITY OWNED/PUBLIC hydrants. Be sure to provide them with a CSFD plan review number to include with their flow reports. Contact CSFD Fire Prevention t 385-5982 to schedule a flow test of PRIVATE OWNED hydrants. A contractor capable of performing the test will be required as CSFD Inspectors WITNESS only. dem 1/04 rev smc-9-06
FYI*****(STANDARD COMMENT 6) This is a PUBLIC water system.
FYI*****(STANDARD COMMENT 8) GENERAL INSPECTIONS/PLANS & SCHEDULING. Minimum notice of two business days is required for all inspections. Due to work loads, holidays, meetings, vacations, etc...the CSFD cannot guarantee a two business day turnaround on all inspections. PLEASE help yourself by helping us - call your inspections in with ample time to allow adequate scheduling. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( For Example: 2005-1234- HS-2) The CSFD APPROVED sets of plans SHALL be on site for all inspections.
FYI*****(STANDARD COMMENT 12) INSPECTOR JOHNSON: STATIONS 1,3,4,5,13,16 : Your assigned Inspector is Kris Johnson. You may contact him at 719-385-7257 to schedule all construction related inspection activities.
FYI*****(STANDARD COMMENT 13) CSFD FEES. Fees for the water submittal will be collected when the building permit is paid. The building permit paid and issued at: 2880 International Circle, Colorado Springs, CO 80910 vc -01-07
FYI*****(STANDARD COMMENT 14) If you have any specific questions or concerns about these comments, please feel free to contact me at: Kristen McClellan Fire Protection Engineer Colorado Springs Fire Department TEL 719-385-7347 FAX 719-385-7385 fdklm@springsgov.com **New Walk-In hours are Tuesday and Thursday from 8-11 am. Walk-Ins are for mylar signatures, re-reviews and question about layouts, fire flow, etc.
9/30/2008 FYIProject Numbers 2008-0985 thru 2008-1002 have been created for University Village Filing No. 1. However, I have not added the FH Unit to each number. This will be done once I approve the final plan.


 