NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

LDS INSTITUTE - MAIN
01425 AUSTIN BLUFFS PY

Review DateStatusComment(s)
10/27/2009 FYI*****(STANDARD COMMENT 1) This project is: LDS on Austin Bluffs ATTENTION: See our web site for our latest plan review comments for your job at: www.springsgov.com - go to "City Agencies" (tab on the teal bar to get a drop box) - click on - "Fire Department" - (Using the links down the left side of the page), click on - "Web Guide." Once you're into the Web Guide, click on "Plan Review Status" This will also give you access to numerous other items that may assist you in your future project design work. smc - 1-02/rev 2-07
Attention*****(STANDARD COMMENT 2) HYDRANT/BUILDING DATA: Size of Bldg. -- sq ft 5427 Construction Type -- VB Fire Sprinklers Y-xx- N-- 50% reduction shown on plans - NOTE: 1500 gpm is CSFD minimum flow Required GPM: -- gpm 1500 # of hydrant(s) required: -- 1 Max AVG spacing between hydrants: -- ft 500 Max hose lay: -- ft 250
DisapprovedDISAPPROVED: The following information and/or corrections are needed prior to completing a full plan review: 1. Need flow report form CSU. 2. All fire service lines can not all come from a dead-end main. C105.2 IFC 3. Need complete building site to determine hose lay. 4. FDC locations is not defined. 5. What is max pressure on site. PVC max is 175 psi per CSU. Also: 1) Review all redline comments and address each one. 2) Return ALL red lined plan sets for each re-review. NOTE: The disapproved items may not constitute a complete list of violations. The designer is to conduct a complete re-review of the plans for additional violations of the standard and incorrect information prior to resubmitting.
Disapproved*****(STANDARD COMMENT 18) DEAD END MAINS: Unless approved, dead end mains shall not be used when all of the following are located on a single tap main: 1. Automatic fire sprinkler systems. 2. Fire hydrants supporting the Fire Department Connection. 3. Fire hydrants required for external fire protection.


 