| Review Date | Status | Comment(s) |
| 10/6/2009 |
Approved | Plans approved and signed. |
| 7/14/2009 |
FYI | RE-REVIEW: The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows:
Plan Review number has been added.
FDC is approved approximately 200-ft from a hydrant.
ATTENTION CONTRACTORS: ISSUES LISTED AS "ISSUE RESOLVED" OR "ISSUE APPROVED" ARE ONLY ITEMS FINALIZED FOR PLAN REVIEW. PLAN REVIEW COMMENTS ARE SUBJECT TO FINAL INSPECTIONS, AND "ON SITE" FIRE FLOW TESTS WILL BE REQUIRED PRIOR TO FINALIZING ANY STRUCTURE FOR OCCUPANCY.
|
| Attention | READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
***NEW: Walk-in hours for mylar signatures are: Tuesday and Thursdays from 8am-11am.
If you need other assistance, contact Dee Withee at 719.385.7361 to schedule an appointment.
klm 6-08 |
| 7/7/2009 |
Approved | It appears that the best location for the FDC is the Northeast corner of the building, which is 200' from the the nearest existing hydrant. The main entrance to the building is from the east lot, off Costilla. This building required 1 hydrant, is fully sprinkled and has 4 existing hydrant in the area. It is no necessary to require an addition hydrant for the sole purpose of meeting the 100' rule. |
| 6/25/2009 |
Attention | *****(STANDARD COMMENT 2) HYDRANT/BUILDING DATA:
Size of Bldg. 22515 sq ft
Construction Type IIB
Fire Sprinklers Y(x) N--
50% reduction shown on plans - NOTE: 1500 gpm is CSFD minimum flow
Required GPM: 1750 gpm
# of hydrant(s) required: 1
Max AVG spacing between hydrants: 500 ft
Max hose lay: 250 ft
|
| Disapproved | DISAPPROVED: The following information and/or corrections are needed prior to completing a full plan review:
1) Add plan # 2007-0926-FH-1 to plans
2) FDC must be labeled and within 100' of a hydrant, on the address side of the buillding. Please call to discuss possible locations.
Also:
1) Review all redline comments and address each one.
2) Return ALL red lined plan sets for each re-review.
NOTE: The disapproved items may not constitute a complete list of violations. The designer is to conduct a complete re-review of the plans for additional violations of the standard and incorrect information prior to resubmitting. |
| Attention | READY FOR SIGNATURES: The water plans appear ready for signature as long as all disapproved comments have been addressed. Please provide one hard copy for CSFD records along with your final copies for our signature.
***NEW: Walk-in hours for mylar signatures are: Tuesday and Thursdays from 8am-11am.
If you need other assistance, contact Kristen McClellan at 719.385.7347 to schedule an appointment.
klm 6-08 |
| FYI | *****(STANDARD COMMENT 3) HYDRANT PAINTING REQUIREMENT: Fire hydrants shall be painted in compliance with Colorado Springs Utilities color coding standards. By using these standards the emergency response crews are provided a quick way to decipher how much water is available from a specific hydrant. The gpm of the hydrant are determined by an actual water flow test, and it is imperative the testing and color coding is accurate. smc 9-07 |
| FYI | *****(STANDARD COMMENT 4) ON SITE FIRE HYDRANT FLOWS:
PRIOR TO THE TIME OF FIRE FINAL INSPECTIONS, on all new construction sites, it will be the responsibility of the owners, GC, or site manager, to have all new and existing fire hydrants, and private water systems flow tested. Per the IFC, all hydrants are to be installed and in service prior to any construction.
**ALL HYDRANT TESTS SHALL BE CONDUCTED BEFORE ON-SITE CONSTRUCTION IS STARTED!!!
As with any new or revised fire protection system, the Fire Department will need to witness all tests to verify the system will meet the fire flow requirements established during the plan review process. If this test occurs without Fire personnel on site, it will be deemed unacceptable by the inspector and will delay the final fire approval. (IFC 2003, Chapter 1) RJG 1/06
Contact SEAN HIGBEE, CSU at 668-4595 to schedule an ACTUAL flow test of CITY OWNED/PUBLIC hydrants. Be sure to provide them with a CSFD plan review number to include with their flow reports.
Contact CSFD Fire Prevention t 385-5982 to schedule a flow test of PRIVATE OWNED hydrants. A contractor capable of performing the test will be required as CSFD Inspectors WITNESS only. dem 1/04 rev smc-9-06 |
| FYI | *****(STANDARD COMMENT 6) This is a PUBLIC water system. |
| FYI | *****(STANDARD COMMENT 8) GENERAL INSPECTIONS/PLANS & SCHEDULING. Minimum notice of two business days is required for all inspections. Due to work loads, holidays, meetings, vacations, etc...the CSFD cannot guarantee a two business day turnaround on all inspections. PLEASE help yourself by helping us - call your inspections in with ample time to allow adequate scheduling.
When calling, please have your complete CSFD plan review number(s) ready for each inspection request.
( For Example: 2005-1234- HS-2)
The CSFD APPROVED sets of plans SHALL be on site for all inspections.
|
| FYI | *****(STANDARD COMMENT 11) INSPECTOR HANENBERG:
Your assigned Inspector is Jeff Hanenberg. You may contact him at 719-385-7359 to schedule all construction related inspection activities.
|
| FYI | *****(STANDARD COMMENT 13) CSFD FEES. Fees for the water submittal will be collected when the building permit is paid. The building permit paid and issued at:
2880 International Circle,
Colorado Springs, CO
80910
vc -01-07 |
| FYI | *****(STANDARD COMMENT 14) If you have any specific questions or concerns about these comments, please feel free to contact me at:
Kristen McClellan
Fire Protection Engineer
Colorado Springs Fire Department
TEL 719-385-7347
FAX 719-385-7385
fdklm@springsgov.com
**New Walk-In hours are Tuesday and Thursday from 8-11 am. Walk-Ins are for mylar signatures, re-reviews and question about layouts, fire flow, etc. |